2014-06-16 17:17:57THE FOLLOWING ITEMS SHALL BE CORRECTED FOR A SUCCESSFUL
 ELECTRICAL REVIEW.
 1. ONLY HALF OF THE CORRIDOR SHOWS PROPER ILLUMINATION.
 ADD THE REQUIRED LIGHTING TO THE CORRIDOR AREA TO MEET
 CODE AND EGRESS LIGHTING REQUIREMENTS.
 2. THE SHALL BE AN EMERGENCY LIGHT IN THE REAR HALL
 AREA AND THE VESTIBULE TO ILLUMINATE THE PATH OF
 EGRESS.
 3. THE PLANS INDICATE CHANGES AND/OR MODIFICATIONS TO
 THE EXISTING FIRE ALARM SYSTEM. WHEN CHANGES OR
 MODIFICATIONS ARE PERFORMED TO THE FIRE ALARM SYSTEM A
 RE-ACCEPTANCE TEST WILL BE REQUIRED.