Plan Review Notes For Permit 14060537 |
Permit Number |
14060537 |
|
Review Stop |
E |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2014-07-11 15:27:48 | 2010 FBC / 2008 NEC | | | | DENIED BY ELECTRICAL | | | | PLAN SHEET E-1 | | | | 1) PROVIDE A SITE PLAN THAT SHOWS THE LOCATION OF THE | | EXISTING METER AND 200 AMP PANEL. CITY AMENDMENTS | | 107.2.1 | | | | 2) PROVIDE A PANEL SCHEDULE FOR THE EXISTING 200 AMP | | PANEL THAT SHOWS THE OVERCURRENT PROTECTION / | | DISCONNECT FOR THE NEW 100 AMP PANEL. CITY AMENDMENTS | | 107.3.5.3, NEC 230.2.5 & 240 | | | | 3) THE SITE PLAN ON SHEET SP-1 INDICATES A RELOCATED | | A/C UNIT AND NEW POOL EQUIPMENT. PLEASE CLARIFY IF THIS | | WORK IS INCLUDED IN THIS PERMIT OR WILL BE DONE UNDER A | | SEPARATE PERMIT. CITY AMENDMENTS 107.2.1 | | | | 4) THERE APPEARS TO BE A TYPO WITH REGARDS TO THE BELOW | | COUNTER OUTLETS THAT ARE SHOWN ON THE PLANS IN THE | | CEILING BESIDE THE SMOKE ALARMS. PLEASE CORRECT. CITY | | AMENDMENTS 107.2.1 | | | | 5) THE RECEPTACLE OUTLETS THAT ARE LOCATED IN THE | | WORKSHOP ARE REQUIRED TO BE GFCI PER NEC 210.8(A)(2). | | | | 6) A WALL SWITCH-CONTROLLED LIGHTING OUTLET IS REQUIRED | | ON THE EXTERIOR SIDE OF THE WORKSHOP DOORS IN | | ACCORDANCE WITH NEC 210.70(A)(2)(B). | | | | 7) A RECEPTACLE OUTLET IS REQUIRED IN THE HALL TO THE | | LEFT OF THE FRONT ENTRY DOORS IN ACCORDANCE WITH NEC | | 210.52(A). | | | | 8) IN ORDER TO SPEED REVIEW TIME, PLEASE SUBMIT A | | RESPONSE LETTER INDICATING HOW EACH OF THE REVIEW | | COMMENTS HAS BEEN ADDRESSED. | | | | ROBERT MCDOUGAL | | BLDG. PLAN REVIEW | | (561)805-6714 | | [email protected] |
|