Plan Review Notes
Plan Review Notes For Permit 14061217
Permit Number 14061217
Review Stop E
Sequence Number 2
Notes
Date Text
2015-09-09 16:37:15PLEASE NOTE THAT I, MIKE ALBARRAN, ELECTRICAL PLANS
 EXAMINER HAVE COMPLETED THE SECOND REVIEW OF THE ABOVE
 MENTIONED JOB. BELOW ARE THE COMMENTS WITH REGARDS TO
 THE REQUIRED CORRECTIONS. THE FOLLOWING ITEMS SHALL BE
 CORRECTED AND THE PLANS RESUBMITTED FOR ANOTHER REVIEW.
 PAGE E101
 1. NEC 600.5 REQUIRES A DEDICATED SIGN OUTLET AT EACH
 ENTRANCE OF A COMMERCIAL BLDG. IN THIS CASE, THERE ARE
 THREE MARKED ON THE PLANS.
 2. NEC 210.62 STATES THAT AT LEAST 1 OUTLET BE
 INSTALLED WITHIN 18? OF THE TOP OF A SHOW WINDOW FOR
 EACH 12? OF WINDOW OR PORTION THEREOF.
 3. ADDITIONAL LIGHTING SHALL BE INSTALLED IN STAIR 3.
 SWITCHING TO CODE.
 PAGE 104
 1. SAME AS NUMBER 1 ABOVE. THE S.E. DOOR MAY NOT
 REQUIRE THIS IF IT IS AN INTERIOR DOOR.
 2. THE SAME APPLIES TO ?FLEX SPACE? 1, 2 & 3.
 PAGE 201
 1. PER FBC-ENERGY SECTION 505.2.1.3(3) HOTEL ROOMS
 SHALL HAVE A MASTER SWITCH AT THE ENTRY DOOR TO ALL
 LIGHTING AND SWITCHED OUTLETS IN THE ROOM.
 2. PER THE SAME CODE, AUTOMATIC LIGHTING CONTROLS ARE
 REQUIRED IN THE ENTRY HALLWAYS.
 3. THERE ARE NO ELECTRICAL OUTLETS SHOWN ON THE
 DRAWINGS FOR THE GUEST ROOMS. GUEST ROOM OUTLETS SHALL
 BE INSTALLED AND SPACED ACCORDING TO NEC 210.52 (A) &
 (D).
 4. THOUGH NEC REQUIRES TAMPER-RESISTANT RECEPTACLES FOR
 DWELLING UNITS NOT SPECIFICALLY GUEST ROOMS, THE
 INSTALLATION OF TAMPER-RESISTANT DEVICES IS A
 SUGGESTION.
 5. FBC-907.2.11.1 REQUIRES THAT SINGLE STATION SMOKE
 DETECTORS BE INSTALLED IN EVERY GUEST ROOM.
 PAGE 301
 1. THERE IS NO LIGHTING REFLECTED FOR THE VARIOUS
 ROOMS. AS PER THE VARIOUS CODES ALL THESE ROOMS REQUIRE
 ILLUMINATION AS WELL AS EMERGENCY LIGHTING. AUTOMATIC
 CONTROLS AS PER FBC-E SHALL BE INSTALLED AS REQUIRED.
 2. ACCORDING TO THE RISER DIAGRAM, PANEL IL IS TO BE
 INSIDE THE MAIN ELECTRICAL ROOM, BUT IT IS NOT
 INDICATED ON DETAIL 4 OF THIS PAGE.
 3. THE RISER REFLECT PANEL IL AS A SINGLE UNIT, YET THE
 PANEL SCHEDULE SHEET SHOWS TWO SEPARATE PANELS.
 4. THE RISER DIAGRAM DOES NOT MATCH THE PANEL SCHEDULE
 AS SHOWN ON THE DRAWINGS.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND LEAVE THE
 PREVIOUSLY REVIEWED SHEETS.
  
 IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO
 CONTACT ME DIRECTLY.
  
 THANK YOU
  