Plan Review Notes
Plan Review Notes For Permit 14060545
Permit Number 14060545
Review Stop B
Sequence Number 1
Notes
Date Text
2014-06-16 07:52:281ST REVIEW:
  
 THE APPLICATION INCLUDES REPLACING FLOORING. PLEASE
 PROVIDE SPECIFICATIONS IN THE FORM OF SUBMITTAL
 DOCUMENTS ON FLOORING AND SOUND INSULATION TO
 DEMONSTRATE COMPLIANCE WITH THE THE FBC SECTIONS BELOW,
  
 1207.1 SCOPE.
 THIS SECTION SHALL APPLY TO COMMON INTERIOR WALLS,
 PARTITIONS AND FLOOR/CEILING ASSEMBLIES BETWEEN
 ADJACENT DWELLING UNITS OR BETWEEN DWELLING UNITS AND
 ADJACENT PUBLIC AREAS SUCH AS HALLS, CORRIDORS, STAIRS
 OR SERVICE AREAS.
  
 1207.2 AIR-BORNE SOUND.
 WALLS, PARTITIONS AND FLOOR/CEILING ASSEMBLIES
 SEPARATING DWELLING UNITS FROM EACH OTHER OR FROM
 PUBLIC OR SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION
 CLASS (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED)
 FOR AIR-BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM
 E 90. PENETRATIONS OR OPENINGS IN CONSTRUCTION
 ASSEMBLIES FOR PIPING; ELECTRICAL DEVICES; RECESSED
 CABINETS; BATHTUBS; SOFFITS; OR HEATING, VENTILATING OR
 EXHAUST DUCTS SHALL BE SEALED, LINED, INSULATED OR
 OTHERWISE TREATED TO MAINTAIN THE REQUIRED RATINGS.
 THIS REQUIREMENT SHALL NOT APPLY TO DWELLING UNIT
 ENTRANCE DOORS; HOWEVER, SUCH DOORS SHALL BE TIGHT
 FITTING TO THE FRAME AND SILL.
  
 1207.3 STRUCTURE-BORNE SOUND.
 FLOOR/CEILING ASSEMBLIES BETWEEN DWELLING UNITS OR
 BETWEEN A DWELLING UNIT AND A PUBLIC OR SERVICE AREA
 WITHIN THE STRUCTURE SHALL HAVE AN IMPACT INSULATION
 CLASS (IIC) RATING OF NOT LESS THAN 50 (45 IF FIELD
 TESTED) WHEN TESTED IN ACCORDANCE WITH ASTM E 492.
  
 603.1 ALLOWABLE MATERIALS.
 COMBUSTIBLE MATERIALS SHALL BE PERMITTED IN BUILDINGS
 OF TYPE I OR II CONSTRUCTION IN THE FOLLOWING
 APPLICATIONS AND IN ACCORDANCE WITH SECTIONS 603.1.1
 THROUGH 603.1.3:
  
 1. FIRE-RETARDANT-TREATED WOOD SHALL BE PERMITTED IN:
  
 1.1. NONBEARING PARTITIONS WHERE THE REQUIRED
 FIRE-RESISTANCE RATING IS 2 HOURS OR LESS.
  
 1.2. NONBEARING EXTERIOR WALLS WHERE NO FIRE RATING IS
 REQUIRED.
  
 1.3. ROOF CONSTRUCTION, INCLUDING GIRDERS, TRUSSES,
 FRAMING AND DECKING.
  
 EXCEPTION: IN BUILDINGS OF TYPE IA CONSTRUCTION
 EXCEEDING TWO STORIES ABOVE GRADE PLANE,
 FIRE-RETARDANT-TREATED WOOD IS NOT PERMITTED IN ROOF
 CONSTRUCTION WHEN THE VERTICAL DISTANCE FROM THE UPPER
 FLOOR TO THE ROOF IS LESS THAN 20 FEET (6096 MM).
  
 2. THERMAL AND ACOUSTICAL INSULATION, OTHER THAN FOAM
 PLASTICS, HAVING A FLAME SPREAD INDEX OF NOT MORE THAN
 25.
  
 EXCEPTIONS:
  
 1. INSULATION PLACED BETWEEN TWO LAYERS OF
 NONCOMBUSTIBLE MATERIALS WITHOUT AN INTERVENING
 AIRSPACE SHALL BE ALLOWED TO HAVE A FLAME SPREAD INDEX
 OF NOT MORE THAN 100.
  
 2. INSULATION INSTALLED BETWEEN A FINISHED FLOOR AND
 SOLID DECKING WITHOUT INTERVENING AIRSPACE SHALL BE
 ALLOWED TO HAVE A FLAME SPREAD INDEX OF NOT MORE THAN
 200.
  