Date |
Text |
2016-04-09 06:34:23 | 1) SHT. A0.04 SHOWS A GENERATOR. SUBMIT MAUFACTURER'S |
| SPECIFICATION SHEETS FOR THE EMERGENCY GENERATOR. |
| SUBMIT COMPLETE PIPING DIAGRAMS, LOCATION & CAPACITY OF |
| TANKS. FBC 107.1. THE GENERATOR SHALL COMPLY WITH NFPA |
| 37 & 110. |
| 2) SHT.C-09 - THE PLANS SHOW A 2 INCH WATER SERVICE AND |
| A 2 INCH IRRIGATION LINE WITH 1 1/2 INCH BACKFLOW |
| PREVENTERS INSTALLED ON THEM. THE BACKFLOW DEVICES |
| SHOULD BE THE SAME SIZE AS THE WATER SERVICE. |
| 3) SHT.A 2.00 - A MINIMUM OF TWO DRINKING FOUNTAINS ARE |
| REQUIRED FOR LEVEL 1 BUSINESS OCCUPANCY IN ACCORDANCE |
| WITH THE 2010 FBC - ACCESSIBILITY SEC.211.2 AND 2010 |
| FBC-PLUMBING TABLE 403.1 & FOOTNOTE (E). |
| 4) SHT.A0.05 - WHY ARE THE DRINKING FOUNTAINS LOCATED |
| IN THE GYM ROOM? THE DRINKING FOUNTAINS SHALL BE |
| LOCATED IN A COMMON AREA FOR ALL TO USE. 2010 FPC SEC. |
| 403.3.1. |
| 5) SHT. A7.00 - THE PLUMBING FIXTURE REQUIREMENT TABLE |
| LISTS THE OCCUPANT LOAD OF THE SUN DECK AS 96 PERSONS |
| AND AT THE BOTTOM OF THE TABLE THE OCCUPANT LOAD IS |
| SHOWN AS 124 PERSONS. WHICH IS IT, 96 PERSONS OR 124 |
| PERSONS? CLARIFY. |
| 6) THE HEIGHT OF THE SINK COUNTER IN THE BREAK ROOM |
| #M11 SHALL BE A MAXIMUM OF 34 INCHES ABOVE THE FINISH |
| FLOOR PER 2010 ACCESSIBILITY SEC.606.3. |
| 7) SHT. P 4.04 - SUBMIT CONFIRMATION/VERIFICATION FROM |
| SCHIER THAT THEY HAVE PERFORMED FACTORY SIZING |
| CALCULATIONS FOR THE GREASE INTERCEPTORS AND SUBMIT 2 |
| COPIES OF THE SIZING CALCULATIONS THAT HAVE BEEN DONE |
| BY SCHIER. 2010 FBC SEC. 1003.2. |
| 8) PLUMBING SHEETS - THE WAY THE PLANS HAVE BEEN |
| STAPLED I CANNOT SEE CERTAIN DETAILS AND CANNOT REVIEW |
| THE COMPLETE PLAN. PLEASE ATTACH THE SHEETS SO THAT ALL |
| DETAILS AND NOTES CAN BE READ. FBC 107.1. |
| 9) INDICATE THE SLOPE (PITCH) OF THE HORIZONTAL |
| STORMWATER SYSTEM ON SHT.P 309. FBC 107.1. COMPLY WITH |
| TABLE 1106.3 OF 2010 FPC. |
| 10) SHT. P 107- RWL #1 IS SHOWN AS 4 INCH AND ON SHT. P |
| 308 IT IS SHOWN AS 6 INCH. CLARIFY. |
| 11) SHT. P 107 - RWL #4 IS SHOWN AS 4 INCH BUT ON SHT. |
| P 308 IT IS SHOWN AS 6 INCH. CLARIFY. |
| 12) SHT. P 301 - THERE IS NO COLD WATER TO THE HI-LO |
| DRINKING FOUNTAIN. |
| 13) SHTS.107 & 108 - THE ROOF DRAIN CALCULATION TABLE |
| SHOWS THE RAINWATER LEADERS AS 4 INCH BUT SHEETS 308 & |
| 309 SHOW SOME OF THE SAME RISERS AS 6 INCH. ALSO, ON |
| SHT. P 308 THERE IS A RISER LABELED AS #6 BUT THERE IS |
| NO RISER LABELED #6 IN THE ROOF DRAIN CALCULATION |
| TABLE. CLARIFY. |
| 14) SHT. P 201 - IDENTIFY/LABEL ALL OF THE RISERS ON |
| THE TYPICAL GUESTROOMS FLOOR PLAN SO A COMPREHENSIVE |
| PLAN REVIEW CAN BE DDONE TO ENSURE THEY CORRELATE WITH |
| THE RISER DIAGRAMS. FBC 107.3.5.1.3. |
| 15) SHT. P 302 - SIZE ALL THE WATER LINES ON THE LEVEL |
| 1 CW-HW-HWR WATER ISOMETRIC. FBC 107.1. |
| 16) SHT. P 306 - SUPPLY THE PLUMBING SYMBOL LEGEND AND |
| CODED NOTES FOR THIS SHEET. 2ND REQUEST. |
| 17) SHT. P 307 - SIZE THE DRAIN AT THE INLET OF THE |
| INTERCEPTOR, THE DRAIN AT THE OUTLET AND THE SECTION OF |
| PIPE BETWEEN THE TWO INTERCEPTORS. |
| 18) SHT. P 309 - SIZE THE GAS LINES DOWNSTREAM OF THE |
| SECOND STAGE REGULATORS. |
| 19) SHT. P 306 - SHOWS SANITARY RISER VII ON THE RISER |
| DIAGRAM BUT IT IS NOT SHOWN ON THE FLOOR PLANS ON SHTS. |
| P 103 & P 104. CLARIFY. |
| 20) SHT. P 104 - LABEL THE VENT SHOWN ON SHT. P 104, |
| LOCATED IN FLEX SPACE #2, UNIT 307, LOCATED IN THE WALL |
| BY THE AIRWALL #304. |
| 21) P 104 - LABEL THE VENT IN THE WALL BETWEEN STORAGE |
| ROOMS #300 # 301. |
| 22) LABEL ALL VENTS THAT ARE SHOWN AS "VENT UP" OR |
| "VENT DOWN." |
| 23) SHT. P 306 - RISERS # II, III, & IV - THE NUMBER |
| AND TYPE OF FIXTURES PERMITTED ON A HORIZONTAL WET VENT |
| IS EXCEEDED. REFER TO 2010 FPC DEFINITION OF A BATHROOM |
| GROUP AND FPC SEC.909.1. REFER TO ROOM NUMBERS |
| 202,203,206, AND 207 & SHEET P 103. |
| 24) SHT. P 307 THE DRAIN LINE FROM THE ELEVATOR SUMP #1 |
| IS SHOWN AS DRAINING 100 F.U.CLARIFY. THERE IS A 4 INCH |
| DRAININ THE SAME AREA DRAINING 156 F.U. CORRECT THE |
| FIXTURE LOADS. |
| 25) SHT. P 306 - LABEL THE SANITARY RISER FOR THE GYM |
| TOILET (#216) AND TOILET ROOM #222. |
| 26) SHT.P 307 - SANITARY GROUND FLOOR ISOMETRIC ? SHOWS |
| A 6 INCH DRAIN WITH 497 FIXTURE UNITS DISCHARGING INTO |
| A 4 INCH LINE FLOWING 665 UNITS. THE SIX INCH LINE |
| CANNOT DISCHARGE INTO A 4 INCH LINE AND THE 4 INCH LINE |
| IS UNDERSIZED. CHECK THE FIXTURE UNIT LOAD FOR THE |
| SANITARY GROUND FLOOR ISOMETRIC.2010 FPC SEC.704.2. |
| 27) SHT. P 307 - CHECK THE FIXTURE UNIT LOAD FOR THE |
| ENTIRE RISER. THERE ARE DRAINS WITH ONE FIXTURE |
| DISCHARGING INTO THEM AND THE FIXTURE LOAD IS SHOWN AS |
| 100, 200 & 300 F.U. AND SOME LINES ARE UNDERSIZED. |
| CLARIFY, |
| 28) SHT. P307 - THE MINIMUM SIZE VENT FOR A SIX INCH |
| DRAIN SHALL COMPLY WITH 2010 FPC SEC.916.1 & TABLE |
| 916.1. THE DIAMETER OF THE VENT PIPE SHALL BE NO LESS |
| THAN ONE-HALF THE DIAMETER OF THE DRAIN SERVED. |
| 29) SHT. P 303 - THE WATER RISER FOR THE MEZZANINE |
| LEVEL HAS ONLY A FEW PIPE SIZES SHOWN. SIZE ALL |
| SECTIONS OF THE WATER RISER. FBC SEC. 107.1. |
| 30) SHT. P 304 RISER C THE NUMBER AND TYPE OF FIXTURES |
| ALLOWED ON A HORIZONTAL WET VENT IS EXCEEDED. SEE THE |
| DEFINITION OF "BATHROOM GROUP" IN CHAPTER 2 AND ALSO |
| SEC. 909.1 OF 2010 FPC. |
| 31) SHT. P 303 - THE WATER RISERS TO THE ROOMS ARE ONLY |
| SHOWING A FEW PIPE SIZES. SIZE THE WATER RISERS IN |
| THEIR ENTIRETY. NOTE: IS IT THE INTENT OF THE DESIGNER |
| THAT A PIPE SIZE WILL REMAIN CONSTANT UNTIL A NEW SIZE |
| IS SHOWN IN THE RISER AND THIS IS THE REASON THAT |
| SECTIONS OF THE WATER RISERS ARE NOT SIZED? IF SO, |
| PLACE A NOTE ON THE PLANS TO THIS EFFECT. IF NOT, THEN |
| SIZE THE WATER RISERS IN THEIR ENTIRETY. FBC 107.1. |
| 32) SHT. P 305 - SHOWS A 2 INCH SANITARY UP TO THE |
| ROOF. LABEL THE RISER IN ORDER FOR IDENTIFYING THE |
| LOCATION ON THE ROOF AND ALSO ON P 107. |
| 33) SHT. P 401 - THE BOOSTER PUMP SHALL BE EQUIPPED |
| WITH A LOW PRESSURE CUTOFF PER 2010 FPC SEC. |
| 606.5.5.THE RESPONSE NARRATIVE STATES THAT A NOTE WAS |
| ADDED ON SHT. P 401 BUT I COULD NOT FIND THIS NOTE. |
| CLARIFY. |
| 34) WATER HAMMER ARRESTORS SHALL BE INSTALLED ON ALL |
| QUICK CLOSING VALVES. AIR CHAMBERS ARE NOT APPROVED. |
| 2010 FPC SEC. 604.9.THE NARRATIVE RESPONSE STATES THAT |
| A NOTE WAS ADDED ON SHT. P 402 BUT I CANNOT FIND THE |
| NOTE. CLARIFY. |
| 35) SHT. P 402 - THERE IS STILL A NOTE REFERRING TO A |
| MIAMI - DADE ORDINANCE FOR PLUMBING FIXTURE |
| REQUIREMENTS. REMOVE THE NOTE AS IT DOES NOT APPLY TO |
| THIS PROJECT. |
| 36) THE DRAINAGE STACKS HAVE HORIZONTAL OFFSETS THAT |
| OCCUR ON THE 2ND, 3RD & 4TH FLOORS AND MUST COMPLY WITH |
| THE 2010 FPC SEC.915 WHERE FIVE OR MORE BRANCH |
| INTERVALS ARE LOCATED ABOVE THE OFFSET. REFER ALSO TO |
| FPC SECS. 915.2 & 915.3. |
| 37) THIS BUILDING IS OVER 10 BRANCH INTERVALS. THE 2010 |
| FPC SEC. 914 REQUIRES THAT SOIL AND WASTE STACKS IN |
| BUILDINGS HAVING MORE THAN 10 BRANCH INTERVALS SHALL BE |
| PROVIDED WITH A RELIEF VENT AT EACH TENTH INTERVAL |
| INSTALLED, BEGINNING WITH THE TOP FLOOR. |
| |
| |
| PLUMBING PLAN REVIEW |
| TIM LARGE |
| CHIEF PLUMBING INSPECTOR |
| 561-805-6692 |
| [email protected] |
| |
| |
| |
| |
| |
| |
| |
| |
| |
| |
| |
| |
| |
| |
| |
| |
| |
| |
| |
| REVIEW NOT COMPLETE |
| |