2014-08-06 15:02:36RESIDENTIAL (R3) ALTERATION, SECOND BUILDING REVIEW
 CHECKLIST.
 CODE: 2010 FBC.
  
 1- PROVIDE ENERGY CALCULATIONS. SEC. 101.4.3 AND SEC.
 103 OF 2010 FBC-ENERGY CONSERVATION. (REPEAT COMMENT.
 NOT ADDRESSED).
 (NOTE: THIS IS NOT A CONTRIBUTING HISTORIC HOUSE).
  
 2- ENGINEER TO REVISE THE ROOF SHEATHING INFORMATION
 GIVEN ON SHEET A-1:
 A) NEED TO SPECIFY MIN. 8D RING SHANK NAILS WHICH ARE 2
 1/2" LONG NOT 1 1/4". SEE SEC. R803.2.3.1 OF 2010
 FBC-RESIDENTIAL.
  
 B) ENGINEER TO CLARIFY WHY THE NAILING ZONES ARE PER
 RAS 117?. WHERE IS THIS INFORMATION TAKEN FROM? ROOF
 SHEATHING AND RAS 117 ARE TWO DIFFERENT THINGS. REVISE
 AS REQUIRED. SEC. 107.2.1 CITY AMENDMENTS TO FBC.
  
 3- ENGINEER TO REVISE EXTERIOR DOOR STRUCTURAL BUCK
 DETAIL ON SHEET A-2. NEED TO COMPLY WITH SEC.
 R612.10.2.1 OF 2010 FBC-RESIDENTIAL. NOTE: THE BUCKS
 NEED TO PROVIDE FULL SUPPORT TO THE DOOR FRAMING. 2" X
 4" BUCK DOESN'T PROVIDE FULL SUPPORT TO THE DOOR FRAME.
 SEE DOOR PRODUCT APPROVAL FOR DOOR FRAME SIZE AND
 REVISE AS REQUIRED.
  
 4- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY
 DCA RULE 9N-3 FOR:
 A) USP HC10 AND USP RT18T STRUCTURAL TRUSS CONNECTORS
 SPECIFIED ON DETAILS ON SHEET A-1. ***NOTE: PROVIDE
 ONLY THE PRODUCT APPROVAL COVER PAGE AND PAGE SHOWING
 THE SPECIFIED CONNECTOR. (REPEAT COMMENT NOT
 ADDRESSED).
  
 B) FIXED WINDOWS. NEED TO PROVIDE COMPLETE DRAWINGS.
 DRAWINGS SUBMITTED WITH NOA 10-1015.02 ARE INCOMPLETE
 AND CUT. NEED COMPLETE DRAWINGS. (REPEAT COMMENT. NOT
 ADDRESSED).
  
 C) NEW COMMENT: SINGLE HUNG NOA 11-0404.09 AND EXTERIOR
 DOOR NOA 09-0608.16 SUBMITTED NOW ARE FOR NON-IMPACT
 WINDOWS AND DOORS. THEREFORE, NEED TO PROVIDE PRODUCT
 APPROVAL (2 COPIES) FOR HURRICANE SHUTTERS AS REQUIRED
 BY SEC. 606.4 OF 2010 FBC-EXISTING BUILDING.
  
 5- ENGINEER OF RECORD TO REVIEW AND APPROVE IN WRITING
 ABOVE PRODUCT APPROVALS AS REQUIRED BY SEC. 107.3.4.1
 OF CITY AMENDMENTS TO FBC.
  
 6- PROVIDE COMPLETE INSTALLATION SCHEDULE FOR THE
 INSTALLATION OF THE HURRICANE SHUTTERS. THERE IS A CITY
 HURRICANE SHUTTERS INSTALLATION CHART THAT YOU CAN USE
 OR YOU CAN PROVIDE A DIFFERENT FORMAT THAT PROVIDES ALL
 THE INFORMATION REQUESTED IN THE CITY SAMPLE. SEC.
 107.2.1 CITY AMENDMENTS TO FBC.
  
  
 ***NOTES:
 *PLEASE PROVIDE RESPONSE LETTER ADDRESSING EACH COMMENT
 TO EXPEDITE THE REVIEW PROCESS.
 *PLEASE REPLACE ANY REVISE SHEET.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CALL
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 (561)805-6712
 [email protected]