2015-05-22 16:10:56 | BUILDING PLAN REVIEW |
| PERMIT: 14061217 |
| ADD: 335 CLEMATIS ST |
| CONT: TBD |
| TEL: (561)856-6655/ NEYITA |
| |
| 2010 FLORIDA BUILDING CODE W |
| * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION |
| 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013. |
| |
| 2ND REVIEW |
| DATE: FRI. MAY 22 2015 |
| ACTION: DENIED |
| |
| 1) PROVISO: THE SURVEY INDICATES THE PROPOSED BUILDING |
| WILL PROVIDE A REPLAT BEFORE PERMIT ISSUANCE. |
| |
| 2) THRESHOLD BUILDINGS. |
| |
| 2A) COMPLIED, 109.3.6.1 SUBMITTED A WRITTEN THRESHOLD |
| PLAN. |
| |
| 2B) COMPLIED. |
| |
| 2C) 2ND REQUEST. THRESHOLD INSPECTOR: WPB AMENDMENT |
| 109.3.6.2 W.P.B. CONSTRUCTION SERVICES DEPARTMENT |
| REQUEST FOR THRESHOLD BUILDINGS A SPECIAL INSPECTOR AS |
| REQUIRED BY FL S S 553.79(5) FLORIDA STATUTES TO THE |
| MINIMUM INSPECTIONS REQUIRED BY THIS CODE.THE THRESHOLD |
| AGREEMENT FORMS MUST BE SIGNED BY ALL INTERESTED |
| PARTIES AND RETURNED TO THE BUILDING DEPARTMENT BEFORE |
| PERMIT ISSUANCE. . CONTACT KEN CONRAD MANAGER OF THE |
| SPECIAL INSPECTOR PROGRAM AT (561)805-6666 OR E-MAIL: |
| [email protected] FOR FURTHER INFORMATION. |
| |
| 2D) 2ND REQUEST. FOR THE SPECIAL INSPECTOR PLEASE |
| PROVIDE A RESUME' OF INSPECTION EXPERIENCE ON PREVIOUS |
| PROJECT. THE RESUME' MUST BE ACCOMPANIED BY ALL |
| CERTIFICATES AS SPECIFIED HEREIN. THE BUILDING OFFICIAL |
| OR HIS DESIGNEE WILL REVIEW THE RESUME'. AFTER THE |
| RESUME' IS REVIEWED, AN INTERVIEW WILL BE REQUIED. |
| |
| 2E) 2ND REQUEST. THE CONTRACTOR OF RECORD WILL PRODUCE |
| A JOB SUMMARY OR HISTORY FOR THIS TYPE OF CONSTRUCTION. |
| THIS MAY BE SUBMITTED TO KEN CONRAD BY E-MAIL. KEN |
| CONRAD: [email protected] |
| |
| 2F) NOTICE ONLY, NO ACTION REQUIRED BY ARCHITECT. |
| PLEASE CALL THE CITY OF WEST PALM BEACH?S AUTOMATED |
| TELEPHONE INSPECTIONS LINE (561) 805-6700) FOR |
| IN-PROGRESS INSPECTIONS FOR AUDITING OF JOBSITE |
| INSPECTIONS. |
| |
| 2G) NOTICE ONLY, NO ACTION REQUIRED BY ARCHITECT. |
| 109.3.6 THRESHOLD BUILDINGS, OPERATING GUIDELINES FOR |
| THRESHOLD INSPECTORS #26. ASSURE THAT THE DESIGNER HAS |
| REQUIRED ON THE PLANS OR SPECIFICATIONS ONE MATERIAL, |
| APPROVED FOR FIRE STOPPING PENETRATIONS, FOR WALLS AND |
| CEILINGS. |
| |
| 3-4) COMPLIED. |
| |
| 5) 2ND REQUEST. NOTE, 3 ADDITIONAL WRITTENTHRESHOLD |
| INSPECTION PLANS WERE SUBMITTED. SHEET S11.1 FOUNDATION |
| NOTE # 1 ARDAMAN & ASSOCIATES HAS COMPLETED A SOILS |
| REPORT DATED MAY 14/ 2014. PLEASE SUPPLY THE BUILDING |
| DEPARTMENT WITH (3) ORIGINAL SIGNED & SEALED REPORTS. |
| 1803.3 BASIS OF INVESTIGATION. SOIL CLASSIFICATION |
| SHALL BE BASED ON OBSERVATION AND ANY NECESSARY TESTS |
| OF THE MATERIALS DISCLOSED BY BORINGS, TEST PITS OR |
| OTHER SUBSURFACE EXPLORATION MADE IN APPROPRIATE |
| LOCATIONS. ADDITIONAL STUDIES SHALL BE MADE AS |
| NECESSARY TO EVALUATE SLOPE STABILITY, SOIL STRENGTH, |
| POSITION AND ADEQUACY OF LOAD-BEARING SOILS, THE EFFECT |
| OF MOISTURE VARIATION ON SOIL-BEARING CAPACITY, |
| COMPRESSIBILITY, LIQUEFACTION AND EXPANSIVENESS. |
| |
| 6) COMPLIED. |
| |
| 7) SHEET A1.00 LIFE SAFETY SHEET: |
| 7A-D) COMPLIED. |
| |
| |
| 7E) PLEASE PROVIDE COMPLIANCE A MEETING WITH OTHER |
| DESIGNERS MAY BE REQUIRED. |
| EMERGENCY POWER NOTES DON'T SHOW COMPLIANCE WITH 2010 |
| FBC-B [F] 403.4.8.1 EMERGENCY POWER LOADS. |
| THE FOLLOWING ARE CLASSIFIED AS EMERGENCY POWER LOADS: |
| 403.4.8.1: |
| (3.) EMERGENCY VOICE/ALARM COMMUNICATIONS SYSTEMS; |
| |
| (4.) AUTOMATIC FIRE DETECTION SYSTEMS; |
| |
| (5.) FIRE ALARM SYSTEMS; AND |
| |
| (6.) ELECTRICALLY POWERED FIRE PUMPS. |
| |
| 7F) (1) COMPLIED. (1) FIRE PUMP) THE LIFE SAFETY SHEET |
| LEVEL 1 DOES NOT INDICATE COMPLIANCE WITH 403.3.2 WATER |
| SUPPLY TO REQUIRED FIRE PUMPS. |
| |
| 7F)(2) @ND REQUEST. CIVIL SHEET 09 DOES NOT SHOW WATER |
| FROM 2 DIFFERENT MAINS. 2010 FBC-B 403.3.2 2 REQUIRED |
| MAINS. REQUIRED FIRE PUMPS SHALL BE SUPPLIED BY |
| CONNECTIONS TO A MINIMUM OF TWO WATER MAINS LOCATED IN |
| DIFFERENT STREETS. SEPARATE SUPPLY PIPING SHALL BE |
| PROVIDED BETWEEN EACH CONNECTION TO THE WATER MAIN AND |
| THE PUMPS. EACH CONNECTION AND THE SUPPLY PIPING |
| BETWEEN THE CONNECTION AND THE PUMPS SHALL BE SIZED TO |
| SUPPLY THE FLOW AND PRESSURE REQUIRED FOR THE PUMPS TO |
| OPERATE. THE EXCEPTION WOULD STILL REQUIRE THE MAINS TO |
| BE VALVED TO ALLOW FOR 2 TAPS TO BE INDEPENDENT BUT THE |
| 2 SUPLY LINES MERGE BACK INTO ONE LINE BEFORE GOING TO |
| THE INPUT CHAMBER OF THE FIRE PUMP. THE FIRE DEPATMENT |
| REQUIRES IF THIS METHOD OF COMPLIANCE IS CHOSEN THAT |
| THE 2 TAPS CONTINUE UNTIL THEY MANIFOLD BACK TOGETHER |
| AS A MANAFOLD JUST BEFORE THE INTAKE OF THE FIRE PUMP. |
| |
| 7G) PROVISO: APPROVED BY FIRE CHIEF PROVIDED THAT THE |
| EQUIPMENT FITS DOES NOT MEET THE SIZE REQUIREMENTS OF |
| 911.1.3.THE LIFE SAFETY SHEET LEVEL 1 DOES NOT INDICATE |
| COMPLIANCE WITH [F] 403.4.5 FIRE COMMAND. A FIRE |
| COMMAND CENTER COMPLYING WITH SECTION 911 SHALL BE |
| PROVIDED IN A LOCATION APPROVED BY THE FIRE DEPARTMENT. |
| |
| 7H-J) COMPLIED. |
| |
| 7K) MISSING INFORMATION: [F] 403.4.1 SMOKE DETECTION. |
| SMOKE DETECTION SHALL BE PROVIDED IN ACCORDANCE WITH |
| SECTION 907.2.13.1. |
| |
| 7L) MISSING INFORMATION: [F] 403.4.2 FIRE ALARM SYSTEM. |
| A FIRE ALARM SYSTEM SHALL BE PROVIDED IN ACCORDANCE |
| WITH SECTION 907.2.13. |
| |
| 7M) [F] 403.4.3 EMERGENCY VOICE/ALARM COMMUNICATION |
| SYSTEM. AN EMERGENCY VOICE/ALARM COMMUNICATION SYSTEM |
| SHALL BE PROVIDED IN ACCORDANCE WITH SECTION 907.5.2.2. |
| |
| 7N) [F] 403.4.4 EMERGENCY RESPONDER RADIO COVERAGE. |
| EMERGENCY RESPONDER RADIO COVERAGE SHALL BE PROVIDED IN |
| ACCORDANCE WITH THE FLORIDA FIRE PREVENTION CODE. [F] |
| 915.1 GENERAL. EMERGENCY RESPONDER RADIO COVERAGE SHALL |
| BE PROVIDED IN ALL NEW BUILDINGS IN ACCORDANCE THE |
| FLORIDA FIRE PREVENTION CODE. |
| |
| |
| 7O) COMPLIED. 403.4.6 SMOKE REMOVAL. SMOKE CONTROL |
| SHALL BE PROVIDED IN ACCORDANCE WITH SECTION 909. |
| |
| 7P) REPEAT OF 7G. |
| |
| 7Q) MISSING INFORMATION: 403.6 ELEVATORS. |
| ELEVATOR INSTALLATION AND OPERATION IN HIGH-RISE |
| BUILDINGS SHALL COMPLY WITH CHAPTER 30 AND SECTIONS |
| 403.6.1 AND 403.6.2. |
| |
| 7Q) 403.6.1 FIRE SERVICE ACCESS ELEVATOR. |
| IN BUILDINGS WITH AN OCCUPIED FLOOR MORE THAN 120 FEET |
| (36 576 MM) ABOVE THE LOWEST LEVEL OF FIRE DEPARTMENT |
| VEHICLE ACCESS, A MINIMUM OF ONE FIRE SERVICE ACCESS |
| ELEVATOR SHALL BE PROVIDED IN ACCORDANCE WITH SECTION |
| 3007. |
| 3007.4 FIRE SERVICE ACCESS ELEVATOR LOBBY. |
| THE FIRE SERVICE ACCESS ELEVATOR SHALL OPEN INTO A FIRE |
| SERVICE ACCESS ELEVATOR LOBBY IN ACCORDANCE WITH |
| SECTIONS 3007.4.1 THROUGH 3007.4.4. |
| |
| EXCEPTION: WHERE A FIRE SERVICE ACCESS ELEVATOR HAS TWO |
| ENTRANCES ONTO A FLOOR, THE SECOND ENTRANCE SHALL BE |
| PERMITTED TO OPEN INTO AN ELEVATOR LOBBY IN ACCORDANCE |
| WITH SECTION 708.14.1. |
| |
| 2ND REQUEST. 3007.4.1 ACCESS. THE FIRE SERVICE ACCESS |
| ELEVATOR LOBBY SHALL HAVE DIRECT ACCESS TO AN EXIT |
| ENCLOSURE. |
| |
| COMPLIED. 3007.4.2 LOBBY ENCLOSURE. |
| THE FIRE SERVICE ACCESS ELEVATOR LOBBY SHALL BE |
| ENCLOSED WITH A SMOKE BARRIER HAVING A MINIMUM 1-HOUR |
| FIRE-RESISTANCE RATING, EXCEPT THAT LOBBY DOORWAYS |
| SHALL COMPLY WITH SECTION 3007.4.3. |
| |
| EXCEPTION: ENCLOSED FIRE SERVICE ACCESS ELEVATOR |
| LOBBIES ARE NOT REQUIRED AT THE STREET FLOOR. |
| |
| 2ND REQUEST. 3007.4.3 LOBBY DOORWAYS. EACH FIRE SERVICE |
| ACCESS ELEVATOR LOBBY SHALL BE PROVIDED WITH A DOORWAY |
| THAT IS PROTECTED WITH A 3/4-HOUR FIRE DOOR ASSEMBLY |
| COMPLYING WITH SECTION 715.4. THE FIRE DOOR ASSEMBLY |
| SHALL ALSO COMPLY WITH THE SMOKE AND DRAFT CONTROL DOOR |
| ASSEMBLY REQUIREMENTS OF SECTION 715.4.3.1 WITH THE UL |
| 1784 TEST CONDUCTED WITHOUT THE ARTIFICIAL BOTTOM SEAL. |
| |
| 2ND REQUEST, PROVIDE THE SQUARE FOOTAGE OF THE FIRE |
| SERVICE ELEVATOR LOBBY. 3007.4.4 LOBBY SIZE. EACH |
| ENCLOSED FIRE SERVICE ACCESS ELEVATOR LOBBY SHALL BE A |
| MINIMUM OF 150 SQUARE FEET (14 M2) IN AN AREA WITH A |
| MINIMUM DIMENSION OF 8 FEET (2440 MM). |
| |
| 7R) SHEET A8.00 WALL TYPES K-P DO NOT PROVIDE FIRE |
| RATING OF WALL. |
| |
| 8-10) COMPLIED. |
| |
| 11) SHEET A2.03: |
| 11A) THE PLANS DO NOT DEPICT ANY SHAFTS IN THE KITCHEN |
| AREA FOR THE FUTURE KITCHEN EXHAUST & HOOD SYSTEM. |
| 708.2 SHAFT REQUIED. SHEET A2.04 DOES SHOW NOT A 2 HOUR |
| SHAFT BUT WHAT APPEARS TO BE 2 HOUR FIRE RATED DUCT |
| WRAP. THIS DETAIL IS CONSISTENT UP THROUGH THE 10TH |
| FLOOR. SEE M107 THE DUCT TURNS LEFT THEN UP AGAIN. |
| ONTHE POOL DECK LEVEL IT IS SHOWN ON M107 IN THE R06 |
| SEERVICE ROOM. ON THE POOL ROOF DECK PLAN A2.11 THE |
| DUCT DOES NOT SHOW UP. DISCREPANCY IN PLANS. |
| |
| IF THERE IS TO BE NO 2 HR SHAFT, THEN A 2 HOUR DUCT |
| WRAP WILL BE REQUIRED, PROVIDE THE MANUFACTURERES |
| DETAILS, THE OTHER ISSUE IS NOT HAVING FIRE STOPPING |
| DETAILS OF THE ASSEMBLY THROUGH THE RATED FLOOR PER |
| 2010 FBC-B 713.3.1.2. THROUGH-PENETRATION FIRESTOP |
| SYSTEMS. |
| |
| 11B-C) COMPLIED. |
| |
| 12) SHEET A2.11: |
| |
| 12A-B) COMPLIED. |
| |
| 12C) DEALS WITH THE STAIRS TO TTHE ELEVATOR EQUIPMENT, |
| 2010 FBC-B 1009.14. THE RESPONSE INDICATES THE USE OF |
| OTIS GEN 2 ELEVATIONS WHICH ARE MACHINELESS EQUIPMENT. |
| PLEASE PROVIDE WHERE THE CONTROL PANEL FOR THE ELEVATOR |
| IS TO BE LOCATED? IF IN RATED WALLS HOW WILL THE RATING |
| BE MAINTAINED? 107.2.1.3. ADDITIONAL INFORMATION IS |
| REQUIRED. |
| |
| 12D) COMPLIED. |
| |
| 13) THE PRODUCT APPROVALS HAVE BEEN REQUESTED TO BE |
| DEFERRED SUBMITTALS. 107.3.4.2 DEFERRED SUBMITTALS. FOR |
| THE PURPOSES OF THIS SECTION, DEFERRED SUBMITTALS ARE |
| DEFINED AS THOSE PORTIONS OF THE DESIGN THAT ARE NOT |
| SUBMITTED AT THE TIME OF THE APPLICATION AND THAT ARE |
| TO BE SUBMITTED TO THE BUILDING OFFICIAL WITHIN A |
| SPECIFIED PERIOD. DEFERRAL OF ANY SUBMITTAL ITEMS SHALL |
| HAVE THE PRIOR APPROVAL OF THE BUILDING OFFICIAL. THE |
| REGISTERED DESIGN PROFESSIONAL IN RESPONSIBLE CHARGE |
| SHALL LIST THE DEFERRED SUBMITTALS ON THE CONSTRUCTION |
| DOCUMENTS FOR REVIEW BY THE BUILDING OFFICIAL. |
| DOCUMENTS FOR DEFERRED SUBMITTAL ITEMS SHALL BE |
| SUBMITTED TO THE REGISTERED DESIGN PROFESSIONAL IN |
| RESPONSIBLE CHARGE WHO SHALL REVIEW THEM AND FORWARD |
| THEM TO THE BUILDING OFFICIAL WITH A NOTATION |
| INDICATING THAT THE DEFERRED SUBMITTAL DOCUMENTS HAVE |
| BEEN REVIEWED AND FOUND TO BE IN GENERAL CONFORMANCE TO |
| THE DESIGN OF THE BUILDING. THE DEFERRED SUBMITTAL |
| ITEMS SHALL NOT BE INSTALLED UNTIL THE DEFERRED |
| SUBMITTAL DOCUMENTS HAVE BEEN APPROVED BY THE BUILDING |
| OFFICIAL. |
| |
| PLEASE PROVIDE 3 SETS OF PRODUCT APPROVALS FOR EACH OF |
| THE FOLLOWING COMPONENTS AND OR CLADDING. |
| 2010 FBC-B 1609.1.2 PROTECTION OF OPENINGS, 1609.6.4.41 |
| COMPONENTS & CLADDING |
| FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS RULE 9N-3 NOV. |
| 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION |
| SYSTEMS THAT WILL REQUIRE PRODUCT APPROVALS: |
| (31)(A) EXTERIOR DOORS. |
| (B) WINDOWS |
| (C) PANEL WALLS: STOREFRONTS, CURTAIN WALLS, WALL |
| LOUVERS, EFIS SYSTEMS, |
| (D) ROOFING PRODUCTS AND ASSEMBLIES & WATERPROOFING FOR |
| SLABS |
| (E) SHUTTERS |
| (F) SKYLIGHTS |
| (G) EXTERIOR COOLER, FREEZERS & PRE-ENGINEERED A/C |
| STANDS |
| |
| 14)PROVISO: 2010 FBC 107.3.4.1 PRODUCT APPROVALS. THOSE |
| PRODUCTS WHICH ARE REGULATED BY THE DCA RULE 9N-03 |
| SHALL BE REVIEWED AND APPROVED IN WRITING BY THE |
| DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR |
| JURISDICTIONAL APPROVAL. |
| FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR |
| SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS, |
| SHOP DRAWINGS ETC.. |
| |
| 15) COMPLIED WIND DESIGN CRITERIA.. |
| |
| 16-20) COMPLIED. |
| |
| 20A) PROVISO: PLEASE ALSO NOTE THE 3 RD FLOOR IS TO BE |
| DESIGNED FOR A FUTURE RESTARAUNT, BE AWARE OF 1013.2 |
| WHERE FIXED SEATING MAY BE A HEIGHT FACTOR IN THE GUARD |
| RAIL. |
| |
| 21) 2ND REQUEST. SHEET S1 AND S11.1 BOTH INDICATE THE |
| USE OF AUGER CAST PILE, PLEASE PROVIDE WHAT AGENCY/ |
| INSPECTION SERVICE WILL BE RESPONSIBLE FOR THEOBSERVING |
| & RECORD KEEPING OF THE AUGER CAST PILE ASWELL AS LOAD |
| TESTING TO SECTION 2010 FBC-B 1810.3.3.1.2. |
| |
| 22) 2ND REQUEST. BEFORE A PERMIT TO CONSTRUCT, MAY BE |
| ISSUED, IMPACT FEES MUST BE PAID TO PALM BEACH COUNTY. |
| THE ACTUAL PERMIT SET OF PLANS MUST BE STAMPED BY THAT |
| OFFICE, AND A COPY OF THE PAID RECEIPT ATTACHED TO THE |
| PERMIT APPLICATION. PLEASE CALL (561)233-5025 FOR MORE |
| INFORMATION. |
| |
| 23) WHEN RESUBMITTING PLANS PLEASE INDICATE THE |
| REVISION & REMOVE & REPLACE ANY PAGES AS NECESSARY. A |
| TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT |
| NUMBER, WITH A DESCRIPTION OF THE REVISION MADE, |
| IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE THE |
| CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT. |
| THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| |
| JAMES A. WITMER CBO |
| SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| TEL: 561-805-6715 |
| FAX: 561-805-6676 |
| E-MAIL: [email protected] |
| |
| DEVELOPMENT SERVICES HOME PAGE |
| HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP |
| |
| PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS |
| LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS |
| REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO |
| THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE |
| THEREFORE SUBJECT TO PUBLIC DISCLOSURE. |
| |
| MEMBER OF BOAF: BUILDING OFFICIALS ASSOCIATION OF |
| FLORIDA SAVING LIVES AND PROPERTY SINCE 1953 |
| |
| |
| |