Plan Review Notes For Permit 14060537 |
Permit Number |
14060537 |
|
Review Stop |
M |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2014-07-11 11:02:42 | 2010 FBC | | | | DENIED BY MECHANICAL | | | | 1) THE PRINTED NAME, SIGNATURE AND LICENSE NUMBER OF | | THE PERSON RESPONSIBLE FOR THE DESIGN IS REQUIRED ON | | THE MECHANICAL PLANS. FS 471.003 & CITY AMENDMENTS | | 107.2.1 | | | | 2) CLEARLY IDENTIFY THE SIZE OF SIZE OF THE SUPPLY | | TRUNK LINE ON THE PLANS. CITY AMENDMENTS 107.2.1 | | | | 3) THE MODEL NUMBERS OF THE AIR HANDLER AND CONDENSING | | UNITS ARE NOT CONSISTANT. THE SAME MODEL NUMBERS ARE | | REQUIRED TO BE ON THE SIZING CALCS., THE AHRI | | CERTIFICATION AND THE PLANS. FBCR M1401.3 & CITY | | AMENDMENTS 107.2.1 | | | | 4) PROVIDE AN EQUIPMENT ANCHORING DETAIL FOR THE | | CONDENSING UNIT TO SHOW COMPLIANCE WITH FBCR M1307.2.1 | | FOR WIND RESISTANCE. | | | | 5) ONE OF THE RETURN AIR GRILLS APPEARS TO BE LOCATED | | IN THE MASTER BATHROOM. FBCR M1602.2 DOES NOT ALLOW | | RETURN AIR TO BE TAKEN FROM A BATHROOM. | | | | ROBERT MCDOUGAL | | BLDG. PLAN REVIEW | | (561)805-6714 | | [email protected] |
|