Plan Review Notes
Plan Review Notes For Permit 14061217
Permit Number 14061217
Review Stop P
Sequence Number 3
Notes
Date Text
2016-04-09 06:34:231) SHT. A0.04 SHOWS A GENERATOR. SUBMIT MAUFACTURER'S
 SPECIFICATION SHEETS FOR THE EMERGENCY GENERATOR.
 SUBMIT COMPLETE PIPING DIAGRAMS, LOCATION & CAPACITY OF
 TANKS. FBC 107.1. THE GENERATOR SHALL COMPLY WITH NFPA
 37 & 110.
 2) SHT.C-09 - THE PLANS SHOW A 2 INCH WATER SERVICE AND
 A 2 INCH IRRIGATION LINE WITH 1 1/2 INCH BACKFLOW
 PREVENTERS INSTALLED ON THEM. THE BACKFLOW DEVICES
 SHOULD BE THE SAME SIZE AS THE WATER SERVICE.
 3) SHT.A 2.00 - A MINIMUM OF TWO DRINKING FOUNTAINS ARE
 REQUIRED FOR LEVEL 1 BUSINESS OCCUPANCY IN ACCORDANCE
 WITH THE 2010 FBC - ACCESSIBILITY SEC.211.2 AND 2010
 FBC-PLUMBING TABLE 403.1 & FOOTNOTE (E).
 4) SHT.A0.05 - WHY ARE THE DRINKING FOUNTAINS LOCATED
 IN THE GYM ROOM? THE DRINKING FOUNTAINS SHALL BE
 LOCATED IN A COMMON AREA FOR ALL TO USE. 2010 FPC SEC.
 403.3.1.
 5) SHT. A7.00 - THE PLUMBING FIXTURE REQUIREMENT TABLE
 LISTS THE OCCUPANT LOAD OF THE SUN DECK AS 96 PERSONS
 AND AT THE BOTTOM OF THE TABLE THE OCCUPANT LOAD IS
 SHOWN AS 124 PERSONS. WHICH IS IT, 96 PERSONS OR 124
 PERSONS? CLARIFY.
 6) THE HEIGHT OF THE SINK COUNTER IN THE BREAK ROOM
 #M11 SHALL BE A MAXIMUM OF 34 INCHES ABOVE THE FINISH
 FLOOR PER 2010 ACCESSIBILITY SEC.606.3.
 7) SHT. P 4.04 - SUBMIT CONFIRMATION/VERIFICATION FROM
 SCHIER THAT THEY HAVE PERFORMED FACTORY SIZING
 CALCULATIONS FOR THE GREASE INTERCEPTORS AND SUBMIT 2
 COPIES OF THE SIZING CALCULATIONS THAT HAVE BEEN DONE
 BY SCHIER. 2010 FBC SEC. 1003.2.
 8) PLUMBING SHEETS - THE WAY THE PLANS HAVE BEEN
 STAPLED I CANNOT SEE CERTAIN DETAILS AND CANNOT REVIEW
 THE COMPLETE PLAN. PLEASE ATTACH THE SHEETS SO THAT ALL
 DETAILS AND NOTES CAN BE READ. FBC 107.1.
 9) INDICATE THE SLOPE (PITCH) OF THE HORIZONTAL
 STORMWATER SYSTEM ON SHT.P 309. FBC 107.1. COMPLY WITH
 TABLE 1106.3 OF 2010 FPC.
 10) SHT. P 107- RWL #1 IS SHOWN AS 4 INCH AND ON SHT. P
 308 IT IS SHOWN AS 6 INCH. CLARIFY.
 11) SHT. P 107 - RWL #4 IS SHOWN AS 4 INCH BUT ON SHT.
 P 308 IT IS SHOWN AS 6 INCH. CLARIFY.
 12) SHT. P 301 - THERE IS NO COLD WATER TO THE HI-LO
 DRINKING FOUNTAIN.
 13) SHTS.107 & 108 - THE ROOF DRAIN CALCULATION TABLE
 SHOWS THE RAINWATER LEADERS AS 4 INCH BUT SHEETS 308 &
 309 SHOW SOME OF THE SAME RISERS AS 6 INCH. ALSO, ON
 SHT. P 308 THERE IS A RISER LABELED AS #6 BUT THERE IS
 NO RISER LABELED #6 IN THE ROOF DRAIN CALCULATION
 TABLE. CLARIFY.
 14) SHT. P 201 - IDENTIFY/LABEL ALL OF THE RISERS ON
 THE TYPICAL GUESTROOMS FLOOR PLAN SO A COMPREHENSIVE
 PLAN REVIEW CAN BE DDONE TO ENSURE THEY CORRELATE WITH
 THE RISER DIAGRAMS. FBC 107.3.5.1.3.
 15) SHT. P 302 - SIZE ALL THE WATER LINES ON THE LEVEL
 1 CW-HW-HWR WATER ISOMETRIC. FBC 107.1.
 16) SHT. P 306 - SUPPLY THE PLUMBING SYMBOL LEGEND AND
 CODED NOTES FOR THIS SHEET. 2ND REQUEST.
 17) SHT. P 307 - SIZE THE DRAIN AT THE INLET OF THE
 INTERCEPTOR, THE DRAIN AT THE OUTLET AND THE SECTION OF
 PIPE BETWEEN THE TWO INTERCEPTORS.
 18) SHT. P 309 - SIZE THE GAS LINES DOWNSTREAM OF THE
 SECOND STAGE REGULATORS.
 19) SHT. P 306 - SHOWS SANITARY RISER VII ON THE RISER
 DIAGRAM BUT IT IS NOT SHOWN ON THE FLOOR PLANS ON SHTS.
 P 103 & P 104. CLARIFY.
 20) SHT. P 104 - LABEL THE VENT SHOWN ON SHT. P 104,
 LOCATED IN FLEX SPACE #2, UNIT 307, LOCATED IN THE WALL
 BY THE AIRWALL #304.
 21) P 104 - LABEL THE VENT IN THE WALL BETWEEN STORAGE
 ROOMS #300 # 301.
 22) LABEL ALL VENTS THAT ARE SHOWN AS "VENT UP" OR
 "VENT DOWN."
 23) SHT. P 306 - RISERS # II, III, & IV - THE NUMBER
 AND TYPE OF FIXTURES PERMITTED ON A HORIZONTAL WET VENT
 IS EXCEEDED. REFER TO 2010 FPC DEFINITION OF A BATHROOM
 GROUP AND FPC SEC.909.1. REFER TO ROOM NUMBERS
 202,203,206, AND 207 & SHEET P 103.
 24) SHT. P 307 THE DRAIN LINE FROM THE ELEVATOR SUMP #1
 IS SHOWN AS DRAINING 100 F.U.CLARIFY. THERE IS A 4 INCH
 DRAININ THE SAME AREA DRAINING 156 F.U. CORRECT THE
 FIXTURE LOADS.
 25) SHT. P 306 - LABEL THE SANITARY RISER FOR THE GYM
 TOILET (#216) AND TOILET ROOM #222.
 26) SHT.P 307 - SANITARY GROUND FLOOR ISOMETRIC ? SHOWS
 A 6 INCH DRAIN WITH 497 FIXTURE UNITS DISCHARGING INTO
 A 4 INCH LINE FLOWING 665 UNITS. THE SIX INCH LINE
 CANNOT DISCHARGE INTO A 4 INCH LINE AND THE 4 INCH LINE
 IS UNDERSIZED. CHECK THE FIXTURE UNIT LOAD FOR THE
 SANITARY GROUND FLOOR ISOMETRIC.2010 FPC SEC.704.2.
 27) SHT. P 307 - CHECK THE FIXTURE UNIT LOAD FOR THE
 ENTIRE RISER. THERE ARE DRAINS WITH ONE FIXTURE
 DISCHARGING INTO THEM AND THE FIXTURE LOAD IS SHOWN AS
 100, 200 & 300 F.U. AND SOME LINES ARE UNDERSIZED.
 CLARIFY,
 28) SHT. P307 - THE MINIMUM SIZE VENT FOR A SIX INCH
 DRAIN SHALL COMPLY WITH 2010 FPC SEC.916.1 & TABLE
 916.1. THE DIAMETER OF THE VENT PIPE SHALL BE NO LESS
 THAN ONE-HALF THE DIAMETER OF THE DRAIN SERVED.
 29) SHT. P 303 - THE WATER RISER FOR THE MEZZANINE
 LEVEL HAS ONLY A FEW PIPE SIZES SHOWN. SIZE ALL
 SECTIONS OF THE WATER RISER. FBC SEC. 107.1.
 30) SHT. P 304 RISER C THE NUMBER AND TYPE OF FIXTURES
 ALLOWED ON A HORIZONTAL WET VENT IS EXCEEDED. SEE THE
 DEFINITION OF "BATHROOM GROUP" IN CHAPTER 2 AND ALSO
 SEC. 909.1 OF 2010 FPC.
 31) SHT. P 303 - THE WATER RISERS TO THE ROOMS ARE ONLY
 SHOWING A FEW PIPE SIZES. SIZE THE WATER RISERS IN
 THEIR ENTIRETY. NOTE: IS IT THE INTENT OF THE DESIGNER
 THAT A PIPE SIZE WILL REMAIN CONSTANT UNTIL A NEW SIZE
 IS SHOWN IN THE RISER AND THIS IS THE REASON THAT
 SECTIONS OF THE WATER RISERS ARE NOT SIZED? IF SO,
 PLACE A NOTE ON THE PLANS TO THIS EFFECT. IF NOT, THEN
 SIZE THE WATER RISERS IN THEIR ENTIRETY. FBC 107.1.
 32) SHT. P 305 - SHOWS A 2 INCH SANITARY UP TO THE
 ROOF. LABEL THE RISER IN ORDER FOR IDENTIFYING THE
 LOCATION ON THE ROOF AND ALSO ON P 107.
 33) SHT. P 401 - THE BOOSTER PUMP SHALL BE EQUIPPED
 WITH A LOW PRESSURE CUTOFF PER 2010 FPC SEC.
 606.5.5.THE RESPONSE NARRATIVE STATES THAT A NOTE WAS
 ADDED ON SHT. P 401 BUT I COULD NOT FIND THIS NOTE.
 CLARIFY.
 34) WATER HAMMER ARRESTORS SHALL BE INSTALLED ON ALL
 QUICK CLOSING VALVES. AIR CHAMBERS ARE NOT APPROVED.
 2010 FPC SEC. 604.9.THE NARRATIVE RESPONSE STATES THAT
 A NOTE WAS ADDED ON SHT. P 402 BUT I CANNOT FIND THE
 NOTE. CLARIFY.
 35) SHT. P 402 - THERE IS STILL A NOTE REFERRING TO A
 MIAMI - DADE ORDINANCE FOR PLUMBING FIXTURE
 REQUIREMENTS. REMOVE THE NOTE AS IT DOES NOT APPLY TO
 THIS PROJECT.
 36) THE DRAINAGE STACKS HAVE HORIZONTAL OFFSETS THAT
 OCCUR ON THE 2ND, 3RD & 4TH FLOORS AND MUST COMPLY WITH
 THE 2010 FPC SEC.915 WHERE FIVE OR MORE BRANCH
 INTERVALS ARE LOCATED ABOVE THE OFFSET. REFER ALSO TO
 FPC SECS. 915.2 & 915.3.
 37) THIS BUILDING IS OVER 10 BRANCH INTERVALS. THE 2010
 FPC SEC. 914 REQUIRES THAT SOIL AND WASTE STACKS IN
 BUILDINGS HAVING MORE THAN 10 BRANCH INTERVALS SHALL BE
 PROVIDED WITH A RELIEF VENT AT EACH TENTH INTERVAL
 INSTALLED, BEGINNING WITH THE TOP FLOOR.
  
  
 PLUMBING PLAN REVIEW
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 561-805-6692
 [email protected]
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
 REVIEW NOT COMPLETE
  