Plan Review Notes
Plan Review Notes For Permit 14061217
Permit Number 14061217
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2014-07-09 15:31:23THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 1. PROVIDE DRAWING NOTE INDICATING ALL CONSTRUCTION AND
 DEMOLITION WORK SHALL CONFORM TO THE REQUIREMENTS OF
 NFPA 241. TRASH AND CONSTRUCTION DEBRIS SHALL BE
 REMOVED FROM THE SITE DAILY. SMOKING SHALL BE
 PROHIBITED EXCEPT IN DESIGNATED EXTERIOR AREAS. ALL
 OTHER DEMOLITION OR CONSTRUCTION AREAS SHALL HAVE "NO
 SMOKING" SIGNS POSTED. WHERE SMOKING IS PERMITTED, SAFE
 RECEPTACLES FOR SMOKING MATERIALS SHALL BE PROVIDED.
  
 2. PER NFPA 241- STANDARD FOR SAFEGUARDING
 CONSTRUCTION, ALTERATION, AND DEMOLITION OPERATIONS,
 SECTION 4.2 TEMPORARY CONSTRUCTION TRAILERS SHALL BE
 SEPARATED FROM ADJACENT TRAILERS OR STRUCTURES IN
 ACCORDANCE WITH TABLE 4.2.1. PER TABLE 4.2.1:
 1) 20 FEET EXPOSED LENGTH SHALL BE SEPARATED FROM
 ADJACENT STRUCTURES BY AT LEAST 30 FEET
 2) 30 FEET EXPOSED LENGTH SHALL BE SEPARATED FROM
 ADJACENT STRUCTURES BY AT LEAST 35 FEET
 3) 40 FEET EXPOSED LENGTH SHALL BE SEPARATED FROM
 ADJACENT STRUCTURES BY AT LEAST 40 FEET
 4) 50 FEET EXPOSED LENGTH SHALL BE SEPARATED FROM
 ADJACENT STRUCTURES BY AT LEAST 45 FEET
 5) 60 FEET EXPOSED LENGTH SHALL BE SEPARATED FROM
 ADJACENT STRUCTURES BY AT LEAST 50 FEET
 6) GREATER THAN 60 FEET EXPOSED LENGTH SHALL BE
 SEPARATED FROM ADJACENT STRUCTURES BY AT LEAST 60 FEET
 **A 75 PERCENT REDUCTION IN SEPARATION DISTANCES SHALL
 BE PERMITTED TO BE APPLIED, PROVIDED AUTOMATIC
 SPRINKLER PROTECTION IS USED IN THE EXPOSING STRUCTURE.
  
 3. PROVIDE A DRAWING NOTES TO THE FUEL SUPPLY OF THE
 GENERATOR AND BOILER.
  
 4. PROVIDE A DRAWING NOTE FOR PROVIDING AN EXTERIOR KEY
 SAFE TO ALLOW EMERGENCY RESPONDERS NON-FORCIBLE ENTRY
 INTO THE BUILDING DURING NON-BUSINESS HOURS. A KEY SAFE
 CAN BE ORDERED FROM WWW.KNOXBOX.COM
  
 5. PROVIDE A DRAWING NOTE FOR TACTILE SIGNAGE AT ALL
 REQUIRED EXIT DOORS WITH EXIT SIGNS.
  
 6. PROVIDE A DRAWING NOTE FOR STAIRWAY IDENTIFICATION:
 NEW ENCLOSED STAIRS SERVING THREE OR MORE STORIES AND
 EXISTING ENCLOSED STAIRS SERVING FIVE OR MORE STORIES
 SHALL COMPLY WITH (A) THROUGH (L).
 (A) THE STAIRS SHALL BE PROVIDED WITH SPECIAL SIGNAGE
 WITHIN THE ENCLOSURE AT EACH FLOOR LANDING.
 (B) THE SIGNAGE SHALL INDICATE THE FLOOR LEVEL.
 (C) THE SIGNAGE SHALL INDICATE THE TERMINUS OF THE TOP
 AND BOTTOM OF THE STAIR ENCLOSURE.
 (D) THE SIGNAGE SHALL INDICATE THE IDENTIFICATION OF
 THE STAIR ENCLOSURE.
 (E) THE SIGNAGE SHALL INDICATE THE FLOOR LEVEL OF, AND
 THE DIRECTION TO, EXIT DISCHARGE.
 (F) THE SIGNAGE SHALL BE LOCATED INSIDE THE ENCLOSURE
 APPROXIMATELY 60-INCHES ABOVE THE FLOOR LANDING IN A
 POSITION THAT IS VISIBLE WHEN THE DOOR IS IN THE OPEN
 OR CLOSED POSITION.
 (G) THE FLOOR LEVEL DESIGNATION SHALL ALSO BE TACTILE.
 (H) THE SIGNAGE SHALL BE PAINTED OR STENCILED ON THE
 WALL OR ON A SEPARATE SIGN SECURELY ATTACHED TO THE
 WALL.
 (I) THE STAIRWAY IDENTIFICATION LETTER SHALL BE LOCATED
 AT THE TOP OF THE SIGN IN MINIMUM 1-INCH HIGH
 LETTERING.
 (J) SIGNAGE THAT READS ?NO ROOF ACCESS? AND IS LOCATED
 UNDER THE STAIRWAY IDENTIFICATION LETTER SHALL
 DESIGNATE STAIRWAYS THAT DO NOT PROVIDE ROOF ACCESS.
 LETTERING SHALL BE A MINIMUM OF 1-INCH HIGH.
 (K) THE FLOOR LEVEL NUMBER SHALL BE LOCATED IN THE
 MIDDLE OF THE SIGN IN MINIMUM 5-INCH HIGH NUMBERS.
 MEZZANINE LEVELS SHALL HAVE THE LETTER ?M? OR OTHER
 APPROPRIATE IDENTIFICATION LETTER PRECEDING THE FLOOR
 NUMBER, WHILE BASEMENT LEVELS SHALL HAVE THE LETTER ?B?
 OR OTHER APPROPRIATE IDENTIFICATION LETTER PRECEDING
 THE FLOOR LEVEL NUMBER.
 (L) IDENTIFICATION OF THE LOWER AND UPPER TERMINUS OF
 THE STAIRWAY SHALL BE LOCATED AT THE BOTTOM OF THE SIGN
 IN MINIMUM 1-INCH HIGH LETTERS OR NUMBERS.
  
 7. SHEET A 1.01 & A 2.01 RETAIL MEZZANINE M22 SHALL NOT
 BE OCCUPIED UNTIL THE 2ND MEANS OF EGRESS IS PROVIDED
 FOR AND APPROVED.
  
 8. CLARIFICATION AND CONSISTENCY IS REQUIRED REGARDING
 ELEVATOR LOBBY DOOR RATINGS:
 SHEET A 2.01 DOOR M21 IS RATED AND APPROVED.
 SHEET A 2.03 DOOR 326 IS NOT RATED.
 SHEET A 2.11 DOORS PD 10 & 10.1 ARE NOT RATED.
 SOME DOORS ARE LABLED CORRIDOR DOORS ON THE DOOR
 SCHEDULE, SOME ARE LABELD ELEVATOR LOBBY DOORS. PLEASE
 PROVIDE JUSTIFICATION. IT IS IMPERATIVE THAT EACH DOOR
 ASSOCIATED WITH
 AN ELEVATOR LOBBY ARE RATED AND INSTALLED CONSISTENTLY
 TO ENSURE EQUAL LIFE SAFETY IN THE SAME SPACES.
  
 9. PROVIDE FOR CO MONITORING IN THE GENERATOR AND
 BOILER ROOMS.
  
 10. SHEETS A 2.00, A 2.01, M101 & M102, DO NOT SHOW A
 VENTILATION SYSTEM IN THE PORTE COCHERE, DROP OFF
 AREAS. IT IS IMPERATIVE THAT THESE AREAS HAVE
 VENTIALTION PROVIDED FOR TO REMOVE ANY BUILDUP OF
 VEHICULAR GASES, CO.
  
 11. SHEET FA 101 CO MONITORS ARE NEEDED FOR THE PORTE
 COCHERE, DROP OFF AREAS. SLEEPING ROOMS ARE DIRECTLY
 ABOVE THIS AREA AND IT IS IMPERATIVE THAT A PROTECTION
 SYSTEM IS PROVIDED TO REDUCE AND/OR ELIMINATE VEHICULAR
 GASES.
  
 12. SHEET E 103 - ADD EXIT SIGN IN MAIN CORRIDOR
 POINTING DOWN CORRIDOR 236 TO STAIR NO. 1, 235.
  
 13. SHEET E 104 - ADD EXIT SIGN IN HALLWAY OF EXTERIOR
 TERRACE 327, LEADING TO STAIR NO. 3, 312.
 - ADD EXIT SIGN OUTSIDE SOTH ELEVATOR LOBBY DOOR
 LEADING TO STAIR NO. 1, 371.
  
 14. SHEET E 106 - ADD EXIT SIGN AT SOUTH CORRIDOR
 DIVIDER HEADER LEADING TO STAIR NO. 1, 518. ( COPY THIS
 EXIT SIGN AS PROVIDED FOR SAME LOCATION ON SHEET E 105)
 - ADD EXIT SIGN AT NORTH CORRIDOR HEADER LEADING TO
 STAIR NO. 2, 513. ( COPY THIS EXIT SIGN AS PROVIDED FOR
 SAME LOCATION ON SHEET E 105)
  
 15. SHEET 107 - REMOVE EXIT SIGN IN ELEVATOR LOBBY
 PD10, SOUTH DOOR LOCATION (NO EXIT) AND ADD EXIT SIGN
 ON SUN DECK PD17, SIDE OF DOOR.
 - ADD EXIT SIGN INSIDE ELEVATOR LOBBY PD10, AT NORTH
 SIDE DOOR.
 - ADD EXIT SIGN AT NORTH SIDE OF SEATING PD12, LEADING
 TO POOL DECK AREA.
 - ADD EXIT SIGN AT NORTH SIDE OF SUN DECK PD17 AT THE
 SEATING AREA LEADING THROUGH SEATING AREA TO POOL DECK.
 - ADD EXIT SIGN AT NORTH SIDE OF POOL DECK PD02,
 LEADING TO NORTH EXIT STAIR PD01. EXIT SIGN SHALL BE
 VISABLE FROM SOUTH POOL DECK AREA.
 - ADD EXIT SIGN AT SOTH SIDE OF POOL DECK LEADING TO
 NORTH EXIT STAIR PD07. EXIT SIGN SHALL BE VISABLE FROM
 NORTH SIDE OF POOL DECK AREA.
  
 16. NO UPPER ROOF ACCESS/EGRESS IS NOTED OR READILY
 IDENTIFIABLE. PLEASE PROVIDE FOR ACCESS/EGRESS.
  
  
  
  