2014-07-05 12:28:34****PROVISO****
 ****ISSUED AT CONTRACTOR'S RISK****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
 FBC FLORIDA BUILDING CODE 2010
 FBC R FLORIDA BUILDING CODE 2010 RESIDENTIAL
  
 SEE FLOOR PLAN. FRONT DOOR IS SHOWN AS EMERGENCY MEANS
 OF ESCAPE. IT IS NOT CLEAR HOW THE ACCORDION SHUTTER
 CAN BE OPENED FROM THE INSIDE WITH AN OUTSWING DOOR.
  
 EMERGENCY MEANS OF ESCAPE FBC R310.4 REQUIRED AND IS TO
 COMPLY WITH THE FOLLOWING:
  
 THE MEANS OF ESCAPE SHALL BE WITHIN THE FIRST FLOOR OF
 THE DWELLING OR DWELLING UNIT AND SHALL NOT BE LOCATED
 WITHIN A GARAGE WITHOUT A SIDE-HINGED DOOR LEADING
 DIRECTLY TO THE EXTERIOR. OCCUPANTS IN ANY PART OF THE
 DWELLING OR DWELLING UNIT SHALL BE ABLE TO ACCESS THE
 MEANS OF ESCAPE WITHOUT PASSING THROUGH A LOCKABLE DOOR
 NOT UNDER THEIR CONTROL.
  
 IF THE EMERGENCY MEANS OF ESCAPE SHOWN ON THE PLAN DOES
 NOT COMPLY WITH THIS REQUIREMENT, A REVISION IS
 REQUIRED.
  
  
  