2014-10-11 10:11:48 | 2010 FBC |
| |
| DENIED BY BUILDING |
| |
| 1) TWO SETS OF NEW PLANS THAT ARE DIFFERENT FROM THE |
| ORIGINAL ONES, WITH A DIFFERENT SCOPE OF WORK AND A |
| DIFFERENT DESIGN PROFESSIONAL (ENGINEER) WERE |
| SUBMITTED. PLEASE CLARIFY THE INTENT OF THIS SUBMITTAL. |
| IF THE WORK THAT WAS SPECIFIED ON THE PERMIT |
| APPLICATION AND SHOWN ON THE FIRST SET OF DRAWINGS IS |
| TO BE DONE, THEN SUBMIT PLANS FROM THE NEW DESIGNER OF |
| RECORD THAT CLEARLY SHOWS THE TOTAL SCOPE OF THE |
| PROPOSED WORK. INCLUDE THE STRUCTURAL REPAIR DETAILS, |
| THE ADDITION AND THE NEW EXTERIOR DOORS & WINDOWS. |
| |
| 2) THIS STRUCTURE'S FOOT PRINT AND LIVING AREA SQUARE |
| FOOTAGE (420 SQFT) IN THE PALM BEACH COUNTY PROPERTY |
| APPRAISER'S RECORDS DOES NOT MATCH WHAT IS SPECIFIED ON |
| THE PLANS (1080 SQFT). THE CITY DOES NOT HAVE ANY |
| RECORD OF THIS ADDITIONAL SQUARE FOOTAGE BEING ADDED. |
| UPON COMPARISON IT APPEARS THAT THE UNFINISHED CARPORT |
| AND STORAGE ROOM HAVE BEEN CONVERTED TO LIVING SPACE. |
| THE PLANS WILL NEED TO ADDRESS THIS ISSUE. FBC 107.2 |
| |
| 3) PROVIDE DIMENSIONS OF THE STRUCTURE AND THE ROOMS ON |
| THE PLANS. FBC 107.2.1 |
| |
| 4) SUBMIT TWO COPIES OF A SURVEY AND SITE PLAN. SHOW |
| LOCATIONS OF A STRUCTURES AND DISTANCES TO PROPERTY |
| LINES. FBC 107.2.1.3 |
| |
| 5) THE ENERGY CALCULATION FORM IS REQUIRED TO BE SIGNED |
| AND DATED BY THE OWNER/AGENT PER FBC ENERGY SECTION |
| 103. |
| |
| 6) INDICATE ALL NEW OR REPLACED WINDOWS AND DOORS ON |
| THE PLANS AND SPECIFY THEIR TYPES AND SIZES. CITY |
| AMENDMENTS 107.2.1 |
| |
| 7) SUBMIT TWO COPIES OF STATE OR MIAMI-DADE PRODUCT |
| APPROVALS FOR THE TRUSS ANCHORS, STRAPS AND CONNECTORS |
| AS REQUIRED BY DCA RULE 9N-3. ALTERNATELY, THEY CAN BE |
| LISTED ON THE PLANS IN AN ANCHOR SCHEDULE WITH THEIR |
| FL# OR NOA NUMBER. |
| |
| 8) THE PRODUCT APPROVALS ARE REQUIRED TO BE REVIEWED |
| AND APPROVED IN WRITING BY THE DESIGNER OF RECORD. CITY |
| AMENDMENTS 107.3.4.1 |
| |
| 9) THE DESIGN PRESSURES OF +62.9 PSF AND -68.3 PSF FOR |
| THE WINDOWS AND DOORS SPECIFIED ON THE PLANS APPEAR TO |
| BE HIGH FOR THIS STRUCTURE LOCATED IN EXPOSURE C WITH A |
| 170 VULT WINDSPEED. THIS COULD REQUIRE PRODUCT |
| APPROVALS WITH HIGHER DESIGN PRESSURES FOR THE DOORS |
| AND WINDOWS. FBC R301.2.1 |
| |
| 10) THE 2007 EDITION OF THE EXISTING BUILDING CODE IS |
| INCORRECTLY SPECIFIED. THE 2010 FBC EXISTING BUILDING |
| IS THE ONE THAT APPLIES. |
| |
| 11) THE SCOPE OF WORK STATES TO BRING THE MAIN HOUSE UP |
| TO THE 2010 NEC. THE 2008 NEC IS THE CORRECT REFERENCE. |
| 2010 FBC-R CHAPTER 43. |
| |
| 12) THE VALUE FOR THE WORK IS SPECIFIED AS $8500.00, |
| WHICH APPEARS TO BE LOW. PLEASE SUBMIT A COPY OF THE |
| SIGNED CONTRACT. CITY AMENDMENTS 109.3 |
| |
| 13) AN IMPACT FEE REVIEW BY PALM BEACH COUNTY WILL BE |
| REQUIRED FOR THE AREA THAT WAS CONVERTED TO LIVING |
| SPACE. |
| |
| 14) PRODUCT APPROVALS WERE SUBMITTED FOR ASPHALT ROOF |
| SINGLES, HOWEVER ROOFING WAS NOT INDICATED ON THE |
| PLANS. PLEASE CLARIFY. FBC 107.2.1 |
| |
| 15) IN ORDER TO REDUCE PLAN REVIEW TIME AND CLARIFY THE |
| SCOPE OF THE PROJECT, PLEASE SUBMIT A RESPONSE LETTER |
| INDICATING HOW EACH REVIEW COMMENT HAS BEEN ADDRESSED. |
| |