2014-06-20 08:59:35 | DATE: 6/20/2014 |
| PROJECT: PAPER SOURCE |
| PERMIT#: 14060542 |
| CODE: 2008 EDITION OF THE NEC |
| 2010 EDITION OF THE FBC |
| 2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1, |
| ADMINISTRATION, 2012 FBC SUPPLEMENTS. |
| |
| 1ST ELECTRICAL PLAN REVIEW |
| ACTION: DENIED |
| |
| 1) THE BRANCH CIRCUIT FEEDING BATTERY BACKED EMERGENCY |
| AND EXIT LIGHTS SHALL BE THE SAME BRANCH CIRCUIT AS |
| THAT SERVING THE NORMAL LIGHTING IN THE AREA AND |
| CONNECTED AHEAD OF ANY LOCAL SWITCHES NEC 701.11(G) |
| |
| 2) PROVIDE SAFETY LABELING FOR FLASH PROTECTION AND FOR |
| THE PANEL BOARDS AND MAIN DISCONNECTING MEANS. NEC |
| 110.16, 110.22 |
| |
| 3) PANEL LOCATIONS NEED TO COMPLY WITH: 110.26 (1) |
| DEPTH OF WORKING SPACE, (2) WIDTH OF WORKING SPACE & |
| (3) HEIGHT OF WORKING SPACE. FOR BOTH PANEL |
| LOCATIONS.THE DEDICATED ELECTRICAL SPACE MUST BE CLEAR |
| OF ANY PIPING, DUCTS, LEAK PROTECTION APPARATUS, OR |
| EQUIPMENT FOREIGN TO THE ELECTRICAL INSTALLATION. |
| PLUMBING, HEATING, VENTILATION, AND AIR-CONDITIONING |
| PIPING, DUCTS, AND EQUIPMENT MUST BE INSTALLED OUTSIDE |
| THE WIDTH AND DEPTH ZONE. |
| THE SINGLE LINE DIAGRAM SUBMITTED ILLUSTRATES ONE |
| TRANSFORMER INSTALLED ON THE FLOOR. THE FLOOR PLAN |
| SUBMITTED ILLUSTRATES TWO TRANSFORMERS HUNG FROM THE |
| CEILING STRUCTURE. |
| A) DETERMINE THE NUMBER OF TRANSFORMERS BEING USED. |
| INDICATE THEIR NAMEPLATE ELECTRICAL WORKING STATISTICS. |
| B) IF INSTALLED IN CEILING SPACE, INDICATE THE WEIGHT, |
| THE DESIGN OF THE SUPPORTING STRUCTURE AND THE DESIGN |
| OF THE HARDWARE PROPOSED TO SUPPORT THE TRANSFORMER(S) |
| SAFELY. |
| |
| NOTE: |
| SEPARATE PERMITS APPLICATIONS, WITH PLANS, INCLUDING |
| ALL MANUFACTURERS EQUUIPMENT SPCIFICATIONS ARE REQUIRED |
| FOR FIRE ALARM, SECURITY, ACCESS CONTROL, CCTV, |
| NETWORK, DATA/COM, AND AUDIO/VIDEO, |
| |
| DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421, |
| 561-805-6717 OR AT [email protected] |