Notes |
Date |
Text |
2014-07-05 12:43:57 | ****PROVISO**** | | ****ISSUED AT CONTRACTOR'S RISK**** | | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | 561-805-6724 [email protected] | | FBC FLORIDA BUILDING CODE 2010 | | FBC R FLORIDA BUILDING CODE 2010 RESIDENTIAL | | | | PROVISO #1: NO ROOM DESIGNATIONS SHOWN FOR THE OPENINGS | | MARKED AS EGRESS. | | | | EMERGENCY MEANS OF ESCAPE FBC R310.4 REQUIRED AND IS TO | | COMPLY WITH THE FOLLOWING: | | | | THE MEANS OF ESCAPE SHALL BE WITHIN THE FIRST FLOOR OF | | THE DWELLING OR DWELLING UNIT AND SHALL NOT BE LOCATED | | WITHIN A GARAGE WITHOUT A SIDE-HINGED DOOR LEADING | | DIRECTLY TO THE EXTERIOR. OCCUPANTS IN ANY PART OF THE | | DWELLING OR DWELLING UNIT SHALL BE ABLE TO ACCESS THE | | MEANS OF ESCAPE WITHOUT PASSING THROUGH A LOCKABLE DOOR | | NOT UNDER THEIR CONTROL. | | | | IF THE EMERGENCY MEANS OF ESCAPE SHOWN ON THE PLAN DOES | | NOT COMPLY WITH THIS REQUIREMENT, A REVISION IS | | REQUIRED. | | | | PROVISO #2: INSTALLATION SCHEDULE FOR PANELS, | | HORIZONTAL INSTALLATION, STATES THAT SUBSTRATE IS | | CONCRETE. PLANS FOR THIS HOUSE SHOWS A BLOCK STRUCTURE, | | SO THE SUBSTRATE WOULD BE BLOCK (FILLED CELLS), NOT | | CONCRETE. | | | | VERIFY THAT ANCHOR SPACING COMPLIES WITH BLOCK | | SUBSTRATE. IF IT DOES NOT, SUBMIT A REVISION. | | | | |
|