Notes |
Date |
Text |
2014-06-30 15:46:11 | ****CORRECTIONS**** | | | | SAMANTHA HILL | | BUILDING PLANS EXAMINER | | [email protected] | | 561-805-6724 | | | | 1. REVISE FLOOR PLAN TO PROVIDE THE FOLLOWING | | INFORMATION FOR BEDROOMS; FBC R310, FBC EB 604.1. THE | | CLEAR OPENING CANNOT BE REDUCED BY MORE THAN 5%: | | | | REVISE PLAN TO STATE WHAT TYPE OF WINDOW IS THERE NOW | | IN THE BEDROOMS - AWNING, CASEMENT, SINGLE HUNG? | | | | REVISE PLAN TO STATE WHAT THE EXISTING CLEAR OPENING | | DIMENSIONS ARE. CLEAR OPENING IS THE OPENING WHICH | | EXISTS WHEN THE WINDOW IS FULLY OPEN. | | | | REVISE PLAN TO STATE WHAT THE PROPOSED CLEAR OPENING | | DIMENSIONS ARE. THIS CAN BE OBTAINED FROM THE | | MANUFACTURER | | | | |
|