Plan Review Notes
Plan Review Notes For Permit 14060537
Permit Number 14060537
Review Stop M
Sequence Number 1
Notes
Date Text
2014-07-11 11:02:422010 FBC
  
 DENIED BY MECHANICAL
  
 1) THE PRINTED NAME, SIGNATURE AND LICENSE NUMBER OF
 THE PERSON RESPONSIBLE FOR THE DESIGN IS REQUIRED ON
 THE MECHANICAL PLANS. FS 471.003 & CITY AMENDMENTS
 107.2.1
  
 2) CLEARLY IDENTIFY THE SIZE OF SIZE OF THE SUPPLY
 TRUNK LINE ON THE PLANS. CITY AMENDMENTS 107.2.1
  
 3) THE MODEL NUMBERS OF THE AIR HANDLER AND CONDENSING
 UNITS ARE NOT CONSISTANT. THE SAME MODEL NUMBERS ARE
 REQUIRED TO BE ON THE SIZING CALCS., THE AHRI
 CERTIFICATION AND THE PLANS. FBCR M1401.3 & CITY
 AMENDMENTS 107.2.1
  
 4) PROVIDE AN EQUIPMENT ANCHORING DETAIL FOR THE
 CONDENSING UNIT TO SHOW COMPLIANCE WITH FBCR M1307.2.1
 FOR WIND RESISTANCE.
  
 5) ONE OF THE RETURN AIR GRILLS APPEARS TO BE LOCATED
 IN THE MASTER BATHROOM. FBCR M1602.2 DOES NOT ALLOW
 RETURN AIR TO BE TAKEN FROM A BATHROOM.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]