2014-06-17 14:13:13PLUMBING PLAN REVIEW
 PERMIT: 14060369
 ADD: 5015 N FLAGLER DR
 CONT: RICHARD ATTENBURG
 TEL: (561)445-8444
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: TUESDAY JUNE 17/2014
 ACTION: DENIED
  
 1) A CERTIFIED GENERAL CONTRACTOR HAS SUBMITTED FOR A
 GAS PERMIT PLEASE SEE FLORIDA STATUTE 489.113 (3)?A
 CONTRACTOR SHALL SUBCONTRACT ALL ELECTRICAL,
 MECHANICAL, PLUMBING, ROOFING, SHEET METAL, SWIMMING
 POOL, AND AIR-CONDITIONING WORK, UNLESS SUCH CONTRACTOR
 HOLDS A STATE CERTIFICATE OR REGISTRATION IN THE
 RESPECTIVE TRADE CATEGORY.
  
 2) THE PLANS ARE DRAWN WITH 4 METERS BUT INDICATE THERE
 TO BE 2 UNITS. THE P B C PROPERTY APPRAISERS OFFICE
 LIST THIS PREOPERTY WITH 4 UNITS.
 107.2.1.3 ADDITIONAL INFORMATION IS REQUIRED, IT
 APPEARS THERE MAY BE A DISCREPANCY IN THE PLANS.
  
 3) THE 2 GAS RISERS GOING TO THE 2ND FLOOR IN BOTH
 ISOMETRICS HAVE ON 1 GAS RISER 18 @ 1/2 AND THE SAME
 RISER 18@ 3/4 THE OTHER RISER THERE IS NO
 DIMENSION. PLEASE FOR ALL 4 SYSTEMS PROVIDE THE TOTAL
 DEVELOPED LENGTH AND A LENGTH FOR EACH SECTION OF PIPE
 WITH DIAMETER GIVEN.
  
 4) THE OTHER ISSUE IS THE PLANS INDICATE THE PIPE IS TO
 BE POLYETHELYNE, OR STEEL OR DOUBLE LAYER HALF LAPPED
 10-MILL POLYETHELYE TAPE.
 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS. DRAWINGS
 AND SPECIFICATIONS SHALL CONTAIN INFORMATION, IN THE
 FORM OF NOTES OR OTHERWISE, AS TO THE QUALITY OF
 MATERIALS, WHERE QUALITY IS ESSENTIAL TO CONFORMITY
 WITH THE TECHNICAL CODES. SUCH INFORMATION SHALL BE
 SPECIFIC, AND THE TECHNICAL CODES SHALL NOT BE CITED AS
 A WHOLE OR IN PART, NOR SHALL THE TERM "LEGAL" OR ITS
 EQUIVALENT BE USED AS A SUBSTITUTE FOR SPECIFIC
 INFORMATION.
  
  
 GAS PERMIT APPLICATION REQUIREMENTS
  
 EFFECTIVE IMMEDIATELY THE FOLLOWING INFORMATION SHALL
 BE SHOWN ON ALL GAS DRAWINGS SUBMITTED FOR PERMITTING
 IN THE CITY OF WEST PALM BEACH:
  
 1. SUBMIT AN ISOMETRIC DRAWING THAT CLEARLY SHOWS ALL
 CUT SECTIONS OF PIPE AND CORRESPONDING LENGTHS PER
 FBC-2010 FUEL GAS.
  
 2. SHOW TYPE OF PIPING MATERIAL BEING INSTALLED, ALL
 PIPE SIZES, AND THE EDH NUMBER OF CORRUGATED STAINLESS
 STEEL TUBING FOR EACH PIPE SIZE IF BEING USED.
  
 3. TYPE OF GAS, (LP OR NATURAL).
  
 4. BTU LOAD OF EACH APPLIANCE AND THE TOTAL BTU LOAD ON
 THE SYSTEM. REFER TO THE FBC-2010 FUEL GAS SECS. 401.8
 THRU 402.6.1 AND TABLES 402.4(1) THRU 402.4(35)
  
 5. SHOW THE DISTANCE FROM THE POINT OF DELIVERY,
 (METER), TO THE MOST REMOTE OUTLET IN THE BUILDING
 AND/OR SYSTEM PER THE FBC-2010 FUEL GAS APPENDIX A ?
 USE OF CAPACITY SECTION A.3.1(4)
  
 6. SUBMIT CALCULATIONS FOR COMBUSTION AIR PER THE
 FBC-2010 FUEL GAS CODE SEC. 304
  
 7. INDICATE THE DELIVERY PRESSURE (PSI) PER FBC-2010
 FUEL GAS SEC. 402.2. IF NATURAL GAS SPECIFY .5 PSI OR 2
 PSI.
  
 8. SUBMIT A DETAIL SHOWING THE TYPE, LOCATION, SIZE AND
 TERMINATION OF THE GAS VENTS PER FBC-2010 FUEL GAS CODE
 SEC. 502 THRU 505.
  
 9. SUBMIT MANUFACTURE SHEETS FOR ALL GAS EQUIPMENT TO
 VERIFY COMPLIANCE WITH STANDARDS NFPA 54, NFPA 58, AND
 FBC-2010 FUEL GAS SEC. 402.2
  
 5) 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
 R315.1 CARBON MONOXIDE PROTECTION.
 EVERY SEPARATE BUILDING OR AN ADDITION TO AN EXISTING
 BUILDING FOR WHICH A PERMIT FOR NEW CONSTRUCTION IS
 ISSUED AND HAVING A FOSSIL-FUEL-BURNING HEATER OR
 APPLIANCE, A FIREPLACE, AN ATTACHED GARAGE, OR OTHER
 FEATURE, FIXTURE, OR ELEMENT THAT EMITS CARBON MONOXIDE
 AS A BYPRODUCT OF COMBUSTION SHALL HAVE AN OPERATIONAL
 CARBON MONOXIDE ALARM INSTALLED WITHIN 10 FEET OF EACH
 ROOM USED FOR SLEEPING PURPOSES.
 EXCEPTION: THIS SECTION SHALL NOT APPLY TO EXISTING
 BUILDINGS THAT ARE UNDERGOING ALTERATIONS OR REPAIR
 UNLESS THE ALTERATION IS AN ADDITION AS DEFINED IN
 SECTION R315.1.3.
 R315.1.1 CARBON MONOXIDE ALARM.
 THE REQUIREMENTS OF SECTION R315.1 SHALL BE SATISFIED
 BY PROVIDING FOR ONE OF THE FOLLOWING ALARM
 INSTALLATIONS:
 (1) A HARD-WIRED CARBON MONOXIDE ALARM.
 (2) A BATTERY-POWERED CARBON MONOXIDE ALARM.
 (3) A HARD-WIRED COMBINATION CARBON MONOXIDE AND SMOKE
 ALARM.
 (4) A BATTERY-POWERED COMBINATION CARBON MONOXIDE AND
 SMOKE ALARM.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER