2014-06-17 14:13:13 | PLUMBING PLAN REVIEW |
| PERMIT: 14060369 |
| ADD: 5015 N FLAGLER DR |
| CONT: RICHARD ATTENBURG |
| TEL: (561)445-8444 |
| |
| 2010 FLORIDA BUILDING CODE W |
| * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION |
| 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013. |
| |
| 2010 EXISTING BUILDING CODE LEVEL II 701.3 |
| COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, |
| SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS |
| OF THE FLORIDA BUILDING CODE, BUILDING. |
| |
| 1ST REVIEW |
| DATE: TUESDAY JUNE 17/2014 |
| ACTION: DENIED |
| |
| 1) A CERTIFIED GENERAL CONTRACTOR HAS SUBMITTED FOR A |
| GAS PERMIT PLEASE SEE FLORIDA STATUTE 489.113 (3)?A |
| CONTRACTOR SHALL SUBCONTRACT ALL ELECTRICAL, |
| MECHANICAL, PLUMBING, ROOFING, SHEET METAL, SWIMMING |
| POOL, AND AIR-CONDITIONING WORK, UNLESS SUCH CONTRACTOR |
| HOLDS A STATE CERTIFICATE OR REGISTRATION IN THE |
| RESPECTIVE TRADE CATEGORY. |
| |
| 2) THE PLANS ARE DRAWN WITH 4 METERS BUT INDICATE THERE |
| TO BE 2 UNITS. THE P B C PROPERTY APPRAISERS OFFICE |
| LIST THIS PREOPERTY WITH 4 UNITS. |
| 107.2.1.3 ADDITIONAL INFORMATION IS REQUIRED, IT |
| APPEARS THERE MAY BE A DISCREPANCY IN THE PLANS. |
| |
| 3) THE 2 GAS RISERS GOING TO THE 2ND FLOOR IN BOTH |
| ISOMETRICS HAVE ON 1 GAS RISER 18 @ 1/2 AND THE SAME |
| RISER 18@ 3/4 THE OTHER RISER THERE IS NO |
| DIMENSION. PLEASE FOR ALL 4 SYSTEMS PROVIDE THE TOTAL |
| DEVELOPED LENGTH AND A LENGTH FOR EACH SECTION OF PIPE |
| WITH DIAMETER GIVEN. |
| |
| 4) THE OTHER ISSUE IS THE PLANS INDICATE THE PIPE IS TO |
| BE POLYETHELYNE, OR STEEL OR DOUBLE LAYER HALF LAPPED |
| 10-MILL POLYETHELYE TAPE. |
| 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS. DRAWINGS |
| AND SPECIFICATIONS SHALL CONTAIN INFORMATION, IN THE |
| FORM OF NOTES OR OTHERWISE, AS TO THE QUALITY OF |
| MATERIALS, WHERE QUALITY IS ESSENTIAL TO CONFORMITY |
| WITH THE TECHNICAL CODES. SUCH INFORMATION SHALL BE |
| SPECIFIC, AND THE TECHNICAL CODES SHALL NOT BE CITED AS |
| A WHOLE OR IN PART, NOR SHALL THE TERM "LEGAL" OR ITS |
| EQUIVALENT BE USED AS A SUBSTITUTE FOR SPECIFIC |
| INFORMATION. |
| |
| |
| GAS PERMIT APPLICATION REQUIREMENTS |
| |
| EFFECTIVE IMMEDIATELY THE FOLLOWING INFORMATION SHALL |
| BE SHOWN ON ALL GAS DRAWINGS SUBMITTED FOR PERMITTING |
| IN THE CITY OF WEST PALM BEACH: |
| |
| 1. SUBMIT AN ISOMETRIC DRAWING THAT CLEARLY SHOWS ALL |
| CUT SECTIONS OF PIPE AND CORRESPONDING LENGTHS PER |
| FBC-2010 FUEL GAS. |
| |
| 2. SHOW TYPE OF PIPING MATERIAL BEING INSTALLED, ALL |
| PIPE SIZES, AND THE EDH NUMBER OF CORRUGATED STAINLESS |
| STEEL TUBING FOR EACH PIPE SIZE IF BEING USED. |
| |
| 3. TYPE OF GAS, (LP OR NATURAL). |
| |
| 4. BTU LOAD OF EACH APPLIANCE AND THE TOTAL BTU LOAD ON |
| THE SYSTEM. REFER TO THE FBC-2010 FUEL GAS SECS. 401.8 |
| THRU 402.6.1 AND TABLES 402.4(1) THRU 402.4(35) |
| |
| 5. SHOW THE DISTANCE FROM THE POINT OF DELIVERY, |
| (METER), TO THE MOST REMOTE OUTLET IN THE BUILDING |
| AND/OR SYSTEM PER THE FBC-2010 FUEL GAS APPENDIX A ? |
| USE OF CAPACITY SECTION A.3.1(4) |
| |
| 6. SUBMIT CALCULATIONS FOR COMBUSTION AIR PER THE |
| FBC-2010 FUEL GAS CODE SEC. 304 |
| |
| 7. INDICATE THE DELIVERY PRESSURE (PSI) PER FBC-2010 |
| FUEL GAS SEC. 402.2. IF NATURAL GAS SPECIFY .5 PSI OR 2 |
| PSI. |
| |
| 8. SUBMIT A DETAIL SHOWING THE TYPE, LOCATION, SIZE AND |
| TERMINATION OF THE GAS VENTS PER FBC-2010 FUEL GAS CODE |
| SEC. 502 THRU 505. |
| |
| 9. SUBMIT MANUFACTURE SHEETS FOR ALL GAS EQUIPMENT TO |
| VERIFY COMPLIANCE WITH STANDARDS NFPA 54, NFPA 58, AND |
| FBC-2010 FUEL GAS SEC. 402.2 |
| |
| 5) 2010 EXISTING BUILDING CODE LEVEL II 701.3 |
| COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, |
| SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS |
| OF THE FLORIDA BUILDING CODE, BUILDING. |
| R315.1 CARBON MONOXIDE PROTECTION. |
| EVERY SEPARATE BUILDING OR AN ADDITION TO AN EXISTING |
| BUILDING FOR WHICH A PERMIT FOR NEW CONSTRUCTION IS |
| ISSUED AND HAVING A FOSSIL-FUEL-BURNING HEATER OR |
| APPLIANCE, A FIREPLACE, AN ATTACHED GARAGE, OR OTHER |
| FEATURE, FIXTURE, OR ELEMENT THAT EMITS CARBON MONOXIDE |
| AS A BYPRODUCT OF COMBUSTION SHALL HAVE AN OPERATIONAL |
| CARBON MONOXIDE ALARM INSTALLED WITHIN 10 FEET OF EACH |
| ROOM USED FOR SLEEPING PURPOSES. |
| EXCEPTION: THIS SECTION SHALL NOT APPLY TO EXISTING |
| BUILDINGS THAT ARE UNDERGOING ALTERATIONS OR REPAIR |
| UNLESS THE ALTERATION IS AN ADDITION AS DEFINED IN |
| SECTION R315.1.3. |
| R315.1.1 CARBON MONOXIDE ALARM. |
| THE REQUIREMENTS OF SECTION R315.1 SHALL BE SATISFIED |
| BY PROVIDING FOR ONE OF THE FOLLOWING ALARM |
| INSTALLATIONS: |
| (1) A HARD-WIRED CARBON MONOXIDE ALARM. |
| (2) A BATTERY-POWERED CARBON MONOXIDE ALARM. |
| (3) A HARD-WIRED COMBINATION CARBON MONOXIDE AND SMOKE |
| ALARM. |
| (4) A BATTERY-POWERED COMBINATION CARBON MONOXIDE AND |
| SMOKE ALARM. |
| |