Plan Review Notes For Permit 14060299 |
Permit Number |
14060299 |
|
Review Stop |
B |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2014-06-15 15:04:11 | ****CORRECTIONS**** | | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | 561-805-6724 | | [email protected] | | | | FBC FLORIDA BUILDING CODE 2010 | | | | 1. FBC 1207.2, FLOOR/CEILING ASSEMBLIES SEPARATING | | DWELLING UNITS FROM EACH OTHER OR FROM PUBLIC OR | | SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION CLASS | | (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED) FOR AIR | | BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM E 90. | | THE TEST PROVIDED INCLUDED A DROPPED GYPSUM CEILING, | | WHICH IS NOT THE CONDITION FOR THIS JOB. PROVIDE A COPY | | OF THE TEST WHICH DOES NOT INCLUDE THE SUSPENDED | | CEILING. | | | | 2. FBC 1207.3, FLOOR/CEILING ASSEMBLIES BETWEEN | | DWELLING UNITS OR BETWEEN A DWELLING UNIT AND A PUBLIC | | OR SERVICE AREA WITHIN THE STRUCTURE SHALL HAVE AN | | IMPACT INSULATION CLASS (IIC) RATING OF NOT LESS THAN | | 50 (45 IF FIELD TESTED) WHEN TESTED IN ACCORDANCE WITH | | ASTM E 492. A SUSPENDED CEILING WAS USED AS A PART OF | | THE TEST, WHICH IS NOT THE CONDITION FOR THIS JOB. | | PROVIDE A COPY OF THE TEST WITHOUT THE SUSPENDED | | CEILING. |
|