2014-06-12 18:22:52DUE TO THE DEFICIENT DRAWING, I CONTACTED THE EC TO
 DISCUSS THE SCOPE OF WORK. ACCORDING TO THE EC:
 1. THE SERVICE WIRES AND THE FEEDER TO THE FIRST
 EXTERIOR PANEL WERE STOLEN.
 2. IN THE PROCESS OF TAKING THE CONDUCTORS, THE METER
 JAWS AND THE MAIN BREAKER WERE DAMAGED.
  
 TO REPAIR THE SERVICE, THE EC WILL:
 1. REPLACE THE SERVICE CONDUCTORS W/3 2/0 CU
 2. REPLACE THE METER JAWS.
 3. REPLACE THE FEEDERS TO THE PANEL W/ 3 2/0 CU
 4. REPLACE THE MAIN BREAKER
 5. IN THE PROCESS THE GROUNDS WILL BE REPLACED AS WELL.
  
 THESE PLANS WERE REVIEWED BY MIKE ALBARRAN, ELECTRICAL
 PLANS EXAMINER
 YOU ARE WELCOME TO REVIEW STATUS OR COMMENTS AT THE
 FOLLOWING LINK:
 HTTP://ONESTOPSHOP.WPBGOV.COM/EGOVPLUS/PERMIT/PERM_STAT
 US.ASPX
 ENTER YOUR PERMIT NUMBER (SEE SUBJECT LINE OF THIS
 EMAIL FOR YOUR PERMIT #), CLICK ON THE PERMIT NUMBER,
 AND THEN GO TO "PLAN REVIEWS" TO SEE YOUR COMMENTS
 (TAB ABOVE THE SECOND PERMIT INFORMATION).
 AFTER ISSUANCE, PLEASE CHECK YOUR PLAN CAREFULLY FOR
 COMPLIANCE WITH ANY REDLINES, NOTES, PROVISOS, OR OTHER
 PERMIT CONDITIONS.
 FOR FURTHER ASSISTANCE, PLEASE FEEL FREE TO CONTACT ME.