2014-08-27 14:30:49BUILDING REVIEW COMMENTS.
 CODE: 2010 FBC.
  
 1- REVISE THE ENERGY CALCULATIONS: A) REVISE DOOR TYPE
 ON SHEET 3 OF 6 TO MATCH TYPE SHOWN ON PLANS AND
 PRODUCT APPROVALS SUBMITTED. B) REVISE WINDOWS OVERHANG
 DEPTH AND SEPARATION TO MATCH PLANS.
  
 2- PROVIDE MANUFACTURER'S SPECS SHOWING THE WINDOWS AND
 DOORS U-FACTOR AND SHGC FACTOR SPECIFIED ON THE ENERGY
 CALCULATIONS ON ITEM #7. SEC. 103.2.2 OF 2010
 FBC-ENERGY CONSERVATION.
  
 3- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY
 DCA RULE 9N-3 FOR: EXTERIOR DOOR NOA 09-0415.08
 SUBMITTED NOW ARE FOR NON-IMPACT GLAZED DOORS. PROVIDE
 PRODUCT APPROVAL (2 COPIES) FOR HURRICANE SHUTTERS.
 SEC. 606.4 OF 2010 FBC-EXISTING BUILDING.
  
 4- ENGINEER OF RECORD TO APPROVE ABOVE PRODUCT
 APPROVAL. SEC. 107.3.4.1 OF CITY AMENDMENTS TO FBC.
  
 5- PROVIDE COMPLETE INSTALLATION SCHEDULE FOR THE
 INSTALLATION OF THE HURRICANE SHUTTERS. SEC. 107.2.1
 CITY AMENDMENTS.
  