Plan Review Notes
Plan Review Notes For Permit 14061217
Permit Number 14061217
Review Stop E
Sequence Number 3
Notes
Date Text
2016-03-17 15:45:123RD ELECTRICAL REVIEW NOTES FOR PERMIT 14061217
 REVIEWED FOR COMPLIANCE WITH: 2010 FBC & NEC 2008
  
 BELOW ARE THE COMMENTS RESPONSES TO THE SECOND REVIEW.
 TO SIMPLIFY MATTERS I HAVE USED THE SAME FORMAT OF THE
 PREVIOUS REVIEW AND DELETED ALL THE SATISFACTORILY
 ADDRESSED AND ONLY LEFT THE ONES REQUIRING FURTHER
 ATTENTION. FURTHERMORE, ALL SHOW WINDOW AND SIGN OUTLET
 REQUIREMENTS HAVE BEEN DEFFERED TO THE TENANT
 BUILD-OUT.
  
 PAGE 201
 2. PER THE SAME CODE, AUTOMATIC LIGHTING CONTROLS ARE
 REQUIRED IN THE ENTRY HALLWAYS.
 (A) PER FBC-E 505.2.1 EVERY AREA ENCLOSED BY WALLS OR
 FLOOR TO CEILING PARTITIONS SHALL HAVE AT LEAST ONE
 CONTROL DEVICE TO CONTROL THE LIGHTING WITHIN THE
 SPACE. THIS MEANS SEPARATE LIGHT SWITCHES ARE REQUIRED
 IN THE TOILET AREA, MAIN BATH AREA AND CLOSET.
 FURTHERMORE, FBC-M SECTION 401.3 REQUIRES THAT
 VENTILATION BE PROVIDED WHENEVER THE SPACE IS OCCUPIED
 THEREFORE THE EXHAUST FANS SHALL BE TIED TO THE
 LIGHTING.
 3. THERE ARE NO ELECTRICAL OUTLETS SHOWN ON THE
 DRAWINGS FOR THE GUEST ROOMS. GUEST ROOM OUTLETS SHALL
 BE INSTALLED AND SPACED ACCORDING TO NEC 210.52 (A) &
 (D).
 (A) RECEPTACLES AS INDICATED ON PLANS DO NOT COMPLY
 WITH THE MINIMUM CODE REQUIREMENTS OF NEC 210.52(A)(1).
 4. THOUGH NEC REQUIRES TAMPER?RESISTANT RECEPTACLES FOR
 DWELLING UNITS NOT SPECIFICALLY GUEST ROOMS, THE
 INSTALLATION OF TAMPER?RESISTANT DEVICES IS A
 SUGGESTION.
 (A) RESPONSE COMPLIANT W/NEC 2008 THOUGH REQUIRED IN
 CURRENT CODE.
  
 PAGE 301
 1. THERE IS NO LIGHTING REFLECTED FOR THE VARIOUS
 ROOMS. AS PER THE VARIOUS CODES ALL THESE ROOMS REQUIRE
 ILLUMINATION AS WELL AS EMERGENCY LIGHTING. AUTOMATIC
 CONTROLS AS PER FBC?E SHALL BE INSTALLED AS REQUIRED.
 (A) RESPONSE ACCEPTED HERE SEE NOTE ABOVE.
  
 WHEN RESUBMITTING, FOR A QUICKER RETURN ON YOUR
 RE-SUBMITTAL, PLEASE PROVIDE A RESPONSE LETTER
 (NARRATIVE) ADDRESSING EACH ITEM AND THE PAGE NUMBER
 WHERE THE CORRECTIONS APPEAR ALONG WITH THE STANDARD
 CITY RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PAGES INTO THE SUBMITTAL PACKAGE. MARK VOID
 AND LEAVE THE PREVIOUSLY REVIEWED SHEETS FOR
 COMPARATIVE REVIEW. CLOUDING THE CHANGES WILL BE
 GREATLY APPRECIATED.
  
 IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO
 CONTACT ME DIRECTLY.
  
 THANK YOU,
 MIKE ALBARRAN
 ELECTRICAL PLANS EXAMINER
 PH: 561-805-6746
 EMAIL: [email protected]
  