2014-08-06 14:07:57 | DATE: 8/6/2014 |
| PROJECT: CLEMATIS HOTEL |
| PERMIT#: 14061217 |
| CODE: 2008 EDITION OF THE NEC |
| 2010 EDITION OF THE FBC |
| 2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1, |
| ADMINISTRATION, 2012 FBC SUPPLEMENTS. |
| |
| 1ST ELECTRICAL PLAN REVIEW |
| ACTION: DENIED |
| |
| 1) THE PRIMARY PERMIT SUBMITTAL INCLUDES A FLORIDA |
| ENERGY EFFICIENCY CODE SUBMITTAL THAT INDICATES |
| COMPLIANCE WITH THE FBC FOR ENERGY. HOWEVER, THE PLANS |
| DO NOT REFLECT FULL COMPLIANCE. INDICATE FULL |
| COMPLIANCE ON THE ELECTRICAL PLANS AS FOLLOWS: |
| 2) PROVIDE A LIGHTING FIXTURE SCHEDULE, ACCOMPANIED BY |
| MANUFACTURER EQUIPMENT SUBMITTALS AND SHOP DRAWINGS ON |
| LIGHTING CONTROL AND/OR ENERGY MANAGEMENT SYSTEMS. FBC |
| 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS |
| 3) SHEET E101 |
| SEE CODE REFERENCE: FBC-E 505.2 LIGHTING CONTROLS |
| (MANDATORY). LIGHTING SYSTEMS SHALL BE PROVIDED WITH |
| CONTROLS AS REQUIRED IN SECTIONS 505.2.1, 505.2.2, |
| 505.2.3 AND 505.2.4 |
| A.) LOBBY AND SERVICE CORRIDORS. INDICATE COMPLIANCE |
| WITH FBC-E 505.2.2 AUTOMATIC LIGHTING SHUTOFF. |
| B.) ELECTRICAL RM #110, FIRE PUMP RM #112, SHOULD NOT |
| HAVE AN OS SWITCH DUE TO 505.2.2 EXCEPTION #4 SPACES |
| WHERE AN AUTOMATIC SHUTOFF WOULD ENDANGER OCCUPANT |
| SAFETY OR SECURITY. |
| C.) THE PORTE COCHERE LIGHTING DOES NOT INDICATE ANY |
| LIGHTING CONTROL FBC-E 505.2.4 EXTERIOR LIGHTING |
| CONTROLS REQUIRED. |
| D.) POLE LIGHTS AT FRONT ENTRY REQUIRE LIGHTING CONTROL |
| AND WIND LOAD CALCULATIONS. FBC 107.2.1 INFORMATION ON |
| CONSTRUCTION DOCUMENTS |
| E.) AC-R1.1 DOES NOT INDICATE A CIRCUIT OR A |
| DISCONNECT. DISCONNECTING MEANS SHALL BE LOCATED WITHIN |
| SIGHT FROM AND READILY ACCESSIBLE FROM THE |
| AIR-CONDITIONING OR REFRIGERATING EQUIPMENT. THE |
| DISCONNECTING MEANS SHALL BE PERMITTED TO BE INSTALLED |
| ON OR WITHIN THE AIR-CONDITIONING OR REFRIGERATING |
| EQUIPMENT. NEC 440.14 |
| |
| 4) SHEET E 102 |
| A.) GENERATOR RM #M10 AND THE BOILER RM #M01 SHOULD NOT |
| HAVE AN OS SWITCH DUE TO 505.2.2 EXCEPTION #4 SPACES |
| WHERE AN AUTOMATIC SHUTOFF WOULD ENDANGER OCCUPANT |
| SAFETY OR SECURITY. 505.2.4 |
| |
| 5) SHEET E103 AND SHEET E 201 |
| SLEEPING ROOMS IN HOTELS REQUIRE LIGHTING CONTROL. |
| FBC-E 505.2.1.3 ADDITIONAL CONTROLS. (3) |
| |
| 6) SHEET E 104 |
| A.) INDICATE COMPLIANCE WITH FBC-E 505.2.2 AUTOMATIC |
| LIGHTING SHUTOFF. |
| B) INDICATE CIRCUITS FOR EXIT AND EMERGENCY LIGHTING. |
| FBC 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS. |
| |
| |
| 7) SHEET E 108 |
| A.) ADDITIONAL GFI SERVICE OUTLETS ON THE ROOF FOR |
| MECHANICAL EQUIPMENT. THE RECEPTACLE SHALL BE LOCATED |
| ON THE SAME LEVEL AND WITHIN 25FT OF THE HEATING, |
| AIR-CONDITIONING, AND REFRIGERATION EQUIPMENT. SEE NEC |
| 210.63, 210.8(A)(3), AND 406.8(B)(1), |
| |
| 8) SHEET E 401 |
| A.) NOTE 4 INDICATES TO REFER TO PANEL SCHEDULES FOR |
| FEEDER SIZE. PANEL MDPAC CALLS FOR 4 RUNS OF 4, 500 |
| KCMIL AL BUT ALSO CALLS FOR A 400AMP SERVICE RATED MCB |
| WITH A CONNECTED LOAD OF 136AMPS PER PHASE. |
| CLARIFICATION IS REQUIRED. FBC 107.2.1 INFORMATION ON |
| CONSTRUCTION DOCUMENTS |
| B.) NOTE 6 INDICATES THE FIRE PUMP IS A 100HP 208V |
| 3PHASE MOTOR. A 100 HP FIRE PUMP MOTOR REQUIRES A |
| MINIMUM 400AMP SERVICE RATED OCPD AND FEEDER. RATE FIRE |
| PUMP CONTROLLER AND FEEDERS PER NEC 695. SUBMIT |
| MANUFACTURER DOCUMENTATION ON FIRE PUMP MOTOR AND |
| CONTROLER/ATS |
| C.) NOTE 13 INDICATES TO FEED THE 100HP FIRE PUMP FROM |
| GENERATOR WITH #2 WIRE. AS STATED ABOVE A 100HP MOTOR |
| REQUIRES A MUCH LARGER FEEDER. REVISE DESIGN FOR CODE |
| COMPLIANCE. SEE NEC 310, 430, 695, AND 700 |
| D.) NOTE 17 INDICATES TO FEED THE 100HP FIRE PUMP FROM |
| UTILITY WITH #2 WIRE. AS STATED ABOVE A 100HP MOTOR |
| REQUIRES A MUCH LARGER FEEDER. THERE IS NO INDICATION |
| OF A METER AHEAD OF THIS UTILITY FEEDER. REVISE DESIGN |
| FOR CODE COMPLIANCE. SEE NEC 215, 225, 230.2, 310, 430 |
| AND 695. |
| E) NOTE 20 INDICATES THE GENERATOR WILL COMPLY WITH |
| NFPA 101 AMONG OTHERS ETC... PLEASE ADD 2008 EDITION OF |
| NFPA 70, ARTICLE 700. |
| F.) NOTE 22 CALL OUT A GENERATOR BUT DOES NOT IDENTIFY |
| THE SIZE AND TYPE. IDENTIFY THE GENERATOR WITH VOLTAGE, |
| KVA/KW SIZE ADEQUATELY TO SUPPORT ALL DESIGN LOADS AND |
| PROVIDE MANUFACTURER EQUIPMENT SUBMITTALS ON THE |
| GENERATOR AND ATS AS SUPPORTING DOCUMENTATION. |
| G.) NOTE 39 INDICATES THIS SPACE TO BE THE FPL UTILITY |
| VAULT. THE NAME DESIGNATION ABOVE THIS ROOM IS |
| GENERATOR ROOM. CLARIFICATION IS REQUIRED. FBC 107.2.1 |
| INFORMATION ON CONSTRUCTION DOCUMENTS |
| H.) PANEL 1L INDICATES IT IS TO BE FED FROM PANEL |
| MDPAC. THERE IS NO LOAD INDICATED IN PANEL MDPAC ON |
| SHEET E 501. I BELIEVE THE INTENT WAS TO INDICATE THE |
| FEED FROM PANEL MDPA HOWEVER THERE IS NO LOAD INDICATED |
| IN PANEL MDPA EITHER. THEREFORE THERE HAS BEEN NO LOAD |
| CALCULATED. |
| I.) THE RISER DIAGRAM INDICATES TO REFERENCE THE PANEL |
| SCHEDULE FOR FEEDER SIZES. WHEN I REFERENCE PANEL MDPA |
| OR MDPAC FOR FEEDER SIZES FOR PANELS 2L, 3L, 4L ETC... |
| OR PANEL 2AC, 3AC, 4AC, ETC... THE NOTE IS THE SAME. TO |
| REFERENCE THE PANEL SCHEDULE FOR FEEDER. THERE ARE NO |
| PANEL SCHEDULES ON ANY OF THE E SHEETS FOR ANY OF THE |
| FLOOR PANELS 2L, 3L,4L ETC..., 2AC, 3AC, 4AC, ETC..., |
| 2R,3R, PROVIDE ALL PANEL SCHEDULES, LOADS AND FEEDERS. |
| FBC 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS. |
| J.) LOAD CALCULATIONS ARE REQUIRED FOR THE BUILDING |
| ELECTRICAL SYSTEM BASED ON THE NEC ARTICLE 220. FBC |
| 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS |
| K.) IDENTIFY ALL SERVICE METERS AND MAINS. NEC 225.37 |
| IDENTIFICATION. |
| L.) INDICATE THE REQUIRED SIGNAGE INSIDE AND OUTSIDE |
| THE BUILDING AS REQUIRED TO IDENTIFY THE GENERATOR AS |
| AN ALTERNATE SOURCE OF POWER. NEC 700.8 NEC 225.37 |
| IDENTIFICATION. |
| M.) PROVIDE MANUFACTURER EQUIPMENT PRODUCT SUBMITTALS |
| FOR THE GENERATOR, ATS AND RELATED EQUIPMENT. FBC |
| 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS |
| N) PROVIDE AND INDICATE THE TESTING AND MAINTENANCE |
| REQUIRED PER NEC 700 |
| O.) THERE IS A RUN IDENTIFIED AS 2, 4? EC (EMPTY |
| CONDUITS) FROM AN UNIDENTIFIED SOURCE NEXT TO |
| UNIDENTIFIED FPL UTILITY METER? THIS APPEARS TO |
| REPRESENT A FUTURE METER FOR A FUTURE TENANT IN WHAT IS |
| IDENTIFIED AS A FUTURE RETAIL SPACE. CLARIFICATION IS |
| REQUIRED. REVISE PLANS TO MAINTAIN GROUPING AND MAXIMUM |
| NUMBER OF MAINS. NEC 225.33 MAXIMUM NUMBER OF |
| DISCONNECTS, AND 225.34 GROUPING OF DISCONNECTS. |
| P.) PANEL K IS INDICATED ON THE THIRD LEVEL. THERE IS |
| NO MAIN INDICATED IN FRONT OF OR GROUPED WITH THE REST |
| OF THE MAINS IN THE MAIN ELECTRICAL ROOM. CLARIFICATION |
| IS REQUIRED. REVISE PLANS TO MAINTAIN GROUPING AND |
| MAXIMUM NUMBER OF MAINS. NEC 225.33 MAXIMUM NUMBER OF |
| DISCONNECTS, AND 225.34 GROUPING OF DISCONNECTS. |
| |
| 9) SHEET E 502 |
| A.) PANEL RAC IS IDENTIFIED AS A 1200AMP MLO PANEL WITH |
| A 110AMP SUPPOSED LOAD FED WITH ONE SET OF 4, 250KCMIL |
| AL W,1#4AL GRND FROM AN UNIDENTIFIED MAIN IN THE MAIN |
| ELECTRICAL ROOM. IDENTIFY THE MAIN AS MAIN #? OF 6? |
| IDENTIFY ALL SERVICE METERS AND MAINS. |
| |
| 10) PROVIDE SAFETY LABELING FOR ARC FLASH PROTECTION |
| FOR THE PANEL BOARDS AND MAIN DISCONNECTING MEANS. NEC |
| 110.16, 110.22 |
| |
| 11) VERIFY THE ELECTRICAL SERVICE DISCONNECTING MEANS |
| HAS A FAULT CURRENT RATING THAT IS SUFFICIENT AT |
| NOMINAL CIRCUIT VOLTAGE FOR THE CURRENT THAT MUST BE |
| INTERRUPTED. NEC 110.9 |
| |
| 12) PROVIDE SEPARATE ELECTRICAL PERMIT APPLICATIONS |
| ACCOMPANIED BY MANUFACTURERS EQUIPMENT SUBMITTALS, |
| PLANS, AND SHOP DRAWINGS AS REQUIRED FOR: GENERATOR, |
| FIRE ALARM, SECURITY, CCTV, DATA/COM, NETWORK, |
| STRUCTURED CABLING, AUDIO/VIDEO, LIGHTNING PROTECTION |
| AND SIGNAGE. |
| |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. SEE LINK: |
| HTTP://WPB.ORG/DEVELOPMENT /WP-CONTENT/UPLOADS/SITES/33 |
| /2013/09/APPLICATION_RESUBMITTAL_FORM_04132010.PDF |
| |
| ADDITIONALLY, PLEASE INSERT CORRECTED PAGES INTO |
| SUBMITTAL PACKAGE AND LEAVE THE PREVIOUSLY REVIEWED |
| SHEETS FOR COMPARATIVE REVIEW. |
| |
| DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421, |
| 561-805-6717 OR [email protected] |
| |
| |
| |