2014-06-26 13:21:45DATE: 6/26/2014
 PROJECT: FLAGLER RESIDENCE ELECTRICAL AS BUILTS-SHEET
 E-03
 PERMIT#: 13070545
 CODE: 2008 EDITION OF THE NEC
 2010 EDITION OF THE FBC
 2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1,
 ADMINISTRATION, 2012 FBC SUPPLEMENTS.
  
 1ST ELECTRICAL PLAN REVIEW
 ACTION: PROVISO
  
 NOTE:
 PLAN REVEIW APPROVED FOR SHEETS E-01 AND E-02 ONLY.
 SHEET E-03 TO BE SUBMITTED AT A LATER DATE. TAKE THE
 FOLLOWING INTP ACCOUNT WHEN RESUBMITTING SHEET E-03
  
 1) RISER DIAGRAM NEEDS TO BE REVISED TO INDICATE THE
 FOLLOWING:
 A) CORRECT CONDUIT LAYOUT FOR FUTURE GENERATOR. I
 BELIEVE THE INTENT WAS TO HAVE TWO SETS OF CONDUITS
 FROM THE FUTURE GENERATOR. ONE SET TO EACH OF THE TWO
 ATS'S
 B) CORRECT GROUNDING DETAIL. CURRENTLY SHOWS UFER
 GROUND ONLY.
  
 2) THE FEEDER SCHEDULE IS UNCLEAR AND CONFLICTS WITH
 THE RISER DIAGRAM. I SUGGEST USING EITHER A FEEDER
 SCHEDULE OR CALL OUT EACH CONDUIT AND WIRE DETAIL ON
 THE RISER DIAGRAM ITSELF. NOT BOTH. IF BOTH ARE USED
 THEY NEED TO MATCH AND BE CLEAR AS TO WHICH CONDUIT
 LOCATION IS REPRESENTED BY THE "TYPE"
  
 3) PANEL SCHEDULES SHALL BE CORRECTED TO MATCH THE
 RISER DIAGRAM. THE RISER DIAGRAM INDICATES PANEL "A"
 FEEDS PANEL "F" BUT IS NOT INDICATED IN THE PANEL "A"
 SCHEDULE.
  
 4) PANEL SCHEDULES SHALL BE CORRECTED TO MATCH THE
 RISER DIAGRAM. THE RISER DIAGRAM INDICATES PANEL "B"
 FEEDS PANEL "E" BUT IS NOT INDICATED IN THE PANEL "B"
 SCHEDULE.
  
 5) THE RISER DIAGRAM INDICATES FOUR PANELS LOCATED IN
 THE GARAGE. THE FLOOR PLAN INDICATES ONLY THREE.
 CORRECT ONE OR THE OTHER.
  
 6) LOAD CALCULATIONS SHALL BE INCLUDED FOR EACH PANEL
 TO INDICATE THE PANEL PROPOSED IS ADEQUATE TO SUPPORT
 THE LOAD.
  
 7) AT LEAST 50% OF THE LAMPS IN PERMANENTLY INSTALLED
 LIGHT FIXTURES SHALL BE HIGH EFFICIENCY. FBC-R 404.1.
 PROVIDE FIXTURE SCHEDULE.
  
 8) RECESSED LIGHTING TO BE AIR TIGHT AND IC RATED.
 FBC-R402.4.5. PROVIDE FIXTURE SCHEDULE.
  
 9) THE GROUNDING ELECTRODE SYSTEM SHALL BE INDICATED ON
 THE RISER AS IT WILL BE INSTALLED AND AS DESCRIBED IN
 SECTION III OF THE NEC 250
  
 10) THE SERVICE DISCONNECTING MEANS SHALL BE INSTALLED
 AT A READILY ACCESSIBLE LOCATION INSIDE OR OUTSIDE THE
 BUILDING NEAREST THE POINT OF SERVICE ENTRANCE IN
 ACCORDANCE WITH NEC 230.70. PLEASE INDICATE THE
 LOCATION OF THE ELECTRICAL SERVICE ENTRANCE AND
 DISCONNECTING MEANS.
  
 11) AN INTERSYSTEM BONDING STRIP IS REQUIRED AT THE
 MAIN SERVICE GROUND. NEC 250.94
  
 12) THE INSTALLATION OF ELECTRICAL WIRING FOR, AND
 EQUIPMENT IN AND ADJACENT TO, NATURAL OR ARTIFICIALLY
 MADE BODIES OF WATER NOT COVERED BY OTHER ARTICLES IN
 THIS CODE SHALL COMPLY WITH THE PROVISIONS OF THE NEC
 682.
  
 NOTE: A SEPARATE ELECTRICAL PERMIT APPLICATION SHALL BE
 SUBMITTED INCLUDING ALL DETAILED PLANS, SHOP DRAWINGS,
 EQUIPMENT SUBMITTALS, PRODUCT APPROVALS, ETC? IS
 REQUIRED FOR ALL OF THE FOLLOWING: SWIMMING POOL, DOCK,
 GENERATOR, AUDIO, VIDEO, NETWORK, SECURITY, CCTV.
  
 DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421,
 561-805-6717 OR AT [email protected]
  