Plan Review Notes
Plan Review Notes For Permit 14060946
Permit Number 14060946
Review Stop E
Sequence Number 1
Notes
Date Text
2014-07-14 07:01:572010 FBC / 2008 NEC
  
 DENIED BY ELECTRIC
  
 1) SHOW COMPLIANCE WITH FBCR 314.3.1. WHEN ALTERATIONS,
 REPAIRS OR ADDITIONS REQUIRING A PERMIT OCCUR, THE
 DWELLING SHALL BE EQUIPPED WITH SMOKE ALARMS AS
 REQUIRED FOR NEW DWELLINGS.
  
 2) SHOW COMPLIANCE WITH NEC 250.50 WHICH REQUIRES ALL
 ELECTRODES THAT ARE PRESENT TO BE BONDED.
  
 3) SHOW COMPLIANCE WITH NEC 250.94 FOR INTER-SYSTEM
 BONDING.
  
 4) SHOW COMPLIANCE WITH NEC 210.52 FOR RECEPTACLE
 OUTLET SPACING. THE WALL SPACES THAT ARE 2 FT OR MORE
 IN WIDTH BETWEEN THE DOORS IN THE MASTER BEDROOM AND
 BEDROOM #2 ARE REQUIRED TO HAVE A RECEPTACLE. ALSO THE
 RECEPTACLE SPACING IN THE NEW FAMILY ROOM NEEDS TO BE
 SUCH THAT NO POINT MEASURED HORIZONTALLY ALONG THE
 FLOOR LINE IN ANY WALL SPACE IS MORE THAN 6 FEET FROM A
 RECEPTACLE.
  
 5) SHOW COMPLIANCE WITH NEC 210.52 (E)(1) WHICH
 REQUIRES A RECEPTACLE AT THE FRONT AND REAR OF THE
 DWELLING.
  
 6) SHOW COMPLIANCE WITH NEC 210.63 FOR THE REQUIRED
 HEATING AND A/C RECEPTACLE FOR THE SERVICING OF THE A/C
 CONDENSING UNIT AT THE EXTERIOR OF THE DWELLING.
  
 7) SHOW COMPLIANCE WITH NEC 210.8(B) FOR GROUND FAULT
 CIRCUIT- INTERRUPTER PROTECTION FOR OUTDOOR RECEPTACLES
 AND NEC 406.8 FOR WEATHER PROTECTION OF RECEPTACLES IN
 WET LOCATIONS.
  
 8) THE NAME AND SIGNATURE OF THE PERSON THAT IS
 RESPONSIBLE FOR THE DESIGN IS REQUIRED ON THE
 ELECTRICAL PLANS. CITY AMENDMENTS 107.2.1
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]