Plan Review Notes
Plan Review Notes For Permit 14061239
Permit Number 14061239
Review Stop B
Sequence Number 2
Notes
Date Text
2014-08-22 18:33:43****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 COMMENTS FROM PREVIOUS LIST:
  
 1. SPECIFICATIONS, ITEM B, STATES "MOUNT CABINET TO
 WALL WITH 1/4" X 3" TAPCON SCREWS (SEE DRAWING FOR
 LOCATIONS."
  
 REPEAT COMMENT FOR THIS ENGINEER - PLAN IS TO INCLUDE
 FASTENING PATTERN OR MINIMUM NUMBER REQUIRED. A SET HAS
 BEEN RETAINED.
  
 2ND REVIEW, PLAN NOT REVISED. A SET HAS BEEN RETAINED.
  
 2. AS ONLY ONE SET WAS PROVIDED, TWO COMPLETE SETS OF
 PLANS WILL BE REQUIRED AT RESUBMITTAL.
  
 2ND REVIEW, WHEN RESUBMITTING, PROVIDE TWO COMPLETE
 SETS OF PLANS.
  
 NEW COMMENT:
  
 3. ITEM L, CHANNEL LETTERS DO NOT HAVE A SPECIFICATION
 FOR FASTENING. MINIMUM REQUIREMENTS - DIAMETER, LENGTH,
 TYPE, AND NUMBER REQUIRED OR FASTENING PATTERN. REPEAT
 COMMENT FOR THIS ENGINEER.
  
  