Plan Review Notes
Plan Review Notes For Permit 14061217
Permit Number 14061217
Review Stop P
Sequence Number 2
Notes
Date Text
2015-06-05 12:43:201) SHT. C-09 SHOWS A 2"IRRIGATION LINE EXITING A METER
 VAULT WITH A 4" FEBCO BFP DEVICE INSTALLED. IS THIS
 CORRECT? CLARIFY.
 2) SHT. P101 SHOWS AN 8" SANITARY LINE EXITING THE
 BUILDING AND SHT. C-09 SHOWS TWO 6" LATERALS. THERE IS
 NO 8" LINE SHOWN COMING INTO THE SITE. CLARIFY.
 3) SUBMIT THE CALCULATIONS FOR THE REQUIRED AMOUNT OF
 DRINKING FOUNTAINS PER FPC TABLE 403.1.FOR THE
 OCCUPANCY TYPE FOR THE FIRST FLOOR INCLUDING THE RETAIL
 SPACE, THE MEZZANINE LEVEL, AND LEVEL 2. THE ONLY
 DRINKING FOUNTAIN CALCULATIONS THAT HAVE BEEN PROVIDED
 ARE FOR THE THIRD LEVEL AND POOL DECK.
 4) SHT. A1.01 - THE SINK IN BREAK ROOM # M11 ON THE
 MEZZANINE LEVEL SHALL COMPLY WITH THE FL. ACCESS. CODE
 SEC. 212, 606 AND 305.
 5) SHT.A7.00 - SUBMIT PLUMBING FIXTURE REQUIREMENTS FOR
 THE FIRST FLOOR INCLUDING THE RETAIL SPACE, THE
 MEZZANINE LEVEL, AND LEVEL 2.
 6) SHT. A7.00 - FIXTURE REQUIREMENTS FOR THE POOL DECK
 - THE CALCULATIONS ARE SHOWING AN OCCUPANT LOAD OF 96
 PERSONS FOR THE SUN DECK AND ALSO 124 PERSONS. CLARIFY.
 7) SHT. A7.00 - FIXTURE REQS. LEVEL 3 - THE TOTAL
 PERSON NUMBER IS SHOWN AS 380 AND THEN DIVIDED INTO 190
 MALES AND 297 FEMALES?? CLARIFY.
 8) A SERVICE SINK IS REQUIRED FOR THE POOL AREA PER FPC
 TABLE 403.1.
 9) SHT. A7.02 - ADA NOTE #6 - A DOOR PULL COMPLYING
 WITH FL. ACCESS. CODE SEC.404.2.7 SHALL BE PLACED ON
 BOTH SIDES OF THE DOOR PER THE FAC SEC.604.8.1.2.
 10) SHT.A7.02 - SHOWER SPRAY UNIT - THE CONTROLS SHALL
 BE LOCATED A MINIMUM OF 38" ABOVE THE FINISH FLOOR, NOT
 3'-8" (44") AS SHOWN. FAC SEC.608.5.1.
 11) 11) ARCHITECTURAL SHEETS - FLOOR PLAN KEYED NOTES #
 28 REFERS TO DETAIL # 2 ON SHT.A8.03 FOR THE SCUPPER
 DETAIL. THERE IS NO SCUPPER DETAIL ON SHT.A8.03.
 DETAILS ARE ON SHT. A8.02. REVISE NOTE AND ALSO PROVIDE
 BOTH DIMENSIONS OF THE SCUPPER IN NOTE # 29.WPB AMEND.
 TO 2010 FBC SEC. 107.2.1.
 12) THE ROOF DRAINAGE CALCULATIONS SHALL INCLUDE
 ONE-HALF THE AREA OF THE VERTICAL WALL AT THE POOL DECK
 AND ANY OTHER AREAS THAT ARE AFFECTED BY A VERTICAL
 (PARAPET) WALL.
 13) SHT.P101 - CODED NOTES #1 REFERS TO SHT. P404 FOR
 GREASE TRAP DETAILS. THERE ARE NO GREASE TRAP DETAILS
 ON SHT. P404.
 14) SHT. P101 CODED NOTE #1 REFERS TO 2-SCHIER GB-250
 GREASE INTERCEPTORS. SUBMIT INTERCEPTOR SIZING
 CALCULATIONS IN ACCORDANCE WITH THE 2010 FPC
 SEC.1003.2, 1003.3.4. THE SIZING CALCULATIONS SHALL BE
 REVIEWED BY SCHIER IN ACCORDANCE WITH 2010 FPC SEC.
 1003.2. CONTACT LEE SCHNEEWEISS AT SCHIER AT
 1-800-538-4792.
 15) SHT.P101 - IDENTIFY/LABEL THE 3" S.S. UP IN THE
 TRASH ROOM. WPB AMEND. TO 2010 FBC SEC. 107.2.1.
 16) SHT. P101 - IDENTIFY/LABEL ALL THE CONDENSATE
 RISERS. WPB AMEND. TO 2010 FBC SEC. 107.2.1.
 17) SHT.P101 - IDENTIFY/LABEL ALL THE WATER RISERS
 (HW,CW, HWR, ).WPB AMEND. TO 2010 FBC SEC.107.2.1.
 18) SHT. P103 - RISER II UP APPEARS TO BE LOCATED
 OUTSIDE THE WALL NEXT TO A COLUMN. CLARIFY.
 19) SHT. P105 --SUPPLY THE PLUMBING SYMBOL LEGEND AND
 ANY CODE NOTES ON THE PLAN. WPB AMEND. TO 2010 FBC
 SEC.107.2.1.
 20) SHTS. #107 & #108 ? ROOF DRAINAGE CALCULATION TABLE
 - SHOWS RWL #1 & #4 AS 4? & SHTS. P307 & P308 SHOW THEM
 AS 6". CLARIFY.
 21) SUBMIT THE DRAINAGE CALCULATIONS FOR THE TRENCH
 DRAINS. WPB AMEND. TO 2010 FBC SEC.107.2.1.
 22) INCLUDE DRAINS #6 & #7 ON THE DRAINAGE CALCULATION
 TABLE. WPB AMEND. TO 2010 FBC SEC.107.2.1.
 23) THE SIZE OF THE DRAINS ON SHEETS #307 & #308 DO NOT
 CORRELATE WITH THE TABLE ON SHT. # 107. CLARIFY.
 24) SHT. P201 - IDENTIFY/LABEL ALL THE RISERS IN ORDER
 TO DO A COMPREHENSIVE REVIEW TO ENSURE THEY CORRELATE
 WITH THE DIAGRAMS. WPB AMEND. TO 2010 FBC SEC.107.2.1.
 25) SHT. P301 - THE HORIZONTAL BRANCHES FOR THE
 DOMESTIC WATER TO THE GUEST ROOMS ARE NOT SIZED, WATER
 LINES ARE NOT SHOWN TO THE PUBLIC RESTROOMS ON LEVEL 3,
 OR TO THE FUTURE KITCHEN. WATER LINES ARE NOT SHOWN TO
 THE RESTROOMS ON THE MEZZANINE LEVEL AND THE LINES ARE
 NOT SIZED TO THE RESTROOMS ON LEVEL 1. WHERE IS THE
 COLD WATER LINE TO THE RESTROOMS ON LEVEL 1? WPB AMEND.
 TO 2010 FBC SEC.107.2.1.
 26) SHT. P301 - THE WATER MAIN BRANCHES HAVE NO
 CONTINUATION/TERMINATION POINTS FOR LEVELS 1,2,3. LOOK
 AT THE WATER HEATERS ALSO. CLARIFY.
 27) SHT. P302 - IDENTIFY THE CONTINUATION /CONNECTION
 POINT OF THE HOT, COLD, AND HOT WATER RETURN LINES ON
 THE LEVEL 1 ISOMETRIC. WPB AMEND. TO 2010 FBC
 SEC.107.2.1.
 28) SHT. P302 SIZE ALL THE WATER LINES ON THE ISOMETRIC
 FOR LEVEL 1 WATER RISER.
 29) SHT. P303 - THE INTERIOR WATER PIPING OF THE ROOMS
 ARE NOT SIZED. SEE ROOMS # 201-209.CLARIFY.
 30) SHT. P304 -THE SHEET IDENTIFIED AS CW & HW
 ISOMETRIC BUT IT IS SANITARY RISERS. PLEASE CORRECT.
 31) SHT. P306 - PLACE CODED NOTES ON SHEET. WPB AMEND.
 TO 2010 FBC SEC.107.2.1.
 32) SHT. P306 - SHOW THE TOTAL DFU'S FOR THE 3" S.S.UP.
 33) SHT. P306 -SIZE ALL SECTIONS OF THE DRAINAGE
 SYSTEM. SEE SECTION UPSTREAM OF STACKS III & IV, INLET
 & OUTLET AND IN BETWEEN THE GREASE INTERCEPTORS AND
 DOWNSTREAM OF THE GREASE INTERCEPTORS.
 34) SUBMIT A SANITARY RISER FOR THE MEZZANINE LEVEL.
 FBC AMEND. TO 2010 FBC SEC. 107.3.5.1.3.
 35) P309 - SIZE THE GAS BRANCH LINES TO THE WATER
 HEATERS. FBC AMEND. TO 2010 FBC SEC. 107.3.5.1.3.
 36) THERE ARE TWO SHEETS NUMBERED P309; ONE IS GAS AND
 ONE IS SANITARY. IS THIS A TYPO? CLARIFY.
 37) SHT. P309 SANITARY - SIZE ALL SECTIONS OF THE
 SANITARY RISERS. WPB AMEND. TO 2010 FBC SEC.107.2.1.
 38) SHT. P309 SANITARY - RISERS II & IV ( ROOM # 206 &
 207 ) ? THE NUMBER AND TYPE OF FIXTURES PERMITTED ON A
 HORIZONTAL WET VENT IS EXCEEDED. REFER TO 2010 FPC
 DEFINITION OF A ?BATHROOM GROUP? AND FPC SEC. 909.1.
 39) RISER IV ON P309 IS LABELED AS RISER V ON P 103 &
 RISER VI ON P103 IS LABELED AS RISER IV ON P309.
 CLARIFY.
 40) THERE IS A PARTIAL RISER ON P309 THAT APPEARS TO BE
 A PRINTING ERROR AND THERE IS ANOTHER RISER THAT IS NOT
 IDENTIFIED. CLARIFY.
 41) SHT.P309 IDENTIFY THE RISER FOR THE GYM TOILET ROOM
 (216) & TOILET ROOM # 222.
 42) SHT. P305 - SIZE ALL SECTIONS OF THE SANITARY
 RISERS. WPB AMEND. TO 2010 FBC SEC.107.2.1.
 43) SHT. P 305 - SANITARY - IDENTIFY/LABEL THE 2?
 SANITARY RISER UP TO ROOF IN ORDER FOR IDENTIFYING
 LOCATION ON ROOF.(BETWEEN ROOMS 4-4 & 4-5).
 44) SHT. P304 - RISERS A, B, C, & D - SIZE ALL SECTIONS
 OF THE SANITARY RISER FOR THE UNITS (LAVATORY STACKS,
 HORIZONTAL DRAINS, SHOWERS. ONE DIAGRAM CAN BE SIZED
 AND SHOWN AS " TYPICAL."
 45) SHT. P 304 - RISER "C" - THE NUMBER AND TYPE OF
 FIXTURES ALLOWED ON A HORIZONTAL WET VENT IS EXCEEDED.
 SEE DEFINITION OF " BATHROOM GROUP" IN FPC AND IN
 SEC.909.1.
 46) SHT. 305 - RISER " E "- THE TOTAL DFU LOAD IS 28.
 THERE ARE TWO ADDITIONAL SHOWERS NEAR THE BASE OF THE
 RISER.
 47) SHT. P306 - SHOW THE TOTAL DFU?S THAT DISCHARGING
 INTO EACH RISER SO THE SIZING OF THE HORIZONTAL
 BRANCHES CAN BE DONE. DO THE SAME ON SHT. P 305. WPB
 AMEND. TO 2010 FBC SEC.107.2.1.
 48) SHTS.P304 & P305 - IDENTIFY / LABEL THE CONNECTION/
 CONTINUATION POINTS OF THE VENTS WHERE THE CONNECT TO
 THE RISERS. WPB AMEND. TO 2010 FBC SEC.107.2.1.
 49) SHOW THE LOCATION OF THE 2ND STAGE REGULATORS ON
 THE GAS DRAWING FOR THE WATER HEATERS.
 50) SHT. P 401 - THE BOOSTER PUMP SHALL BE EQUIPPED
 WITH A LOW PRESSURE CUTOFF PER 2010 FPC SEC.606.5.5.
 51) SHT. P309 - HOW CAN THE LONGEST RUN OF THE GAS
 PIPING BE NOTED AS 50 FEET WHEN THE DIMENSIONS ADD UP
 TO 81 FEET???
 52) THE DOMESTIC WATER SYSTEM SHALL BE EQUIPPED WITH
 PRESSURE REDUCING VALVES IF THE POSSIBILITY OF THE
 PRESSURE TO EXCEED 80 PSI EXISTS FPC SEC.604.8.
 53) WATER HAMMER ARRESTORS SHALL BE INSTALLED ON ALL
 QUICK CLOSING VALVES. AIR CHAMBERS ARE NOT APPROVED.
 FPC SEC.604.9.
 54) SUBMIT THE SPECS/INSTALLATION MANUAL FOR THE POWER
 VENTS FOR THE GAS WATER HEATERS.
 55) SHT. P402 REFERS TO MIAMI-DADE ORDINANCE FOR
 PLUMBING FIXTURE REQUIREMENTS. REMOVE ALL REFERENCE TO
 MIAMI-DADE COUNTY.
 56) SHT. P402 - SUBMIT AN EXPLANATION ON HOW THE
 CALCULATIONS FOR THE COMBUSTION AIR FOR THE GAS WATER
 HEATERS WERE DONE. THERE IS A REFERENCE TO SEC. 706 OF
 THE FBC-MECHANICAL CODE. THIS SECTION SPECIFICALLY
 STATES THAT THE CODE SECTION DOES NOT APPLY TO DIRECT
 VENT APPLIANCES. SEC. 304.1 OF THE FBC-FUEL GAS STATES
 THAT DIRECT VENT APPLIANCES SHALL BE PROVIDED WITH
 COMBUSTION, VENTILATION AND DILUTION AIR IN ACCORDANCE
 WITH THE APPLIANCE MANUFACTURER?S INSTRUCTIONS. SUBMIT
 A COPY OF THE INSTRUCTIONS FOR REVIEW AND SUPPLY THE
 CALCS FOR COMBUSTION AIR ACCORDING TO THE MANUFACTURER.
 57) THE HOT WATER RECIRCULATION SYSTEM SHALL COMPLY
 WITH THE FL. ENERGY CODE SEC. 504.6 FOR SYSTEM
 CONTROLS.
 58) THE SANITARY RISER STACKS SHALL BE VENTED TO COMPLY
 WITH THE FPC SEC. 915.1, 915.2, 915.3 FOR THE VENTING
 OF STACK OFFSETS
 59) THE RESPONSE FROM THE DESIGN PROFESSIONAL REFERS TO
 SHEET P300. THERE IS NO SHT. 300 IN THE PLANS. CLARIFY.
  
 PLUMBING PLAN REVIEW
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 561-805-6692
 [email protected]
  
  
  


Account Summary | Usage Policy | Privacy Policy