Plan Review Notes For Permit 14061270 |
Permit Number |
14061270 |
|
Review Stop |
M |
Sequence Number |
3 |
|
Notes |
Date |
Text |
2014-08-27 15:20:34 | MECHANICAL REVIEW COMMENTS. | | CODE: 2010 FBC. | | | | 1- REVISE EQUIPMENT SIZING CALCULATIONS. SEC. 103.2.2 | | OF 2010 FBC-ENERGY CONSERVATION. | | A) FRONT DOOR DOESN'T FACE EAST. | | B) GLAZING U-VALUE AND SHGC VALUE DOESN'T MATCH THE ONE | | SPECIFIED IN THE ENERGY CALCULATIONS. | | | | 2- REVISE TRANSFER DUCT SIZE SPECIFIED FOR DEN AREA. | | SIZE TO BE MIN. 13" AS REQUIRED BY SEC. M1602.4 OF 2010 | | FBC-RESIDENTIAL. | | | | 3- A/C PLAN TO HAVE THE NAME AND SIGNATURE OF PERSON | | RESPONSIBLE FOR THE DESIGN. SEC. 107.2.1 OF CITY | | AMENDMENTS TO FBC. | | | | IF YOU HAVE ANY QUESTIONS, PLEASE CALL | | JULIO GOMEZ | | COMMERCIAL COMBINATION PLANS EXAMINER | | DEVELOPMENT SERVICES DEPARTMENT | | (561)805-6712 |
|