 PROJECT: MESTON RESIDENCE REMODEL
 PERMIT#: 14060946
 CODE: 2008 EDITION OF THE NEC, 2010 EDITION OF THE FBC
 ,2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1,
 ADMINISTRATION, 2012 FBC SUPPLEMENTS.
 3RD ELECTRICAL PLAN REVIEW
 ACTION: APPROVED WITH EXCEPTION
  
 1) VERIFY COMPLIANCE WITH THE NEC 210.8 AND
 210.11(C)(3) THAT REQUIRES AT LEAST ONE 20AMP GFCI
 BRANCH CIRCUIT FOR THE BATHROOM.
  
 2) VERIFY COMPLIANCE WITH 408.4 REVISE THE PANEL
 SCHEDULE TO IDENTIFY EVERY CIRCUIT AND CIRCUIT
 MODIFICATION AS TO ITS CLEAR, EVIDENT, AND SPECIFIC
 PURPOSE OR USE. NEC 408.4
  
 3) VERIFY COMPLIANCE WITH NEC 110.58 A DISCONNECT IS
 REQUIRED WITHIN SIGHT OF THE IRRIGATION PUMP.
  
 DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421,