Plan Review Notes For Permit 14061270 |
Permit Number |
14061270 |
|
Review Stop |
B |
Sequence Number |
3 |
|
Notes |
Date |
Text |
2014-08-27 14:30:49 | BUILDING REVIEW COMMENTS. | | CODE: 2010 FBC. | | | | 1- REVISE THE ENERGY CALCULATIONS: A) REVISE DOOR TYPE | | ON SHEET 3 OF 6 TO MATCH TYPE SHOWN ON PLANS AND | | PRODUCT APPROVALS SUBMITTED. B) REVISE WINDOWS OVERHANG | | DEPTH AND SEPARATION TO MATCH PLANS. | | | | 2- PROVIDE MANUFACTURER'S SPECS SHOWING THE WINDOWS AND | | DOORS U-FACTOR AND SHGC FACTOR SPECIFIED ON THE ENERGY | | CALCULATIONS ON ITEM #7. SEC. 103.2.2 OF 2010 | | FBC-ENERGY CONSERVATION. | | | | 3- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY | | DCA RULE 9N-3 FOR: EXTERIOR DOOR NOA 09-0415.08 | | SUBMITTED NOW ARE FOR NON-IMPACT GLAZED DOORS. PROVIDE | | PRODUCT APPROVAL (2 COPIES) FOR HURRICANE SHUTTERS. | | SEC. 606.4 OF 2010 FBC-EXISTING BUILDING. | | | | 4- ENGINEER OF RECORD TO APPROVE ABOVE PRODUCT | | APPROVAL. SEC. 107.3.4.1 OF CITY AMENDMENTS TO FBC. | | | | 5- PROVIDE COMPLETE INSTALLATION SCHEDULE FOR THE | | INSTALLATION OF THE HURRICANE SHUTTERS. SEC. 107.2.1 | | CITY AMENDMENTS. | | | | IF YOU HAVE ANY QUESTIONS, PLEASE CALL | | JULIO GOMEZ | | COMMERCIAL COMBINATION PLANS EXAMINER | | DEVELOPMENT SERVICES DEPARTMENT | | (561)805-6712 | | [email protected] |
|