2014-08-06 14:07:57DATE: 8/6/2014
 PROJECT: CLEMATIS HOTEL
 PERMIT#: 14061217
 CODE: 2008 EDITION OF THE NEC
 2010 EDITION OF THE FBC
 2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1,
 ADMINISTRATION, 2012 FBC SUPPLEMENTS.
  
 1ST ELECTRICAL PLAN REVIEW
 ACTION: DENIED
  
 1) THE PRIMARY PERMIT SUBMITTAL INCLUDES A FLORIDA
 ENERGY EFFICIENCY CODE SUBMITTAL THAT INDICATES
 COMPLIANCE WITH THE FBC FOR ENERGY. HOWEVER, THE PLANS
 DO NOT REFLECT FULL COMPLIANCE. INDICATE FULL
 COMPLIANCE ON THE ELECTRICAL PLANS AS FOLLOWS:
 2) PROVIDE A LIGHTING FIXTURE SCHEDULE, ACCOMPANIED BY
 MANUFACTURER EQUIPMENT SUBMITTALS AND SHOP DRAWINGS ON
 LIGHTING CONTROL AND/OR ENERGY MANAGEMENT SYSTEMS. FBC
 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS
 3) SHEET E101
 SEE CODE REFERENCE: FBC-E 505.2 LIGHTING CONTROLS
 (MANDATORY). LIGHTING SYSTEMS SHALL BE PROVIDED WITH
 CONTROLS AS REQUIRED IN SECTIONS 505.2.1, 505.2.2,
 505.2.3 AND 505.2.4
 A.) LOBBY AND SERVICE CORRIDORS. INDICATE COMPLIANCE
 WITH FBC-E 505.2.2 AUTOMATIC LIGHTING SHUTOFF.
 B.) ELECTRICAL RM #110, FIRE PUMP RM #112, SHOULD NOT
 HAVE AN OS SWITCH DUE TO 505.2.2 EXCEPTION #4 SPACES
 WHERE AN AUTOMATIC SHUTOFF WOULD ENDANGER OCCUPANT
 SAFETY OR SECURITY.
 C.) THE PORTE COCHERE LIGHTING DOES NOT INDICATE ANY
 LIGHTING CONTROL FBC-E 505.2.4 EXTERIOR LIGHTING
 CONTROLS REQUIRED.
 D.) POLE LIGHTS AT FRONT ENTRY REQUIRE LIGHTING CONTROL
 AND WIND LOAD CALCULATIONS. FBC 107.2.1 INFORMATION ON
 CONSTRUCTION DOCUMENTS
 E.) AC-R1.1 DOES NOT INDICATE A CIRCUIT OR A
 DISCONNECT. DISCONNECTING MEANS SHALL BE LOCATED WITHIN
 SIGHT FROM AND READILY ACCESSIBLE FROM THE
 AIR-CONDITIONING OR REFRIGERATING EQUIPMENT. THE
 DISCONNECTING MEANS SHALL BE PERMITTED TO BE INSTALLED
 ON OR WITHIN THE AIR-CONDITIONING OR REFRIGERATING
 EQUIPMENT. NEC 440.14
  
 4) SHEET E 102
 A.) GENERATOR RM #M10 AND THE BOILER RM #M01 SHOULD NOT
 HAVE AN OS SWITCH DUE TO 505.2.2 EXCEPTION #4 SPACES
 WHERE AN AUTOMATIC SHUTOFF WOULD ENDANGER OCCUPANT
 SAFETY OR SECURITY. 505.2.4
  
 5) SHEET E103 AND SHEET E 201
 SLEEPING ROOMS IN HOTELS REQUIRE LIGHTING CONTROL.
 FBC-E 505.2.1.3 ADDITIONAL CONTROLS. (3)
  
 6) SHEET E 104
 A.) INDICATE COMPLIANCE WITH FBC-E 505.2.2 AUTOMATIC
 LIGHTING SHUTOFF.
 B) INDICATE CIRCUITS FOR EXIT AND EMERGENCY LIGHTING.
 FBC 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
  
  
 7) SHEET E 108
 A.) ADDITIONAL GFI SERVICE OUTLETS ON THE ROOF FOR
 MECHANICAL EQUIPMENT. THE RECEPTACLE SHALL BE LOCATED
 ON THE SAME LEVEL AND WITHIN 25FT OF THE HEATING,
 AIR-CONDITIONING, AND REFRIGERATION EQUIPMENT. SEE NEC
 210.63, 210.8(A)(3), AND 406.8(B)(1),
  
 8) SHEET E 401
 A.) NOTE 4 INDICATES TO REFER TO PANEL SCHEDULES FOR
 FEEDER SIZE. PANEL MDPAC CALLS FOR 4 RUNS OF 4, 500
 KCMIL AL BUT ALSO CALLS FOR A 400AMP SERVICE RATED MCB
 WITH A CONNECTED LOAD OF 136AMPS PER PHASE.
 CLARIFICATION IS REQUIRED. FBC 107.2.1 INFORMATION ON
 CONSTRUCTION DOCUMENTS
 B.) NOTE 6 INDICATES THE FIRE PUMP IS A 100HP 208V
 3PHASE MOTOR. A 100 HP FIRE PUMP MOTOR REQUIRES A
 MINIMUM 400AMP SERVICE RATED OCPD AND FEEDER. RATE FIRE
 PUMP CONTROLLER AND FEEDERS PER NEC 695. SUBMIT
 MANUFACTURER DOCUMENTATION ON FIRE PUMP MOTOR AND
 CONTROLER/ATS
 C.) NOTE 13 INDICATES TO FEED THE 100HP FIRE PUMP FROM
 GENERATOR WITH #2 WIRE. AS STATED ABOVE A 100HP MOTOR
 REQUIRES A MUCH LARGER FEEDER. REVISE DESIGN FOR CODE
 COMPLIANCE. SEE NEC 310, 430, 695, AND 700
 D.) NOTE 17 INDICATES TO FEED THE 100HP FIRE PUMP FROM
 UTILITY WITH #2 WIRE. AS STATED ABOVE A 100HP MOTOR
 REQUIRES A MUCH LARGER FEEDER. THERE IS NO INDICATION
 OF A METER AHEAD OF THIS UTILITY FEEDER. REVISE DESIGN
 FOR CODE COMPLIANCE. SEE NEC 215, 225, 230.2, 310, 430
 AND 695.
 E) NOTE 20 INDICATES THE GENERATOR WILL COMPLY WITH
 NFPA 101 AMONG OTHERS ETC... PLEASE ADD 2008 EDITION OF
 NFPA 70, ARTICLE 700.
 F.) NOTE 22 CALL OUT A GENERATOR BUT DOES NOT IDENTIFY
 THE SIZE AND TYPE. IDENTIFY THE GENERATOR WITH VOLTAGE,
 KVA/KW SIZE ADEQUATELY TO SUPPORT ALL DESIGN LOADS AND
 PROVIDE MANUFACTURER EQUIPMENT SUBMITTALS ON THE
 GENERATOR AND ATS AS SUPPORTING DOCUMENTATION.
 G.) NOTE 39 INDICATES THIS SPACE TO BE THE FPL UTILITY
 VAULT. THE NAME DESIGNATION ABOVE THIS ROOM IS
 GENERATOR ROOM. CLARIFICATION IS REQUIRED. FBC 107.2.1
 INFORMATION ON CONSTRUCTION DOCUMENTS
 H.) PANEL 1L INDICATES IT IS TO BE FED FROM PANEL
 MDPAC. THERE IS NO LOAD INDICATED IN PANEL MDPAC ON
 SHEET E 501. I BELIEVE THE INTENT WAS TO INDICATE THE
 FEED FROM PANEL MDPA HOWEVER THERE IS NO LOAD INDICATED
 IN PANEL MDPA EITHER. THEREFORE THERE HAS BEEN NO LOAD
 CALCULATED.
 I.) THE RISER DIAGRAM INDICATES TO REFERENCE THE PANEL
 SCHEDULE FOR FEEDER SIZES. WHEN I REFERENCE PANEL MDPA
 OR MDPAC FOR FEEDER SIZES FOR PANELS 2L, 3L, 4L ETC...
 OR PANEL 2AC, 3AC, 4AC, ETC... THE NOTE IS THE SAME. TO
 REFERENCE THE PANEL SCHEDULE FOR FEEDER. THERE ARE NO
 PANEL SCHEDULES ON ANY OF THE E SHEETS FOR ANY OF THE
 FLOOR PANELS 2L, 3L,4L ETC..., 2AC, 3AC, 4AC, ETC...,
 2R,3R, PROVIDE ALL PANEL SCHEDULES, LOADS AND FEEDERS.
 FBC 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
 J.) LOAD CALCULATIONS ARE REQUIRED FOR THE BUILDING
 ELECTRICAL SYSTEM BASED ON THE NEC ARTICLE 220. FBC
 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS
 K.) IDENTIFY ALL SERVICE METERS AND MAINS. NEC 225.37
 IDENTIFICATION.
 L.) INDICATE THE REQUIRED SIGNAGE INSIDE AND OUTSIDE
 THE BUILDING AS REQUIRED TO IDENTIFY THE GENERATOR AS
 AN ALTERNATE SOURCE OF POWER. NEC 700.8 NEC 225.37
 IDENTIFICATION.
 M.) PROVIDE MANUFACTURER EQUIPMENT PRODUCT SUBMITTALS
 FOR THE GENERATOR, ATS AND RELATED EQUIPMENT. FBC
 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS
 N) PROVIDE AND INDICATE THE TESTING AND MAINTENANCE
 REQUIRED PER NEC 700
 O.) THERE IS A RUN IDENTIFIED AS 2, 4? EC (EMPTY
 CONDUITS) FROM AN UNIDENTIFIED SOURCE NEXT TO
 UNIDENTIFIED FPL UTILITY METER? THIS APPEARS TO
 REPRESENT A FUTURE METER FOR A FUTURE TENANT IN WHAT IS
 IDENTIFIED AS A FUTURE RETAIL SPACE. CLARIFICATION IS
 REQUIRED. REVISE PLANS TO MAINTAIN GROUPING AND MAXIMUM
 NUMBER OF MAINS. NEC 225.33 MAXIMUM NUMBER OF
 DISCONNECTS, AND 225.34 GROUPING OF DISCONNECTS.
 P.) PANEL K IS INDICATED ON THE THIRD LEVEL. THERE IS
 NO MAIN INDICATED IN FRONT OF OR GROUPED WITH THE REST
 OF THE MAINS IN THE MAIN ELECTRICAL ROOM. CLARIFICATION
 IS REQUIRED. REVISE PLANS TO MAINTAIN GROUPING AND
 MAXIMUM NUMBER OF MAINS. NEC 225.33 MAXIMUM NUMBER OF
 DISCONNECTS, AND 225.34 GROUPING OF DISCONNECTS.
  
 9) SHEET E 502
 A.) PANEL RAC IS IDENTIFIED AS A 1200AMP MLO PANEL WITH
 A 110AMP SUPPOSED LOAD FED WITH ONE SET OF 4, 250KCMIL
 AL W,1#4AL GRND FROM AN UNIDENTIFIED MAIN IN THE MAIN
 ELECTRICAL ROOM. IDENTIFY THE MAIN AS MAIN #? OF 6?
 IDENTIFY ALL SERVICE METERS AND MAINS.
  
 10) PROVIDE SAFETY LABELING FOR ARC FLASH PROTECTION
 FOR THE PANEL BOARDS AND MAIN DISCONNECTING MEANS. NEC
 110.16, 110.22
  
 11) VERIFY THE ELECTRICAL SERVICE DISCONNECTING MEANS
 HAS A FAULT CURRENT RATING THAT IS SUFFICIENT AT
 NOMINAL CIRCUIT VOLTAGE FOR THE CURRENT THAT MUST BE
 INTERRUPTED. NEC 110.9
  
 12) PROVIDE SEPARATE ELECTRICAL PERMIT APPLICATIONS
 ACCOMPANIED BY MANUFACTURERS EQUIPMENT SUBMITTALS,
 PLANS, AND SHOP DRAWINGS AS REQUIRED FOR: GENERATOR,
 FIRE ALARM, SECURITY, CCTV, DATA/COM, NETWORK,
 STRUCTURED CABLING, AUDIO/VIDEO, LIGHTNING PROTECTION
 AND SIGNAGE.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. SEE LINK:
 HTTP://WPB.ORG/DEVELOPMENT /WP-CONTENT/UPLOADS/SITES/33
 /2013/09/APPLICATION_RESUBMITTAL_FORM_04132010.PDF
  
 ADDITIONALLY, PLEASE INSERT CORRECTED PAGES INTO
 SUBMITTAL PACKAGE AND LEAVE THE PREVIOUSLY REVIEWED
 SHEETS FOR COMPARATIVE REVIEW.
  
 DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421,