Plan Review Notes
Plan Review Notes For Permit 14061217
Permit Number 14061217
Review Stop G
Sequence Number 1
Notes
Date Text
2014-07-27 08:51:15GAS PLAN REVIEW
 PERMIT: 14061217
 ADD: 335 CLEMATIS ST
 CONT: TBD
 TEL: (561)856-6655/ NEYITA
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 1ST REVIEW
 DATE: SUN. JULY 27/ 2014
 ACTION: DENIED
  
 A THOROUGH REVIEW CAN NOT BE MADE AT THIS TIME, AS A
 RESULT OF THE ADDITIONAL INFORMATION REQUESTED
 ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF
 THIS REVIEW.
  
 NOTICE TO THE DESIGNER OF RECORD:
 CHAPTER 553.80(2)(B) FLORIDA STATUTES STATES THAT A
 LOCAL GOVERNMENT SHALL IMPOSE A FEE OF FOUR TIMES THE
 FEE TO THE DESIGNER FOR PLAN REVIEW, IF PLANS ARE
 REJECTED THREE OR MORE TIMES FOR REPEATED FAILURE TO
 CORRECT A CODE VIOLATION.
  
 1) SHEET P101 INDICATES THE USE OF A 2 LB. NATURAL GAS
 SYSTEM. THE PLANS SHOW THE NATURAL GAS SYSTEM INTRERING
 THE BUILDING WITHIN THE FPL VAULT. PLEASE CHECK WITH
 FPL, I DO NOT BELIEVE THEY WANT ANY OTHER UTILITES
 SHARING THEIR VAULT SPACE EXSPECIALLY A 2LB NATURAL GAS
 SYSTEM.
 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING
 CODE, CHAPTER 1, 101.3 THE PURPOSE OF THIS CODE IS TO
 ESTABLISH THE MINIMUM REQUIREMENTS TO SAFEGUARD THE
 PUBLIC HEALTH, SAFETY AND GENERAL WELFARE THROUGH
 STRUCTURAL STRENGTH, MEANS OF EGRESS FACILITIES,
 STABILITY, SANITATION, ADEQUATE LIGHT AND VENTILATION,
 ENERGY CONSERVATION, AND SAFETY TO LIFE AND PROPERTY
 FROM FIRE AND OTHER HAZARDS ATTRIBUTED TO THE BUILT
 ENVIRONMENT AND TO PROVIDE SAFETY TO FIRE FIGHTERS,
 CODE OFFICIALS, AND EMERGENCY RESPONDERS DURING
 EMERGENCY OPERATIONS.
  
 2) A SEPERATE GAS PERMIT WILL NEED TO BE APPLIED FOR,
 THE FUEL GAS REVIEW CAN TAKE PLACE UNDER THE PRIME
 (MASTER) PERMIT OR THE GAS CAN BE TAKEN OUT TOTALLY AND
 REVIEWED INDEPENDENTLY AS A SEPERATE PERMIT.
  
 3) THERE ARE NO GAS PLANS, THE PLANS SUBMITTED DO NOT
 INDICATE WHAT TYPE OF FUEL THE FIRE PUMP AND GENERATOR
 ARE TO RUN ON PLEASE REVIEW THE MINIMUM PLAN REVIEW
 CRITERIA FOR A COMMERCIAL GAS PLAN REVIEW:
  
 GAS PERMIT APPLICATION REQUIREMENTS
  
 EFFECTIVE IMMEDIATELY THE FOLLOWING INFORMATION SHALL
 BE SHOWN ON ALL GAS DRAWINGS SUBMITTED FOR PERMITTING
 IN THE CITY OF WEST PALM BEACH:
  
 3.1. SUBMIT AN ISOMETRIC DRAWING THAT CLEARLY SHOWS ALL
 CUT SECTIONS OF PIPE AND CORRESPONDING LENGTHS PER
 FBC-2010 FUEL GAS.
  
 3.2. SHOW TYPE OF PIPING MATERIAL BEING INSTALLED, ALL
 PIPE SIZES, AND THE EDH NUMBER OF CORRUGATED STAINLESS
 STEEL TUBING FOR EACH PIPE SIZE IF BEING USED.
  
 3.3. TYPE OF GAS, (LP OR NATURAL).
  
 3.4. BTU LOAD OF EACH APPLIANCE AND THE TOTAL BTU LOAD
 ON THE SYSTEM. REFER TO THE FBC-2010 FUEL GAS SECS.
 401.8 THRU 402.6.1 AND TABLES 402.4(1) THRU 402.4(35)
  
 3.5. SHOW THE DISTANCE FROM THE POINT OF DELIVERY,
 (METER), TO THE MOST REMOTE OUTLET IN THE BUILDING
 AND/OR SYSTEM PER THE FBC-2010 FUEL GAS APPENDIX A ?
 USE OF CAPACITY SECTION A.3.1(4)
  
 3.6. SUBMIT CALCULATIONS FOR COMBUSTION AIR PER THE
 FBC-2010 FUEL GAS CODE SEC. 304
  
 3.7. INDICATE THE DELIVERY PRESSURE (PSI) PER FBC-2010
 FUEL GAS SEC. 402.2. IF NATURAL GAS SPECIFY .5 PSI OR 2
 PSI.
  
 3.8. SUBMIT A DETAIL SHOWING THE TYPE, LOCATION, SIZE
 AND TERMINATION OF THE GAS VENTS PER FBC-2010 FUEL GAS
 CODE SEC. 502 THRU 505.
  
 3.9. SUBMIT MANUFACTURE SHEETS FOR ALL GAS EQUIPMENT TO
 VERIFY COMPLIANCE WITH STANDARDS NFPA 54, NFPA 58, AND
 FBC-2010 FUEL GAS SEC. 402.2
  
 3.10 2010 FBC-B 916.1 CARBON MONOXIDE PROTECTION.
 EVERY SEPARATE BUILDING OR AN ADDITION TO AN EXISTING
 BUILDING FOR WHICH A PERMIT FOR NEW CONSTRUCTION IS
 ISSUED AND HAVING A FOSSIL-FUEL-BURNING HEATER OR
 APPLIANCE, A FIREPLACE, AN ATTACHED GARAGE, OR OTHER
 FEATURE, FIXTURE, OR ELEMENT THAT EMITS CARBON MONOXIDE
 AS A BYPRODUCT OF COMBUSTION SHALL HAVE AN OPERATIONAL
 CARBON MONOXIDE ALARM INSTALLED WITHIN 10 FEET OF EACH
 ROOM USED FOR SLEEPING PURPOSES IN THE NEW BUILDING OR
 ADDITION, OR AT SUCH OTHER LOCATIONS AS REQUIRED BY
 THIS CODE.
  
 916.1.1 CARBON MONOXIDE ALARM.
 THE REQUIREMENTS OF SECTION 916.1 SHALL BE SATISFIED BY
 PROVIDING FOR ONE OF THE FOLLOWING ALARM INSTALLATIONS:
  
 1. A HARD-WIRED CARBON MONOXIDE ALARM.
  
 2. A BATTERY-POWERED CARBON MONOXIDE ALARM.
  
 3. A HARD-WIRED COMBINATION CARBON MONOXIDE AND SMOKE
 ALARM.
  
 4. A BATTERY-POWERED COMBINATION CARBON MONOXIDE AND
 SMOKE ALARM.
  
 916.1.2 COMBINATION ALARMS.
 COMBINATION SMOKE/CARBON MONOXIDE ALARMS SHALL BE
 LISTED AND LABELED BY A NATIONALLY RECOGNIZED TESTING
 LABORATORY.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL
 LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH
 A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE
 SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE
 FOUND WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR
 YOUR ANTICIPATED COOPERATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved