2015-05-20 13:10:55CHRISTOPHER COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  
  
 PERMIT #14061217
 MECHANICAL REVIEW.
  
 1 ) COOLING & HEATING LOAD CALCULATIONS: THE SUBMITTAL
 DOES NOT INCLUDE THE CALCULATIONS FOR THE HOTEL ROOMS,
 AND MANY OF THE ROOMS AND SPACES SHOWN ON THE 1ST,
 MEZZANINE, AND 2ND FLOOR PLANS SUCH AS THE GYM, TRASH
 ROOM, SECURITY ROOM, LINEN ROOM, EMPLOYEE LOUNGE,
 HOUSEKEEPING; AND THE VARIOUS OFFICES, STORAGE ROOMS
 ETC. THROUGHOUT THE BUILDING, AND THE ROOMS AND SPACES
 ON THE POOL DECK FLOOR. IN ADDITION, THE SQUARE
 FOOTAGES LISTED ON THE DOCUMENTS DO NOT MATCH THE
 SQUARE FOOTAGES LISTED ON THE PLAN (SEE LIFE SAFETY
 SHEETS A1.00- A1.11.) FOR SQUARE FOOT TABLES. PLEASE
 NOTE THAT THE NUMBERED ZONES ON THE CALCS DO NOT
 CORRELATE TO THE PLANS WHICH DO NOT INDICATE ZONES.
 PLEASE REVIEW AND REVISE.
 2) ENERGY CALCULATION FORM 405-2010: THE FORM IS
 IDENTIFYING THE AC SYSTEMS AS "THROUGH THE WALL SINGLE
 PACKAGE" HOWEVER THE MAJORITY OF THE UNITS ARE
 MULTI-SPLIT SYSTEMS EXCEPT FOR THE TWO RTU?S.
 ADDITIONALLY, I DO NOT SEE HOW THE SYSTEMS LISTED- 1,
 2, & 15 CORRELATE TO THE ACTUAL SYSTEMS SHOWN ON THE
 HVAC PLAN SCHEDULES: PLEASE REVISE THE CALCULATIONS TO
 MATCH THE SYSTEMS ON THE PLANS, AND PLACE THE
 EFFICIENCY RATINGS OF THE SYSTEMS ON THE EQUIPMENT
 SCHEDULES.
 3) SHEETS M101, M102, & M103: THE PLANS INDICATE THE
 CORRIDORS BEING USED TO CONVEY RETURN AIR BACK TO THE
 UNITS WHICH IS NOT PERMITTED PER SECTION 601.2 FMC-10.
 PLEASE PROVIDE DUCTED RETURNS.
 4) M101: THERE ARE FIRE DAMPERS MISSING FOR DUCTS
 PENETRATING THE COMMON WALLS BETWEEN THE WOMEN'S
 RESTROOM/HR ROOMS, SECURITY/HR ROOM, AND THE
 OFFICE/VALET ROOMS; AND DAMPERS MISSING OVER THE RATED
 DOORS IN THE SERVICE CORRIDOR, AND OVER THE
 LINEN/CORRIDOR DOOR. PLEASE NOTE THAT A FLEX DUCT IS
 SHOWN PENETRATING THE OFFICE/VALET WALL- NOT PERMITTED
 PER SECTION 603.6.5 FMC-10.
 5) M101: EXHAUST IS REQUIRED FOR THE TRASH ROOM IN
 ACCORDANCE WITH TABLE 6-4 ASHRAE 62.1 04. REVISE THE
 PLANS TO SHOW THE FAN, EXHAUST DUCT IF NEEDED, AND
 TERMINATION LOCATION. INCLUDE THE REQUIRED FAN IN THE
 EQUIPMENT SCHEDULES.
 6) M102: FIRE DAMPERS MISSING FOR DUCTS PENETRATING
 COMMON WALLS BETWEEN THE MECH. RM/EMPLOYEE LOUNGE,
 MECH. RM/LOCKER RM, LOCKER RM/STORAGE RM, AND THE O/A
 DUCTS AT BOILER RM/SERVICE CORRIDOR AND SERVICE
 CORRIDOR/MECH. RM.
 7) M102: A RETURN AIR ARROW SYMBOL IS SHOWN DIRECTING
 AIR FROM THE SERVICE CORRIDOR THROUGH THE RATED DOUBLE
 DOORS AT THE MECH. RM: HOW IS AIR RETURNING THROUGH
 THESE RATED DOORS?
 8) M102: CLARIFY HOW THE EXHAUST SYSTEMS WERE SIZED FOR
 THE GENERATOR AND FIRE PUMP ROOMS: PROVIDE CALCULATIONS
 AND INDICATE THE SEQUENCE OF OPERATION FOR THE FANS.
 9) M102: CLARIFY HOW THE BOILER/PUMP ROOM WILL BE
 VENTILATED.
 10 )M101 & M102: INDICATE SEQUENCE OF OPERATION FOR THE
 O/A MOTORIZED DAMPERS FOR AC-1.1, AC-1.2, AND AC-1.3.
 11) M101 & M102: VERIFY REQUIRED 10' HORIZONTAL
 CLEARANCES FOR THE AIR INTAKES TO STREETS, PARKING,
 EXHAUST VENTS, ETC.- SECTION 401.4.1 FMC-10.
 12) M103: FLEX DUCTS ARE SHOWN IN MANY LOCATIONS OFF
 THE SERVICE CORRIDOR PENETRATING RATED WALLS, AND AT
 THE MECH. CLOSET FOR AC-2.1. FIRE DAMPERS ARE ALSO
 MISSING FOR RETURNS GRILLS IN MANY LOCATIONS: PLEASE
 CORRECT.
 13) M101- M108, M201: SHOW THE LOCATIONS OF AC PIPING
 RUNS OR CHASES. PROVIDE ON THE PLANS THE TYPE OF
 PIPING, TYPE AND THICKNESS OF PIPING INSULATION, AND
 THROUGH PENETRATION FIRE STOPPING DETAILS.
 14) M101- M106, M201: PROVIDE FSD SYMBOLS AT THE
 REQUIRED LOCATIONS- SEE SHEET 601. THE PLANS ARE
 INDICATING ONLY FD'S. PLACE A "TYPICAL" NOTE INDICATING
 REQUIRED ACCESS TO DAMPERS WILL BE PROVIDED- SECTION
 607.4 FMC-10.
 15) M104- M106: DAMPERS ARE NOT SHOWN FOR THE DUCTS
 PENETRATING THE RATED SHAFTS FOR RTU-1 & 2: PLEASE
 CORRECT.
 16) M107: SHOW LOCATIONS OF REQUIRED DAMPERS
 PENETRATING THE RATED FLOOR/CEILING ASSEMBLY.
 17) M107: INDICATE THE EXHAUST DUCT RUNS AND
 TERMINATION LOCATIONS FOR EF-6 & EF-7.
 18) M107: CLARIFY HOW THE POOL EQUIPMENT EXHAUST SYSTEM
 WAS SIZED: SHOW METHOD AND CALCULATIONS AND INDICATE
 SEQUENCE OF OPERATION
 19) M302 & 303: THE WIND LOAD TIE DOWN DETAILS SHOWN
 FOR THE AC UNITS, CURBS, STANDS, AND FANS ETC. MUST BE
 CERTIFIED BY A STRUCTURAL ENGINEER. PLEASE NOTE THAT
 ALL INSTALLATIONS SHALL WITHSTAND 170 MPH WIND LOADS
 AND ASSOCIATED UPLIFT AND LATERAL PRESSURES. PLEASE
 UPDATE THE NOTE UNDER DETAIL 1/M303.
 20) M502: O/A CALCULATIONS DO NOT INCLUDE THE ROOMS AND
 SPACES BEING SERVED BY A1.3 (MEZZANINE LOUNGE,
 ENGINEER'S OFFICE ETC.), AC-2.1 (2ND FLOOR OFFICES,
 HOUSEKEEPING ETC.), AC-2.2 (2ND FLOOR GYM), AND THE
 FCU-1'S AND FCU-2'S (GUEST ROOMS). ADDITIONALLY PROVIDE
 A CALCULATION FOR THE DIRTY LINENS ROOM PER TABLE 403.3
 FMC-10.
 21) M502: PROVIDE AIR BALANCE CALCULATIONS FOR FLOORS
 1-3.
 22) M602: PLEASE SEE SECTION 909 FBC-10 BUILDING FOR
 REQUIRED SUBMITTALS AND DOCUMENTS FOR THE PROPOSED
 SMOKE CONTROL SYSTEMS INCLUDING A RATIONAL ANALYSIS,
 AND A NARRATIVE DETAILING SPECIAL INSPECTIONS AND
 TESTING OF THE SYSTEM.
 23) PROVIDE A SUBMITTAL PACKAGE FOR THE PROJECT
 INCLUDING MANUFACTURER'S SPECIFICATIONS FOR THE RTU'S
 AND AC SYSTEMS AND ALL ASSOCIATED COMPONENTS FOR
 INSTALLATION OF COMPLETE SYSTEMS, THE SPF 1-2 AND SR-1,
 THE EXHAUST AND AIR INTAKE FANS, FIRE DAMPERS, FIRE AND
 SMOKE DAMPERS, SMOKE DETECTORS, DUCT SMOKE DETECTORS,
 MOTORIZED DAMPERS, CONTROLS, ETC.
 THE PACKAGE SHALL CONTAIN ALL REQUIRED FL. PRODUCT
 APPROVALS AND MIAMI-DADE NOA?S FOR EXTERIOR MOUNTED
 COMPONENTS SUBJECT TO WIND PRESSURES
  
  
  