Date |
Text |
2015-06-05 12:43:20 | 1) SHT. C-09 SHOWS A 2"IRRIGATION LINE EXITING A METER |
| VAULT WITH A 4" FEBCO BFP DEVICE INSTALLED. IS THIS |
| CORRECT? CLARIFY. |
| 2) SHT. P101 SHOWS AN 8" SANITARY LINE EXITING THE |
| BUILDING AND SHT. C-09 SHOWS TWO 6" LATERALS. THERE IS |
| NO 8" LINE SHOWN COMING INTO THE SITE. CLARIFY. |
| 3) SUBMIT THE CALCULATIONS FOR THE REQUIRED AMOUNT OF |
| DRINKING FOUNTAINS PER FPC TABLE 403.1.FOR THE |
| OCCUPANCY TYPE FOR THE FIRST FLOOR INCLUDING THE RETAIL |
| SPACE, THE MEZZANINE LEVEL, AND LEVEL 2. THE ONLY |
| DRINKING FOUNTAIN CALCULATIONS THAT HAVE BEEN PROVIDED |
| ARE FOR THE THIRD LEVEL AND POOL DECK. |
| 4) SHT. A1.01 - THE SINK IN BREAK ROOM # M11 ON THE |
| MEZZANINE LEVEL SHALL COMPLY WITH THE FL. ACCESS. CODE |
| SEC. 212, 606 AND 305. |
| 5) SHT.A7.00 - SUBMIT PLUMBING FIXTURE REQUIREMENTS FOR |
| THE FIRST FLOOR INCLUDING THE RETAIL SPACE, THE |
| MEZZANINE LEVEL, AND LEVEL 2. |
| 6) SHT. A7.00 - FIXTURE REQUIREMENTS FOR THE POOL DECK |
| - THE CALCULATIONS ARE SHOWING AN OCCUPANT LOAD OF 96 |
| PERSONS FOR THE SUN DECK AND ALSO 124 PERSONS. CLARIFY. |
| 7) SHT. A7.00 - FIXTURE REQS. LEVEL 3 - THE TOTAL |
| PERSON NUMBER IS SHOWN AS 380 AND THEN DIVIDED INTO 190 |
| MALES AND 297 FEMALES?? CLARIFY. |
| 8) A SERVICE SINK IS REQUIRED FOR THE POOL AREA PER FPC |
| TABLE 403.1. |
| 9) SHT. A7.02 - ADA NOTE #6 - A DOOR PULL COMPLYING |
| WITH FL. ACCESS. CODE SEC.404.2.7 SHALL BE PLACED ON |
| BOTH SIDES OF THE DOOR PER THE FAC SEC.604.8.1.2. |
| 10) SHT.A7.02 - SHOWER SPRAY UNIT - THE CONTROLS SHALL |
| BE LOCATED A MINIMUM OF 38" ABOVE THE FINISH FLOOR, NOT |
| 3'-8" (44") AS SHOWN. FAC SEC.608.5.1. |
| 11) 11) ARCHITECTURAL SHEETS - FLOOR PLAN KEYED NOTES # |
| 28 REFERS TO DETAIL # 2 ON SHT.A8.03 FOR THE SCUPPER |
| DETAIL. THERE IS NO SCUPPER DETAIL ON SHT.A8.03. |
| DETAILS ARE ON SHT. A8.02. REVISE NOTE AND ALSO PROVIDE |
| BOTH DIMENSIONS OF THE SCUPPER IN NOTE # 29.WPB AMEND. |
| TO 2010 FBC SEC. 107.2.1. |
| 12) THE ROOF DRAINAGE CALCULATIONS SHALL INCLUDE |
| ONE-HALF THE AREA OF THE VERTICAL WALL AT THE POOL DECK |
| AND ANY OTHER AREAS THAT ARE AFFECTED BY A VERTICAL |
| (PARAPET) WALL. |
| 13) SHT.P101 - CODED NOTES #1 REFERS TO SHT. P404 FOR |
| GREASE TRAP DETAILS. THERE ARE NO GREASE TRAP DETAILS |
| ON SHT. P404. |
| 14) SHT. P101 CODED NOTE #1 REFERS TO 2-SCHIER GB-250 |
| GREASE INTERCEPTORS. SUBMIT INTERCEPTOR SIZING |
| CALCULATIONS IN ACCORDANCE WITH THE 2010 FPC |
| SEC.1003.2, 1003.3.4. THE SIZING CALCULATIONS SHALL BE |
| REVIEWED BY SCHIER IN ACCORDANCE WITH 2010 FPC SEC. |
| 1003.2. CONTACT LEE SCHNEEWEISS AT SCHIER AT |
| 1-800-538-4792. |
| 15) SHT.P101 - IDENTIFY/LABEL THE 3" S.S. UP IN THE |
| TRASH ROOM. WPB AMEND. TO 2010 FBC SEC. 107.2.1. |
| 16) SHT. P101 - IDENTIFY/LABEL ALL THE CONDENSATE |
| RISERS. WPB AMEND. TO 2010 FBC SEC. 107.2.1. |
| 17) SHT.P101 - IDENTIFY/LABEL ALL THE WATER RISERS |
| (HW,CW, HWR, ).WPB AMEND. TO 2010 FBC SEC.107.2.1. |
| 18) SHT. P103 - RISER II UP APPEARS TO BE LOCATED |
| OUTSIDE THE WALL NEXT TO A COLUMN. CLARIFY. |
| 19) SHT. P105 --SUPPLY THE PLUMBING SYMBOL LEGEND AND |
| ANY CODE NOTES ON THE PLAN. WPB AMEND. TO 2010 FBC |
| SEC.107.2.1. |
| 20) SHTS. #107 & #108 ? ROOF DRAINAGE CALCULATION TABLE |
| - SHOWS RWL #1 & #4 AS 4? & SHTS. P307 & P308 SHOW THEM |
| AS 6". CLARIFY. |
| 21) SUBMIT THE DRAINAGE CALCULATIONS FOR THE TRENCH |
| DRAINS. WPB AMEND. TO 2010 FBC SEC.107.2.1. |
| 22) INCLUDE DRAINS #6 & #7 ON THE DRAINAGE CALCULATION |
| TABLE. WPB AMEND. TO 2010 FBC SEC.107.2.1. |
| 23) THE SIZE OF THE DRAINS ON SHEETS #307 & #308 DO NOT |
| CORRELATE WITH THE TABLE ON SHT. # 107. CLARIFY. |
| 24) SHT. P201 - IDENTIFY/LABEL ALL THE RISERS IN ORDER |
| TO DO A COMPREHENSIVE REVIEW TO ENSURE THEY CORRELATE |
| WITH THE DIAGRAMS. WPB AMEND. TO 2010 FBC SEC.107.2.1. |
| 25) SHT. P301 - THE HORIZONTAL BRANCHES FOR THE |
| DOMESTIC WATER TO THE GUEST ROOMS ARE NOT SIZED, WATER |
| LINES ARE NOT SHOWN TO THE PUBLIC RESTROOMS ON LEVEL 3, |
| OR TO THE FUTURE KITCHEN. WATER LINES ARE NOT SHOWN TO |
| THE RESTROOMS ON THE MEZZANINE LEVEL AND THE LINES ARE |
| NOT SIZED TO THE RESTROOMS ON LEVEL 1. WHERE IS THE |
| COLD WATER LINE TO THE RESTROOMS ON LEVEL 1? WPB AMEND. |
| TO 2010 FBC SEC.107.2.1. |
| 26) SHT. P301 - THE WATER MAIN BRANCHES HAVE NO |
| CONTINUATION/TERMINATION POINTS FOR LEVELS 1,2,3. LOOK |
| AT THE WATER HEATERS ALSO. CLARIFY. |
| 27) SHT. P302 - IDENTIFY THE CONTINUATION /CONNECTION |
| POINT OF THE HOT, COLD, AND HOT WATER RETURN LINES ON |
| THE LEVEL 1 ISOMETRIC. WPB AMEND. TO 2010 FBC |
| SEC.107.2.1. |
| 28) SHT. P302 SIZE ALL THE WATER LINES ON THE ISOMETRIC |
| FOR LEVEL 1 WATER RISER. |
| 29) SHT. P303 - THE INTERIOR WATER PIPING OF THE ROOMS |
| ARE NOT SIZED. SEE ROOMS # 201-209.CLARIFY. |
| 30) SHT. P304 -THE SHEET IDENTIFIED AS CW & HW |
| ISOMETRIC BUT IT IS SANITARY RISERS. PLEASE CORRECT. |
| 31) SHT. P306 - PLACE CODED NOTES ON SHEET. WPB AMEND. |
| TO 2010 FBC SEC.107.2.1. |
| 32) SHT. P306 - SHOW THE TOTAL DFU'S FOR THE 3" S.S.UP. |
| 33) SHT. P306 -SIZE ALL SECTIONS OF THE DRAINAGE |
| SYSTEM. SEE SECTION UPSTREAM OF STACKS III & IV, INLET |
| & OUTLET AND IN BETWEEN THE GREASE INTERCEPTORS AND |
| DOWNSTREAM OF THE GREASE INTERCEPTORS. |
| 34) SUBMIT A SANITARY RISER FOR THE MEZZANINE LEVEL. |
| FBC AMEND. TO 2010 FBC SEC. 107.3.5.1.3. |
| 35) P309 - SIZE THE GAS BRANCH LINES TO THE WATER |
| HEATERS. FBC AMEND. TO 2010 FBC SEC. 107.3.5.1.3. |
| 36) THERE ARE TWO SHEETS NUMBERED P309; ONE IS GAS AND |
| ONE IS SANITARY. IS THIS A TYPO? CLARIFY. |
| 37) SHT. P309 SANITARY - SIZE ALL SECTIONS OF THE |
| SANITARY RISERS. WPB AMEND. TO 2010 FBC SEC.107.2.1. |
| 38) SHT. P309 SANITARY - RISERS II & IV ( ROOM # 206 & |
| 207 ) ? THE NUMBER AND TYPE OF FIXTURES PERMITTED ON A |
| HORIZONTAL WET VENT IS EXCEEDED. REFER TO 2010 FPC |
| DEFINITION OF A ?BATHROOM GROUP? AND FPC SEC. 909.1. |
| 39) RISER IV ON P309 IS LABELED AS RISER V ON P 103 & |
| RISER VI ON P103 IS LABELED AS RISER IV ON P309. |
| CLARIFY. |
| 40) THERE IS A PARTIAL RISER ON P309 THAT APPEARS TO BE |
| A PRINTING ERROR AND THERE IS ANOTHER RISER THAT IS NOT |
| IDENTIFIED. CLARIFY. |
| 41) SHT.P309 IDENTIFY THE RISER FOR THE GYM TOILET ROOM |
| (216) & TOILET ROOM # 222. |
| 42) SHT. P305 - SIZE ALL SECTIONS OF THE SANITARY |
| RISERS. WPB AMEND. TO 2010 FBC SEC.107.2.1. |
| 43) SHT. P 305 - SANITARY - IDENTIFY/LABEL THE 2? |
| SANITARY RISER UP TO ROOF IN ORDER FOR IDENTIFYING |
| LOCATION ON ROOF.(BETWEEN ROOMS 4-4 & 4-5). |
| 44) SHT. P304 - RISERS A, B, C, & D - SIZE ALL SECTIONS |
| OF THE SANITARY RISER FOR THE UNITS (LAVATORY STACKS, |
| HORIZONTAL DRAINS, SHOWERS. ONE DIAGRAM CAN BE SIZED |
| AND SHOWN AS " TYPICAL." |
| 45) SHT. P 304 - RISER "C" - THE NUMBER AND TYPE OF |
| FIXTURES ALLOWED ON A HORIZONTAL WET VENT IS EXCEEDED. |
| SEE DEFINITION OF " BATHROOM GROUP" IN FPC AND IN |
| SEC.909.1. |
| 46) SHT. 305 - RISER " E "- THE TOTAL DFU LOAD IS 28. |
| THERE ARE TWO ADDITIONAL SHOWERS NEAR THE BASE OF THE |
| RISER. |
| 47) SHT. P306 - SHOW THE TOTAL DFU?S THAT DISCHARGING |
| INTO EACH RISER SO THE SIZING OF THE HORIZONTAL |
| BRANCHES CAN BE DONE. DO THE SAME ON SHT. P 305. WPB |
| AMEND. TO 2010 FBC SEC.107.2.1. |
| 48) SHTS.P304 & P305 - IDENTIFY / LABEL THE CONNECTION/ |
| CONTINUATION POINTS OF THE VENTS WHERE THE CONNECT TO |
| THE RISERS. WPB AMEND. TO 2010 FBC SEC.107.2.1. |
| 49) SHOW THE LOCATION OF THE 2ND STAGE REGULATORS ON |
| THE GAS DRAWING FOR THE WATER HEATERS. |
| 50) SHT. P 401 - THE BOOSTER PUMP SHALL BE EQUIPPED |
| WITH A LOW PRESSURE CUTOFF PER 2010 FPC SEC.606.5.5. |
| 51) SHT. P309 - HOW CAN THE LONGEST RUN OF THE GAS |
| PIPING BE NOTED AS 50 FEET WHEN THE DIMENSIONS ADD UP |
| TO 81 FEET??? |
| 52) THE DOMESTIC WATER SYSTEM SHALL BE EQUIPPED WITH |
| PRESSURE REDUCING VALVES IF THE POSSIBILITY OF THE |
| PRESSURE TO EXCEED 80 PSI EXISTS FPC SEC.604.8. |
| 53) WATER HAMMER ARRESTORS SHALL BE INSTALLED ON ALL |
| QUICK CLOSING VALVES. AIR CHAMBERS ARE NOT APPROVED. |
| FPC SEC.604.9. |
| 54) SUBMIT THE SPECS/INSTALLATION MANUAL FOR THE POWER |
| VENTS FOR THE GAS WATER HEATERS. |
| 55) SHT. P402 REFERS TO MIAMI-DADE ORDINANCE FOR |
| PLUMBING FIXTURE REQUIREMENTS. REMOVE ALL REFERENCE TO |
| MIAMI-DADE COUNTY. |
| 56) SHT. P402 - SUBMIT AN EXPLANATION ON HOW THE |
| CALCULATIONS FOR THE COMBUSTION AIR FOR THE GAS WATER |
| HEATERS WERE DONE. THERE IS A REFERENCE TO SEC. 706 OF |
| THE FBC-MECHANICAL CODE. THIS SECTION SPECIFICALLY |
| STATES THAT THE CODE SECTION DOES NOT APPLY TO DIRECT |
| VENT APPLIANCES. SEC. 304.1 OF THE FBC-FUEL GAS STATES |
| THAT DIRECT VENT APPLIANCES SHALL BE PROVIDED WITH |
| COMBUSTION, VENTILATION AND DILUTION AIR IN ACCORDANCE |
| WITH THE APPLIANCE MANUFACTURER?S INSTRUCTIONS. SUBMIT |
| A COPY OF THE INSTRUCTIONS FOR REVIEW AND SUPPLY THE |
| CALCS FOR COMBUSTION AIR ACCORDING TO THE MANUFACTURER. |
| 57) THE HOT WATER RECIRCULATION SYSTEM SHALL COMPLY |
| WITH THE FL. ENERGY CODE SEC. 504.6 FOR SYSTEM |
| CONTROLS. |
| 58) THE SANITARY RISER STACKS SHALL BE VENTED TO COMPLY |
| WITH THE FPC SEC. 915.1, 915.2, 915.3 FOR THE VENTING |
| OF STACK OFFSETS |
| 59) THE RESPONSE FROM THE DESIGN PROFESSIONAL REFERS TO |
| SHEET P300. THERE IS NO SHT. 300 IN THE PLANS. CLARIFY. |
| |
| PLUMBING PLAN REVIEW |
| TIM LARGE |
| CHIEF PLUMBING INSPECTOR |
| 561-805-6692 |
| [email protected] |
| |
| |
| |