2015-05-11 12:15:51 | THIS 2ND PLAN REVIEW WAS FAILED BY PETER LEDUC, FIRE |
| MARSHAL, WITH THE FOLLOWING COMMENTS: |
| |
| 1) SHEET A1.00 ADD AND EXIT SIGN AT DOOR # 108 FROM THE |
| LOBBY AREA. A REMOTE EXIT FROM THE FRONT LOBBY DOORS IS |
| REQUIRED. CHANGE EXIT SIGNS TO THE OPPISITE SIDE OF |
| DOORS # 107.1 SHOWN ON E 101. |
| |
| 2) SHEET A 2.03 DOOR # 325 THE DOOR SWING IS REQUIRED |
| TO SWING IN THE DIRECTION OF EXIT TRAVEL. SHOW DOORS |
| SWINING IN OPPOSITE DIRECTION. |
| |
| 3) SHEET E 104 EXIT SIGNS UNDER THE CENTER TERRACE AREA |
| NEED TO BE TURNED IN THE OPPISTE DIRECTION LEADING |
| PEOPLE TO THE STAIR, NOT AWAY FROM IT. |
| |
| 4) SHEET E 107, REQUIRED TO ADD AN EXIT SIGN, MOUNTED |
| ON THE CORNER WALL, SENDING PEOPLE FROM THE BATHROOM |
| AND SUNDECK AREA THRU THE SEATING AREA. |
| |
| 5) SHEET A 1.11 EXIT STAIR 1 EXIT LOAD CALCULATION |
| SHOWS 388 PERSON/3 STAIRS 130 PERSONS. THERE ARE ONLY 2 |
| STAIRS FROM THIS AREA. PLEASE CORRECT. |
| |
| 6) SHEET E 104, DOORS # 311 - 311.1 SHOWS A DIFFERENT |
| SWING THAN WHAT IS SHOWN ON A 1.03 AND A 2.03. PLEASE |
| CORRECT |
| SHEET A 1.03, REQUIRED TO HAVE A 2ND EXIT FROM |
| RESTURANT AREA REMOTE FROM THE CENTER STAIR EXIT. THE |
| EXIT DOOR NEEDS TO SWING IN THE DIRECTION OF TRAVEL. |
| PLEASE CORRECT. |
| |
| 7) SHEET FA 301 PROVIDE A NOTE INDICATING VOICE/ALARM |
| COMMUNICATION SYSTEM PER NFPA 1 13.7.2.27.2. |
| |