Plan Review Notes
Plan Review Notes For Permit 14060299
Permit Number 14060299
Review Stop B
Sequence Number 1
Notes
Date Text
2014-06-15 15:04:11****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724
 [email protected]
  
 FBC FLORIDA BUILDING CODE 2010
  
 1. FBC 1207.2, FLOOR/CEILING ASSEMBLIES SEPARATING
 DWELLING UNITS FROM EACH OTHER OR FROM PUBLIC OR
 SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION CLASS
 (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED) FOR AIR
 BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM E 90.
 THE TEST PROVIDED INCLUDED A DROPPED GYPSUM CEILING,
 WHICH IS NOT THE CONDITION FOR THIS JOB. PROVIDE A COPY
 OF THE TEST WHICH DOES NOT INCLUDE THE SUSPENDED
 CEILING.
  
 2. FBC 1207.3, FLOOR/CEILING ASSEMBLIES BETWEEN
 DWELLING UNITS OR BETWEEN A DWELLING UNIT AND A PUBLIC
 OR SERVICE AREA WITHIN THE STRUCTURE SHALL HAVE AN
 IMPACT INSULATION CLASS (IIC) RATING OF NOT LESS THAN
 50 (45 IF FIELD TESTED) WHEN TESTED IN ACCORDANCE WITH
 ASTM E 492. A SUSPENDED CEILING WAS USED AS A PART OF
 THE TEST, WHICH IS NOT THE CONDITION FOR THIS JOB.
 PROVIDE A COPY OF THE TEST WITHOUT THE SUSPENDED
 CEILING.