2014-06-26 06:57:19PLUMBING PLAN REVIEW
 REVISION: 14060885
 PERMIT: 14050971
 ADD: 640 FOREST HILL BLVD
 CONT: DURHAM BROTHERS
 TEL: (561)315-1835
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: THURS. JUNE 26/ 2014
 ACTION: DENIED
  
 REVISION (1ST REVIEW) IS FOR PLUMBING UNDER THE MASTER
 PERMIT.
  
 1A) THE PLANS SHOW THE LAV AND SINK TYING INTO THE SAME
 STACK/ VENT. 2010 FBC-R P3108.2.1 HORIZONTAL WET VENT.
 THE DRY-VENT CONNECTION FOR A HORIZONTAL WET-VENT
 SYSTEM SHALL BE AN INDIVIDUAL VENT OR A COMMON VENT FOR
 ANY BATHROOM GROUP FIXTURE, EXCEPT AN EMERGENCY FLOOR
 DRAIN. WHERE THE DRY VENT CONNECTS TO A WATER CLOSET
 FIXTURE DRAIN, THE DRAIN SHALL CONNECT HORIZONTALLY TO
 THE HORIZONTAL WET VENT SYSTEM. NOT MORE THAN ONE
 WET-VENTED FIXTURE DRAIN SHALL DISCHARGE UPSTREAM OF
 THE DRY-VENTED FIXTURE DRAIN CONNECTION.
  
 1B) P3108.1 HORIZONTAL WET VENT PERMITTED. ANY
 COMBINATION OF FIXTURES WITHIN TWO BATHROOM GROUPS
 LOCATED ON THE SAME FLOOR LEVEL ARE PERMITTED TO BE
 VENTED BY A HORIZONTAL WET VENT. THE WET VENT SHALL BE
 CONSIDERED THE VENT FOR THE FIXTURES AND SHALL EXTEND
 FROM THE CONNECTION OF THE DRY VENT ALONG THE DIRECTION
 OF THE FLOW IN THE DRAIN PIPE TO THE MOST DOWNSTREAM
 FIXTURE DRAIN CONNECTION. EACH FIXTURE DRAIN SHALL
 CONNECT HORIZONTALLY TO THE HORIZONTAL BRANCH BEING WET
 VENTED OR SHALL HAVE A DRY VENT. EACH WET-VENTED
 FIXTURE DRAIN SHALL CONNECT INDEPENDENTLY TO THE
 HORIZONTAL WET VENT. ONLY THE FIXTURES WITHIN THE
 BATHROOM GROUPS SHALL CONNECT TO THE WET-VENTED
 HORIZONTAL BRANCH DRAIN. ANY ADDITIONAL FIXTURES SHALL
 DISCHARGE DOWNSTREAM OF THE HORIZONTAL WET VENT.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL
 LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH
 A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE
 SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE
 FOUND WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR
 YOUR ANTICIPATED COOPERATION.
  