2014-07-24 12:33:50 | PLUMBING PLAN REVIEW |
| PERMIT: 14061217 |
| ADD: 335 CLEMATIS ST |
| CONT: TBD |
| TEL: (561)856-6655/ NEYITA |
| |
| 2010 FLORIDA BUILDING CODE W |
| * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION |
| 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013. |
| |
| 1ST REVIEW |
| DATE: SUN. JULY 27/ 2014 |
| ACTION: DENIED |
| |
| A THOROUGH REVIEW CAN NOT BE MADE AT THIS TIME, AS A |
| RESULT OF THE ADDITIONAL INFORMATION REQUESTED |
| ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF |
| THIS REVIEW. |
| |
| NOTICE TO THE DESIGNER OF RECORD: |
| CHAPTER 553.80(2)(B) FLORIDA STATUTES STATES THAT A |
| LOCAL GOVERNMENT SHALL IMPOSE A FEE OF FOUR TIMES THE |
| FEE TO THE DESIGNER FOR PLAN REVIEW, IF PLANS ARE |
| REJECTED THREE OR MORE TIMES FOR REPEATED FAILURE TO |
| CORRECT A CODE VIOLATION. |
| |
| 1A) NEITHER SHEET A0.01 BLDG & ZONING CALCS., SHEET |
| A1.00 LIFE SAFETY NOR P101 PROVIDE OCCUPANCY LOADS |
| (TOTAL) NOR DOES SHEET P101 PROVIDE THE MINIMUM |
| PLUMBING FIXTURES REQUIRED PER 2010 FBC-PLUMBING |
| NEITHER SHEET A0.01 BLDG & ZONING CALCS., SHEET A1.00 |
| LIFE SAFETY NOR P101 PROVIDE OCCUPANCY LOADS NOR DOES |
| SHEET P101 PROVIDE THE MINIMUM PLUMBING FIXTURES |
| REQUIRED PER 2010 FBC-PLUMBING SECTION 403 AND TABLE |
| 403.1 FOR THEFOR THE COMMON AREAS ON THE 1ST FLOOR AND |
| 2ND FLOOR (MEZZANINE). |
| |
| 1B) SHEET P104 THE 3RD FLOOR RESTUARANT AND FLEX AREAS |
| PROVIDE A TABLE/ CHART IN COMPLIANCE WITH THE 2010 |
| FBC-P SECTION 403 AND TABLE 403.1. |
| |
| 1C) SHEET P107 THE ROOF DECK/ POOL DECK DOES NOT |
| PROVIDE A TABLE/ CHART IN COMPLIANCE WITH THE 2010 |
| FBC-P SECTION 403 AND TABLE 403.1. |
| |
| 2) SHEET P101: |
| |
| 2A) SHEET P101 INDICATES THE USE OF A 2 LB. NATURAL GAS |
| SYSTEM. THE PLANS SHOW THE NATURAL GAS SYSTEM INTRERING |
| THE BUILDING WITHIN THE FPL VAULT. PLEASE CHECK WITH |
| FPL, I DO NOT BELIEVE THEY WANT ANY OTHER UTILITES |
| SHARING THEIR VAULT SPACE EXSPECIALLY A 2LB NATURAL GAS |
| SYSTEM. |
| 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING |
| CODE, CHAPTER 1, 101.3 THE PURPOSE OF THIS CODE IS TO |
| ESTABLISH THE MINIMUM REQUIREMENTS TO SAFEGUARD THE |
| PUBLIC HEALTH, SAFETY AND GENERAL WELFARE THROUGH |
| STRUCTURAL STRENGTH, MEANS OF EGRESS FACILITIES, |
| STABILITY, SANITATION, ADEQUATE LIGHT AND VENTILATION, |
| ENERGY CONSERVATION, AND SAFETY TO LIFE AND PROPERTY |
| FROM FIRE AND OTHER HAZARDS ATTRIBUTED TO THE BUILT |
| ENVIRONMENT AND TO PROVIDE SAFETY TO FIRE FIGHTERS, |
| CODE OFFICIALS, AND EMERGENCY RESPONDERS DURING |
| EMERGENCY OPERATIONS. |
| |
| 2B) SHEET P101 INDICATES THE USE OF A 2 LB. NATURAL GAS |
| SYSTEM. THE REST OF THE FUEL GAS COMMENTS WILL BE UNDER |
| A SEPERATE GAS REVIEW. |
| |
| 3) SHEET P101 INDICATES THE USE OF (2) NEW SCHIER 250 |
| GREASE INTERCEPTORS, NOTE # 1 INDICATES SEE DETAILS |
| FOUND ON SHEET P400. THERE IS NO SHEET P400 IN ALL (3) |
| SETS OF PLANS. THERE IS NO SHEET P400 LISTED IN THE |
| INDEX EITHER. PLEAS PROVIDE THE SIZING CALCULATIONS |
| USED FOR THIS INSTALATION PER 2010 FBC-P 1003.2 |
| APPROVAL. THE SIZE, TYPE AND LOCATION OF EACH |
| INTERCEPTOR AND OF EACH SEPARATOR SHALL BE APPROVED BY |
| THE PLUMBING OFFICIAL. THE INTERCEPTOR OR SEPARATOR |
| SHALL BE DESIGNED AND INSTALLED IN ACCORDANCE WITH THE |
| MANUFACTURER?S INSTRUCTIONS AND THE REQUIREMENTS OF |
| THIS SECTION. WASTES THAT DO NOT REQUIRE TREATMENT OR |
| SEPARATION SHALL NOT BE DISCHARGED INTO ANY INTERCEPTOR |
| OR SEPARATOR. |
| |
| WITHOUT THE FUTURE RESTUARANT LAYOUT, EQUIPMENT, TYPE |
| OF FOODS, LOW, MEDIUM OR HIGH GREASE CONTENT HOW CAN |
| THE COMMERCIAL KITCHEN AND GREASY WASTE BE SIZED? |
| |
| 1003.3.4 GREASE INTERCEPTORS AND AUTOMATIC GREASE |
| REMOVAL DEVICES. |
| GREASE INTERCEPTORS AND AUTOMATIC GREASE REMOVAL |
| DEVICES SHALL BE SIZED IN ACCORDANCE WITH PDI G101, |
| ASME A112.14.3 APPENDIX A, OR ASME A112.14.4. GREASE |
| INTERCEPTORS AND AUTOMATIC GREASE REMOVAL DEVICES SHALL |
| BE DESIGNED AND TESTED IN ACCORDANCE WITH PDI G101, |
| ASME A112.14.3 OR ASME A112.14.4. GREASE INTERCEPTORS |
| AND AUTOMATIC GREASE REMOVAL DEVICES SHALL BE INSTALLED |
| IN ACCORDANCE WITH THE MANUFACTURER?S INSTRUCTIONS. |
| |
| 4) SHEET P101 NOTE # 4 INDICATES WITHIN THE ELEVATOR |
| SHAFT THE USE OF SUMP PUMPS AND INDIRECT WASTE. PLEASE |
| PROVIDE THE TYPE OF ELEVATORS TO BE INSTALLED. IF |
| HYDROLIC ELEVATORS THEN EITHER A OIL SEPARATOR OR AN |
| APPROVED ALARM SYSTEM IS INSTALLED. SEE 2010 FBC_P |
| 1003.4. |
| |
| 5) SHEET P101 FIRE PUMP ROOM THE FLOOR DRAIN IS MISSING |
| THE TRAP PRIMER. 2010 FBC-P 1002.4. |
| |
| 6) SHEET P101 THE A/C CONDENSATE PIPING IS NOT SIZED |
| NOR TYPE OF MATERIAL, PLEASE SIZE TO THE 2010 FBC-P |
| 314.2 & TABLE 314.2, THIS COMMENT IS COMMON TO ALL |
| FLOORS. |
| |
| 7) SHEET P101 A/C CONDENSATE LEADS FROM THE BUILDING TO |
| THE DRIVE AND CATCH BASIN, NOT ALSO THERE ARE (2) 6" |
| STORM PIPES (RAIN/ STORM) PIPES LEADING FROM UNDER THE |
| BUILDING. THE MATERIAL THESE PIPES ARE MADE FROM IS NOT |
| IDENTIFIED, IDENTIFY MATERIAL AND THICKNESS AND OR |
| SCHUDULE. |
| |
| 1102.4 BUILDING STORM SEWER PIPE. BUILDING STORM SEWER |
| PIPE SHALL CONFORM TO ONE OF THE STANDARDS LISTED IN |
| TABLE 1102.4. |
| |
| 1102.5 SUBSOIL DRAIN PIPE. SUBSOIL DRAINS SHALL BE |
| OPEN-JOINTED, HORIZONTALLY SPLIT OR PERFORATED PIPE |
| CONFORMING TO ONE OF THE STANDARDS LISTED IN TABLE |
| 1102.5. |
| |
| 8) SHEETS P102- P108 ARE INCOMPLETE THERE ARE NO NOTES |
| ON ANY OF THESE SHEETS. |
| |
| 9A) ) THERE ARE NO PLUMBING SANITARY RISER ISOMETRIC |
| PLANS SUBMITTED. 2010 WEST PALM BEACH AMENDMENTS TO THE |
| FLORIDA BUILDING CODE, CHAPTER 1, ADMINISTRATION, |
| 107.3.5 MINIMUM PLAN REVIEW CRITERIA FOR BUILDINGS |
| 107.3.5.1.3 PLUMBING 13. PLUMBING RISER. |
| |
| 9B) THIS BUILDING IS CONSIDERED 12 STORIES TALL. PLEASE |
| PROVIDE COMPLIANCE WITH 2010 FBC-P: |
| 914.1 WHERE REQUIRED. |
| SOIL AND WASTE STACKS IN BUILDINGS HAVING MORE THAN 10 |
| BRANCH INTERVALS SHALL BE PROVIDED WITH A RELIEF VENT |
| AT EACH TENTH INTERVAL INSTALLED, BEGINNING WITH THE |
| TOP FLOOR. |
| |
| 914.2 SIZE AND CONNECTION. |
| THE SIZE OF THE RELIEF VENT SHALL BE EQUAL TO THE SIZE |
| OF THE VENT STACK TO WHICH IT CONNECTS. THE LOWER END |
| OF EACH RELIEF VENT SHALL CONNECT TO THE SOIL OR WASTE |
| STACK THROUGH A WYE BELOW THE HORIZONTAL BRANCH SERVING |
| THE FLOOR, AND THE UPPER END SHALL CONNECT TO THE VENT |
| STACK THROUGH A WYE NOT LESS THAN 3 FEET (914 MM) ABOVE |
| THE FLOOR. |
| |
| SECTION 915 |
| VENTS FOR STACK OFFSETS |
| |
| 915.1 VENT FOR HORIZONTAL OFFSET OF DRAINAGE STACK. |
| HORIZONTAL OFFSETS OF DRAINAGE STACKS SHALL BE VENTED |
| WHERE FIVE OR MORE BRANCH INTERVALS ARE LOCATED ABOVE |
| THE OFFSET. THE OFFSET SHALL BE VENTED BY VENTING THE |
| UPPER SECTION OF THE DRAINAGE STACK AND THE LOWER |
| SECTION OF THE DRAINAGE STACK. |
| |
| 10A) THERE IS NO PLUMBING STORM/ ROOF DRAINAGE RISER |
| ISOMETRIC DIAGRAM SUBMITTED. 107.3.5 MINIMUM PLAN |
| REVIEW CRITERIA FOR BUILDINGS 107.3.5.1.3 PLUMBING 13. |
| PLUMBING RISER. |
| |
| 10B) THIS BUILDING IS OVER 12 STORIES TALL. PROVIDE |
| COMPLIANCE WITH 2010 FBC-P: |
| |
| 914.1 WHERE REQUIRED. |
| SOIL AND WASTE STACKS IN BUILDINGS HAVING MORE THAN 10 |
| BRANCH INTERVALS SHALL BE PROVIDED WITH A RELIEF VENT |
| AT EACH TENTH INTERVAL INSTALLED, BEGINNING WITH THE |
| TOP FLOOR. |
| |
| 914.2 SIZE AND CONNECTION. |
| THE SIZE OF THE RELIEF VENT SHALL BE EQUAL TO THE SIZE |
| OF THE VENT STACK TO WHICH IT CONNECTS. THE LOWER END |
| OF EACH RELIEF VENT SHALL CONNECT TO THE SOIL OR WASTE |
| STACK THROUGH A WYE BELOW THE HORIZONTAL BRANCH SERVING |
| THE FLOOR, AND THE UPPER END SHALL CONNECT TO THE VENT |
| STACK THROUGH A WYE NOT LESS THAN 3 FEET (914 MM) ABOVE |
| THE FLOOR. |
| |
| SECTION 915 |
| VENTS FOR STACK OFFSETS |
| |
| 915.1 VENT FOR HORIZONTAL OFFSET OF DRAINAGE STACK. |
| HORIZONTAL OFFSETS OF DRAINAGE STACKS SHALL BE VENTED |
| WHERE FIVE OR MORE BRANCH INTERVALS ARE LOCATED ABOVE |
| THE OFFSET. THE OFFSET SHALL BE VENTED BY VENTING THE |
| UPPER SECTION OF THE DRAINAGE STACK AND THE LOWER |
| SECTION OF THE DRAINAGE STACK. |
| |
| 11) MISSING: ROOF & DECK DRAINAGE PLANS. |
| 11A) A203/ P104 A- SHEET 3RD FLOOR TERRACE/ RETUARANT |
| NOTE# (20) PROVIDE 4 INCH CONTINIOUS DECK DRAIN, NO |
| OVER FLOW PLUMBING SHEET NO NOTES |
| 11B) A2.11/ P107 A-SHEET POOL DECK NOTE# (20) PROVIDE 4 |
| INCH CONTINIOUS DECK DRAIN, NO OVER FLOW, PLUMBING |
| SHEET NO NOTES. |
| 11C) A2.12/ P1.108 A-SHEET UPPER ROOF DRAINAGE NOTE 15 |
| REFFERS TO PLUMBING SHEETS, PLUMBING SHEETS NO NOTES. |
| |
| THE ROOF AND DECK DRAINAGE ARE TO BE SIZED, BASED ON |
| THE 100-YEAR HOURLY RAINFALL RATE INDICATED IN FIGURE |
| 1106.1 OR ON OTHER RAINFALL RATES DETERMINED FROM |
| APPROVED LOCAL WEATHER DATA. 2010 FBC-P 1106.1 FOR THE |
| CITY OF WEST PALM BEACH THIS IS 4.5 INCHES. 100-YEAR, |
| 1-HOUR RAINFALL (INCHES). |
| |
| 11B) PLEASE PROVIDE CALCULATIONS FOR SIZING OF THE ROOF |
| DRAINS, & DECK DRAINS FOR THE FLAT AREAS SERVED PLUS |
| THE VERTICAL WALL AREA AS REQUIRED BY |
| 1106.4. IF THERE ARE CONTRIBUTING SLOPED ROOFS THAT ADD |
| TO THE DRAIN BEING SERVED PROVIDE THE SQ FOOTAGE OF |
| THAT AREA AS WELL. |
| |
| 11C) 1106.2 VERTICAL CONDUCTORS AND LEADERS. VERTICAL |
| CONDUCTORS AND LEADERS SHALL BE SIZED FOR THE MAXIMUM |
| PROJECTED ROOF AREA, IN ACCORDANCE WITH TABLES |
| 1106.2(1) AND 1106.2(2). |
| |
| 11D) 1106.3 BUILDING STORM DRAINS AND SEWERS. |
| THE SIZE OF THE BUILDING STORM DRAIN, BUILDING STORM |
| SEWER AND THEIR HORIZONTAL BRANCHES HAVING A SLOPE OF |
| ONE-HALF UNIT OR LESS VERTICAL IN 12 UNITS HORIZONTAL |
| (4-PERCENT SLOPE) SHALL BE BASED ON THE MAXIMUM |
| PROJECTED ROOF AREA IN ACCORDANCE WITH TABLE 1106.3. |
| THE MINIMUM SLOPE OF HORIZONTAL BRANCHES SHALL BE |
| ONE-EIGHTH UNIT VERTICAL IN 12 UNITS HORIZONTAL |
| (1-PERCENT SLOPE) UNLESS OTHERWISE APPROVED. |
| |
| 11E) 1110.4 MINIMUM NUMBER OF ROOF DRAINS. |
| NOT LESS THAN TWO ROOF DRAINS SHALL BE INSTALLED IN |
| ROOF AREAS 10,000 SQUARE FEET (929 M2) OR LESS AND NOT |
| LESS THAN FOUR ROOF DRAINS SHALL BE INSTALLED IN ROOFS |
| OVER 10,000 SQUARE FEET (929 M2) IN AREA. |
| |
| 12) FOR BOTH THE 3RD FLOOR TERRACE (P104) AND POOL DECK |
| (P107) NEITHER OF THSE PLANS INDICATE HOW COMPLIANCE |
| WITH : |
| 2010 FBC-PLUMBING SECTION 1107/ SECONDARY (EMERGENCY) |
| ROOF DRAINS |
| |
| 12A)1107.1 SECONDARY DRAINAGE REQUIRED. |
| SECONDARY (EMERGENCY) ROOF DRAINS OR SCUPPERS SHALL BE |
| PROVIDED WHERE THE ROOF PERIMETER CONSTRUCTION EXTENDS |
| ABOVE THE ROOF IN SUCH A MANNER THAT WATER WILL BE |
| ENTRAPPED IF THE PRIMARY DRAINS ALLOW BUILDUP FOR ANY |
| REASON. |
| |
| 12B)1107.2 SEPARATE SYSTEMS REQUIRED. |
| SECONDARY ROOF DRAIN SYSTEMS SHALL HAVE THE END POINT |
| OF DISCHARGE SEPARATE FROM THE PRIMARY SYSTEM. |
| DISCHARGE SHALL BE ABOVE GRADE, IN A LOCATION THAT |
| WOULD NORMALLY BE OBSERVED BY THE BUILDING OCCUPANTS OR |
| MAINTENANCE PERSONNEL. |
| |
| 12C)1107.3 SIZING OF SECONDARY DRAINS. |
| SECONDARY (EMERGENCY) ROOF DRAIN SYSTEMS SHALL BE SIZED |
| IN ACCORDANCE WITH SECTION 1106 BASED ON THE RAINFALL |
| RATE FOR WHICH THE PRIMARY SYSTEM IS SIZED IN TABLES |
| 1106.2(1), 1106.2(2), 1106.3 AND 1106.6. SCUPPERS SHALL |
| BE SIZED TO PREVENT THE DEPTH OF PONDING WATER FROM |
| EXCEEDING THAT FOR WHICH THE ROOF WAS DESIGNED AS |
| DETERMINED BY SECTION 1101.7 . SCUPPERS SHALL NOT HAVE |
| AN OPENING DIMENSION OF LESS THAN 4 INCHES (102 MM). |
| THE FLOW THROUGH THE PRIMARY SYSTEM SHALL NOT BE |
| CONSIDERED WHEN SIZING THE SECONDARY ROOF DRAIN SYSTEM. |
| |
| 12D) NOTE SHEET A212 DOES PROVIDE OVER FLOW SCUPPERS |
| AND SIZED PROPERLY FOR A 5 INCH /PER HOUR RAINFALL. THE |
| PLANS DO NEED TO MAKE A CORRECTION. THE PLANS INDICATE |
| A 5 FOOT RAIN FALL/ HOUR. 107.2.1.3 TYPO |
| |
| 13) WITHIN THE POOL DECK THERE WILL PLANTERS THAT WILL |
| REQUIRE ADDITIONAL DRAINAGE, NO DETAILS WERE SUBMITTED |
| WITHIN THIS REVIEW. 107.2.1.3 ADDITIONAL INFORMATION IS |
| REQUIED. |
| |
| 14) NOTE TO DATE THERE HAS BEEN NO IRRIGATION DRAWINGS |
| BEING SUBMITTED. IRRIGATION DOES REQUIRE A SEPARATE |
| PERMIT AND ASSOCIATED FEES. |
| |
| 15) POOL DECK SHEET P107: |
| 15A) POOL BAR IS MISSING THE WATER SERVICE (POTTABLE |
| WATER REQUIRED 602.2) TO THE BAR AREA. |
| |
| 15B) POOL PIPING TO BE REVIEWED UNDER THE POOL PERMIT, |
| WILL THERE BE GAS POOL HEATERS? 107.2.1.3 ADDITIONAL |
| INFORMATION. |
| |
| 15C) MISSING 424.1.6.1.4 HOSE BIBB. A HOSE BIBB WITH |
| VACUUM BREAKER SHALL BE PROVIDED IN OR WITHIN 25 FEET |
| (7620 MM) OF EACH RESTROOM TO ALLOW FOR EASE OF |
| CLEANING. |
| |
| 15D) MISSING 424.1.6.2 RINSE SHOWER. A MINIMUM OF ONE |
| RINSE SHOWER SHALL BE PROVIDED ON THE POOL DECK OF ALL |
| OUTDOOR POOLS WITHIN 20 FEET (60 960 MM) OF THE NEAREST |
| POOL WATER?S EDGE. |
| |
| 15E) THE PLANS INDICATE A 1" WATER SERVICE INTO THE |
| POOL EQUIPMENT ROOM, PLANS SHOW A VALVE BUT IT APPEARS |
| THERE IS NO PROTECTION TO THE POTTABLE WATER SUPPLY. |
| 2010 FBC-P 608.3. |
| |
| A THOROUGH REVIEW CAN NOT BE MADE AT THIS TIME, AS A |
| RESULT OF THE ADDITIONAL INFORMATION REQUESTED |
| ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF |
| THIS REVIEW. |
| |
| WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION & |
| REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL |
| LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH |
| A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE |
| SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE |
| FOUND WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR |
| YOUR ANTICIPATED COOPERATION. |
| |
| JAMES A. WITMER CBO |
| SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| TEL: 561-805-6715 |
| FAX: 561-805-6676 |
| E-MAIL: [email protected] |
| |
| |
| |
| |
| . |
| |
| |
| |
| |
| |
| |
| |
| |
| |
| |
| |
| |
| |
| |