Plan Review Notes
Plan Review Notes For Permit 14060942
Permit Number 14060942
Review Stop B
Sequence Number 3
Notes
Date Text
2014-08-25 07:45:002010 FBC
  
 DENIED BY BUILDING
  
 1) THE ROOFING INFORMATION THAT WAS SUBMITTED IS NOT
 CORRECT. THE PLANS SHOW AN INSULATED FLAT ROOF. THE
 SYSTEM THAT WAS SELECTED IS FOR A NON-INSULATED DECK.
 THE RAS 117 ENHANCED FASTENING CALCULATIONS THAT WERE
 SUBMITTED ARE FOR MECHANICALLY FASTENED INSULATION,
 HOWEVER, NONE OF THE INSULATED SYSTEMS IN NOA NO.
 14-0224.03 HAVE MECHANICALLY FASTENED INSULATION. ONLY
 THE ANCHOR SHEET NEEDS ENHANCED FASTENING. THE
 INSULATION IS ADHERED TO THE ANCHOR SHEET WITH HOT
 ASPHALT. I'LL LET YOU KNOW IF THERE IS ANY THING ELSE
 THAT NEEDS TO BE CORRECTED. PLEASE CORRECT. CITY
 AMENDMENTS 107.2.1
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]