2014-06-26 06:57:19 | PLUMBING PLAN REVIEW |
| REVISION: 14060885 |
| PERMIT: 14050971 |
| ADD: 640 FOREST HILL BLVD |
| CONT: DURHAM BROTHERS |
| TEL: (561)315-1835 |
| |
| 2010 FLORIDA BUILDING CODE W |
| * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION |
| 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013. |
| |
| 2010 EXISTING BUILDING CODE LEVEL II 701.3 |
| COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, |
| SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS |
| OF THE FLORIDA BUILDING CODE, BUILDING. |
| |
| 1ST REVIEW |
| DATE: THURS. JUNE 26/ 2014 |
| ACTION: DENIED |
| |
| REVISION (1ST REVIEW) IS FOR PLUMBING UNDER THE MASTER |
| PERMIT. |
| |
| 1A) THE PLANS SHOW THE LAV AND SINK TYING INTO THE SAME |
| STACK/ VENT. 2010 FBC-R P3108.2.1 HORIZONTAL WET VENT. |
| THE DRY-VENT CONNECTION FOR A HORIZONTAL WET-VENT |
| SYSTEM SHALL BE AN INDIVIDUAL VENT OR A COMMON VENT FOR |
| ANY BATHROOM GROUP FIXTURE, EXCEPT AN EMERGENCY FLOOR |
| DRAIN. WHERE THE DRY VENT CONNECTS TO A WATER CLOSET |
| FIXTURE DRAIN, THE DRAIN SHALL CONNECT HORIZONTALLY TO |
| THE HORIZONTAL WET VENT SYSTEM. NOT MORE THAN ONE |
| WET-VENTED FIXTURE DRAIN SHALL DISCHARGE UPSTREAM OF |
| THE DRY-VENTED FIXTURE DRAIN CONNECTION. |
| |
| 1B) P3108.1 HORIZONTAL WET VENT PERMITTED. ANY |
| COMBINATION OF FIXTURES WITHIN TWO BATHROOM GROUPS |
| LOCATED ON THE SAME FLOOR LEVEL ARE PERMITTED TO BE |
| VENTED BY A HORIZONTAL WET VENT. THE WET VENT SHALL BE |
| CONSIDERED THE VENT FOR THE FIXTURES AND SHALL EXTEND |
| FROM THE CONNECTION OF THE DRY VENT ALONG THE DIRECTION |
| OF THE FLOW IN THE DRAIN PIPE TO THE MOST DOWNSTREAM |
| FIXTURE DRAIN CONNECTION. EACH FIXTURE DRAIN SHALL |
| CONNECT HORIZONTALLY TO THE HORIZONTAL BRANCH BEING WET |
| VENTED OR SHALL HAVE A DRY VENT. EACH WET-VENTED |
| FIXTURE DRAIN SHALL CONNECT INDEPENDENTLY TO THE |
| HORIZONTAL WET VENT. ONLY THE FIXTURES WITHIN THE |
| BATHROOM GROUPS SHALL CONNECT TO THE WET-VENTED |
| HORIZONTAL BRANCH DRAIN. ANY ADDITIONAL FIXTURES SHALL |
| DISCHARGE DOWNSTREAM OF THE HORIZONTAL WET VENT. |
| |
| WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION & |
| REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL |
| LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH |
| A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE |
| SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE |
| FOUND WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR |
| YOUR ANTICIPATED COOPERATION. |
| |