2014-08-06 16:49:03RESIDENTIAL (R3) ALTERATION, SECOND MECHANICAL REVIEW
 CHECKLIST.
 CODE: 2010 FBC.
  
 ****NOTE: THERE WAS NOT INFORMATION SUBMITTED TO
 ADDRESS THE COMMENTS ON FIRST REVIEW. PLEASE ADDRESS
 THE FOLLOWING COMMENTS FROM THE FIRST CHECKLIST:
  
  
  
 1- PROVIDE COMPLETE INFORMATION FOR REVIEW:
 A) EQUIPMENT SIZING CALCULATIONS WITH THE EQUIPMENT
 MANUFACTURER AND MODEL AS REQUIRED BY SEC. 403.6 OF
 2010 FBC-ENERGY CONSERVATION.
  
 B) COMPLETE A/C PLAN WITH DUCT SYSTEMS AND EQUIPMENT
 INFORMATION. EQUIPMENT TO MATCH EQUIPMENT SIZING
 CALCULATIONS. SEC. 107.3.5.3(10) OF CITY AMENDMENTS TO
 FBC
  
  