Plan Review Notes For Permit 14061217 |
Permit Number |
14061217 |
|
Review Stop |
M |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2014-08-07 09:42:41 | PLAN DENIED | | | | 1) PAGE M-101 PROVIDE EXHAUST FAN FOR LAUNDRY ROOM | | PER TABLE 403.3 FBC (M) 2010 | | 2) MISSING MULTIPLE FIRE DAMPERS REFER TO SECTION | | 607.5.1 | | 2010 FBC (M) | | 3) PLEASE PROVIDE RATED WALLS ON MECHANICAL PLAN | | PER SECTION 107 FBC 2010 | | 4) PLAN SHOWS FRESH AIR INTAKE FOR A/C 1.2 ON NORTH | | SIDE OF THE BUILDING. REFER TO SECTION 401.4.1 2010 FBC | | (M) | | PAGE M-102 | | 1) MISSING MULTIPLE FIRE DAMPERS 607.5.1 | | 2) BATHROOM EXHAUST ROOM # M-13 M- 14 NEED FAN NUMBER | | AND | | CFM. | | 3) GENERATOR REQUIRES SEPARATE APPLICATION, PLAN AND | | PERMIT. | | 4) GREASE DUCT AND HOOD REQUIRE SEPARATE APPLICATION, | | PLAN | | AND PERMIT. | | 5) PROVIDE INFORMATION ON CLOTHES DRYER LOCATION AND | | VENTILATION | | PER SECTION 504.8 FBC (M) | | 6) PROVIDE SMOKE CONTROL ANALYSIS WITH THE PLAN | | PER SECTION 513.4 FBC (M) | | 7) PROVIDE INFORMATION ON PRESSURIZED STAR TOWER | | CHAPTER 9 FBC 2010 | | | | PLAN REVIEW BY HAROLD MOSER | | [email protected] | | OFFICE 561-805-6732 | | FAX 561-805-6676 |
|