2014-10-11 09:28:472010 FBC / 2008 NEC
  
 DENIED BY ELECTRIC
  
 1) FBC- 107.3.5.3 - PROVIDE AN ELECTRIC SERVICE RISER
 DIAGRAM WITH WIRE SIZES, CONDUIT DETAIL AND GROUNDING
 DETAIL.
  
 2) SHOW COMPLIANCE WITH NEC 250.50 WHICH REQUIRES ALL
 ELECTRODES THAT ARE PRESENT TO BE BONDED.
  
 3) SHOW COMPLIANCE WITH NEC 250.94 FOR INTER-SYSTEM
 BONDING.
  
 4) SHOW COMPLIANCE WITH NEC 210.52 FOR RECEPTACLE
 OUTLET SPACING. THE RECEPTACLE SPACING IN THE DEN NEEDS
 TO BE SUCH THAT NO POINT MEASURED HORIZONTALLY ALONG
 THE FLOOR LINE IN ANY WALL SPACE IS MORE THAN 6 FEET
 FROM A RECEPTACLE.
  
 5) NEC 210.12 (B) - OUTLETS TO BE AFCI PROTECTED.
  
 6) NEC 406.11 - TAMPER-RESISTANT RECEPTACLES ARE
 REQUIRED.
  
 7) NEC 250.56 - SERVICE GROUNDING ELECTRODE TO BE
 AUGMENTED BY AN ADDITIONAL ELECTRODE 6 FEET AWAY OR
 PROVIDE EVIDENCE OF RESISTANCE TO GROUND OF 25 OHMS OR
 LESS.
  
 8) NEC 110.9 - SPECIFY THE A.I.C. RATING OF THE
 ELECTRICAL EQUIPMENT ON THE PLANS.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714