Plan Review Notes For Permit 14060946 |
Permit Number |
14060946 |
|
Review Stop |
M |
Sequence Number |
3 |
|
Notes |
Date |
Text |
2015-01-07 10:07:39 | PLAN REVIEW COMMENTS | | | | | | 3RD REVIEW: FBC 2010 | | ROBERT MCDOUGAL, CBO | | COMMERCIAL COMBINATION PLANS EXAMINER | | (561) 805-6714 | | [email protected] | | | | MECHANICAL | | | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | 1) THERE ARE HVAC LOAD CALCULATIONS IN THIS SUBMITTAL | | AND THE DRAWINGS INDICATE THAT THERE IS AN EXISTING | | HVAC SYSTEM. PLEASE CLARIFY. FBC 107.2.1 | | | | 2) THE TOTAL COOLING AND HEATING BTUH ON THE ENERGY | | CALULATION FORM DOES NOT MATCH THE HEATING AND COOLING | | BTUH LISTED ON THE ENERGY FORM 405-10. | | | | 3) FBC -107.3.5.1.4 MECHANICAL MINIMUM PLAN REVIEW | | CRITERIA: SHOW, EXHAUST SYSTEMS, CLOTHES DRYER EXHAUST, | | KITCHEN EQUIPMENT EXHAUST, SPECIALTY EXHAUST SYSTEMS, | | EQUIPMENT, EQUIPMENT LOCATION, MAKE-UP AIR, | | ROOF-MOUNTED EQUIPMENT, DUCT SYSTEMS, VENTILATION, | | COMBUSTION AIR, CHIMNEYS, FIREPLACES AND VENTS, | | APPLIANCES, BOILERS, REFRIGERATION, BATHROOM | | VENTILATION, LABORATORY, DESIGN FLOOD ELEVATION. | | PROVIDE TWO SETS OF MECHANICAL PLANS THAT SHOW ANY NEW | | MECHANICAL WORK OR DUCTWORK THAT IS BEING DONE, | | INCLUDING THE NEW DROP THAT IS REQUIRED TO SUPPLY HEAT | | TO THE NEW FAMILY ROOM PER FBC-R303.8 . | | | | 4) IN ORDER TO REDUCE PLAN REVIEW TIMES AND PROVIDE | | CLARIFICATION, PLEASE SUBMIT A RESPONSE LETTER | | INDICATING HOW EACH OF THE REVIEW COMMENTS HAS BEEN | | ADDRESSED. FBC 107.2.1.3 | | | | | | | | |
|