Plan Review Notes
Plan Review Notes For Permit 14061219
Permit Number 14061219
Review Stop B
Sequence Number 1
Notes
Date Text
2014-07-17 14:07:24BUILDING REVIEW APPROVED WITH PROVISO:
  
 1- REVISE ENERGY CALCULATIONS FORM 402-2010 SUBMITTED:
 A) NEED TO INSTALL ALL THE VALUES THAT ARE LISTED ON
 TABLE 402A (SECOND PAGE) OF FORM SUBMITTED. REVISE PAGE
 ONE AND PAGE TWO AS REQUIRED.
  
 ***NOTE:
 PERFORMANCE FORM 405 MAY ALSO BE USED INSTEAD OF THE
 PRESCRIPTIVE FORM 402. ( ALL THE REQUIREMENTS OF
 PRESCRIPTIVE FORM 402 MUST BE INSTALLED AND NEED TO
 PROVIDE MORE INFORMATION SHOWING HOW ACHIEVING THOSE
 VALUES LISTED IN TABLE 402A)
  
 2- PROVIDE PRODUCT APPROVAL FOR:
 A) NON-IMPACT SINGLE HUNG WINDOWS.
  
 B) WINDOW MULLIONS.
  
 3- ABOVE PRODUCT APPROVALS NEED TO BE REVIEWED AND
 APPROVED IN WRITING BY THE ENGINEER OF RECORD.
  
 4- PROVIDE COMPLETE INSTALLATION SCHEDULE FOR THE STORM
 SHUTTERS. SEE CITY SAMPLE.