2014-06-12 15:54:01 | BUILDING PLAN REVIEW |
| PERMIT: 14060450 |
| ADD: 503 AVENIDA HERMOSA BLDG (MAIN HOUSE). |
| CONT: PETERSONDEAN ROOFING |
| TEL: (561)881-0660 |
| |
| 2010 FLORIDA BUILDING CODE W |
| * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION |
| 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013. |
| |
| 2010 EXISTING BUILDING CODE LEVEL II 701.3 |
| COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, |
| SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS |
| OF THE FLORIDA BUILDING CODE, BUILDING. |
| |
| 1ST REVIEW |
| DATE: THURS. JUNE 12/ 2014 |
| ACTION: DENIED |
| |
| 1) THE ROOF ING FORMS LIST THIS AS A "B" EXPOSURE |
| WHEREAS THE CITY REVIEWS THIS AS A SURFACE ROUGHNESS C. |
| OPEN TERRAIN WITH SCATTERED OBSTRUCTIONS HAVING HEIGHTS |
| GENERALLY LESS THAN 30 FEET (9144 MM). THIS CATEGORY |
| INCLUDES FLAT OPEN COUNTRY AND GRASSLANDS.THIS SURFACE |
| ROUGHNESS SHALL ALSO APPLY TO ANY BUILDING LOCATED |
| WITHIN SURFACE ROUGHNESS B-TYPE TERRAIN WHERE THE |
| BUILDING IS WITHIN 100 FEET HORIZONTALLY IN ANY |
| DIRECTION OF OPEN AREAS OF SURFACE ROUGHNESS C OR |
| D-TYPE TERRAIN THAT EXTENDS MORE THAN 600 FEET (182.9 |
| M) AND WIDTH GREATER THAN 150 FEET IN THE UPWIND |
| DIRECTION. 2010 FBC-B 1609.4.2 THE C SURFACE ROUGHNESS |
| TERRAIN IS TO THE NOTH AND NORTHEAST. |
| |
| THE SUBMITTED PRODUCT APPROVAL NOA 13-0529 SHEET 24 OF |
| 27 HAS A MAXIMUM DESIGN PRESSURE OF -52.5 AND |
| LIMITATION # 7 THAT ALLOWS ENHANCED FASTENING, RAS 117 |
| BY A FL ARCHITECT OR ENGINEER IN ROOF ZONES 2 & 3 . |
| |
| 2) NOA 12-0222.02 BARCELONA 900 CONCRETE ROOF TILE THE |
| CONTRACTOR DID NOT IDENTIFY WHAT TYPE OF FASTENER IS |
| GOING TO BE INSTALLED ON THIS ROOFING SYSTEM FOR EITHER |
| NAIL ON OR ADHESIVE ROOFING SYSTEMS. 107.2.1.2 FOR ROOF |
| ASSEMBLIES REQUIRED BY THE CODE, THE CONSTRUCTION |
| DOCUMENTS SHALL |
| ILLUSTRATE, DESCRIBE AND DELINEATE THE TYPE OF ROOFING |
| SYSTEM, MATERIALS, FASTENING REQUIREMENTS, FLASHING |
| REQUIREMENTS AND WIND RESISTANCE RATING THAT ARE |
| REQUIRED TO BE INSTALLED. PRODUCT EVALUATION AND |
| INSTALLATION SHALL INDICATE COMPLIANCE WITH THE WIND. |
| CRITERIA REQUIRED FOR THE SPECIFIC SITE |
| |