2014-07-21 11:32:22RESIDENTIAL (R3) ALTERATION, BUILDING REVIEW COMMENTS.
 CODE: 2010 FBC.
  
 1- PROVIDE ENERGY CALCULATIONS. SEC. 101.4.3 OF 2010
 FBC-ENERGY CONSERVATION.
 (NOTE: NOT A CONTRIBUTING HISTORIC HOUSE).
  
 2- ENGINEER TO PROVIDE COMPLETE DETAIL AND
 SPECIFICATIONS FOR GABLE END WALL SHOWING COMPLIANCE
 WITH SEC. R609.4 OF 2010 FBC-RESIDENTIAL.
  
 3- PROVIDE COMPLETE SPECIFICATIONS FOR THE NEW ROOF
 SHEATHING. SPECIFY MATERIAL AND FASTENER TYPE AND
 SPACING. SEE SEC. R803.2.3.1 FOR MINIMUM TYPE OF NAIL
 AND SPACING TO BE USED, INCLUDING ROOF ZONE #3.
  
 4- PROVIDE COMPLETE SPECIFICATIONS FOR THE ROOF
 VENTILATION AS REQUIRED BY SEC. R806.
  
 5- A) REVISE ALL WINDOW STRUCTURAL BUCK DETAILS ON
 SHEET A-2. PROVIDE COMPLETE SPECIFICATIONS FOR SIZE AND
 FASTENING OF WINDOW BUCKS. REVISE DETAILS TO COMPLY
 WITH SEC. R612.10.2.1 OF 2010 FBC-RESIDENTIAL. NOTE:
 THE BUCKS NEED TO PROVIDE FULL SUPPORT TO THE WINDOW
 FRAMING. REVISE DETAILS AS REQUIRED.
  
 B) PROVIDE COMPLETE STRUCTURAL BUCK DETAIL FOR DOORS.
 SEC. R612.10.2.1. COORDINATE WITH COMMENT 5(A) ABOVE.
  
 6- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY
 DCA RULE 9N-3 FOR:
 A) SINGLE HUNG WINDOWS TO BE INSTALLED.
  
 B) WINDOW MULLIONS. AND CLEARLY IDENTIFY MULLION SIZE
 AND FASTENING TO VERIFY COMPLIANCE WITH THE DESIGN
 PRESSURES.
  
 C) USP HC10 AND USP RT18T STRUCTURAL TRUSS CONNECTORS
 SPECIFIED ON DETAILS. ***NOTE: PROVIDE ONLY THE PRODUCT
 APPROVAL COVER PAGE AND PAGE SHOWING THE SPECIFIED
 CONNECTOR
  
 D) FIXED WINDOWS. NEED TO PROVIDE COMPLETE DRAWINGS.
 DRAWINGS SUBMITTED WITH NOA 10-1015.02 ARE CUT. NEED
 COMPLETE DRAWINGS.
  
 7- ENGINEER OF RECORD TO REVIEW AND APPROVE IN WRITING
 (NOT SIGNING AND SEALING) ALL THE PRODUCT APPROVALS AS
 REQUIRED BY SEC. 107.3.4.1 OF CITY AMENDMENTS TO FBC.
  
 8- BEDROOM WINDOWS TO BE REPLACED: SPECIFY EXISTING
 TYPE AND SIZE OF EXITING WINDOWS TO BE REPLACED TO
 VERIFY COMPLIANCE WITH THE EGRESS REQUIREMENTS OF SEC.
 604.1 OF 2010 FBC-EXISTING BUILDING.
  
 9- REVISE WINDOW SCHEDULE. THERE ARE NO ALUMINUM CLAD
 WOOD WINDOWS. SEE PRODUCT APPROVALS SUBMITTED AND
 REVISE AS REQUIRED. SEC. 103.2.2 OF 2010 FBC-ENERGY
 CONSERVATION.
  
 ***NOTE: PLEASE PROVIDE RESPONSE LETTER ADDRESSING EACH
 COMMENT TO EXPEDITE THE REVIEW PROCESS...
  