2016-03-17 15:45:12 | 3RD ELECTRICAL REVIEW NOTES FOR PERMIT 14061217 |
| REVIEWED FOR COMPLIANCE WITH: 2010 FBC & NEC 2008 |
| |
| BELOW ARE THE COMMENTS RESPONSES TO THE SECOND REVIEW. |
| TO SIMPLIFY MATTERS I HAVE USED THE SAME FORMAT OF THE |
| PREVIOUS REVIEW AND DELETED ALL THE SATISFACTORILY |
| ADDRESSED AND ONLY LEFT THE ONES REQUIRING FURTHER |
| ATTENTION. FURTHERMORE, ALL SHOW WINDOW AND SIGN OUTLET |
| REQUIREMENTS HAVE BEEN DEFFERED TO THE TENANT |
| BUILD-OUT. |
| |
| PAGE 201 |
| 2. PER THE SAME CODE, AUTOMATIC LIGHTING CONTROLS ARE |
| REQUIRED IN THE ENTRY HALLWAYS. |
| (A) PER FBC-E 505.2.1 EVERY AREA ENCLOSED BY WALLS OR |
| FLOOR TO CEILING PARTITIONS SHALL HAVE AT LEAST ONE |
| CONTROL DEVICE TO CONTROL THE LIGHTING WITHIN THE |
| SPACE. THIS MEANS SEPARATE LIGHT SWITCHES ARE REQUIRED |
| IN THE TOILET AREA, MAIN BATH AREA AND CLOSET. |
| FURTHERMORE, FBC-M SECTION 401.3 REQUIRES THAT |
| VENTILATION BE PROVIDED WHENEVER THE SPACE IS OCCUPIED |
| THEREFORE THE EXHAUST FANS SHALL BE TIED TO THE |
| LIGHTING. |
| 3. THERE ARE NO ELECTRICAL OUTLETS SHOWN ON THE |
| DRAWINGS FOR THE GUEST ROOMS. GUEST ROOM OUTLETS SHALL |
| BE INSTALLED AND SPACED ACCORDING TO NEC 210.52 (A) & |
| (D). |
| (A) RECEPTACLES AS INDICATED ON PLANS DO NOT COMPLY |
| WITH THE MINIMUM CODE REQUIREMENTS OF NEC 210.52(A)(1). |
| 4. THOUGH NEC REQUIRES TAMPER?RESISTANT RECEPTACLES FOR |
| DWELLING UNITS NOT SPECIFICALLY GUEST ROOMS, THE |
| INSTALLATION OF TAMPER?RESISTANT DEVICES IS A |
| SUGGESTION. |
| (A) RESPONSE COMPLIANT W/NEC 2008 THOUGH REQUIRED IN |
| CURRENT CODE. |
| |
| PAGE 301 |
| 1. THERE IS NO LIGHTING REFLECTED FOR THE VARIOUS |
| ROOMS. AS PER THE VARIOUS CODES ALL THESE ROOMS REQUIRE |
| ILLUMINATION AS WELL AS EMERGENCY LIGHTING. AUTOMATIC |
| CONTROLS AS PER FBC?E SHALL BE INSTALLED AS REQUIRED. |
| (A) RESPONSE ACCEPTED HERE SEE NOTE ABOVE. |
| |
| WHEN RESUBMITTING, FOR A QUICKER RETURN ON YOUR |
| RE-SUBMITTAL, PLEASE PROVIDE A RESPONSE LETTER |
| (NARRATIVE) ADDRESSING EACH ITEM AND THE PAGE NUMBER |
| WHERE THE CORRECTIONS APPEAR ALONG WITH THE STANDARD |
| CITY RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| CORRECTED PAGES INTO THE SUBMITTAL PACKAGE. MARK VOID |
| AND LEAVE THE PREVIOUSLY REVIEWED SHEETS FOR |
| COMPARATIVE REVIEW. CLOUDING THE CHANGES WILL BE |
| GREATLY APPRECIATED. |
| |