Plan Review Notes For Permit 14060286 |
Permit Number |
14060286 |
|
Review Stop |
M |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2014-08-18 15:20:08 | 8/18/14. | | NOTES: | | 1.PROVIDE OUTSIDE AIR BASED ON THE TOTAL OCCUPANT LOAD | | AND AS REQUIRED BY FMC, TABLE 403.3 OR ASHRAE | | 62.1-2004.USE EQUATION 4-1 AS REQUIRED BY SEC.403.1.1. | | 2.SHOW DISCHARGE LOCATION OF THE CONDENSATE DRAIN AS | | REQUIRED BY SEC.307 OF THE FMC AND SEC.1503.7 OF THE | | FBC. | | 3.PROVIDE ON PLANS COMPLETE DETAIL OF THE INSTALLATION | | OF THE AIR HANDLING UNIT AND THE CONDENSING UNIT. | | 4.SHOW ON PLANS HOW THE CONDENSING UNIT STAND IS | | ATTACHED TO ROOF STRUCTURE AND THE UNIT TO THE STAND. | | 5.SHOW ON PLANS AUTOMATIC SHUTOFF DAMPER AS REQUIRED BY | | FEC SEC.503.2.4.4 AND 503.2.5.4. | | 6.PROVIDE ON PLANS COMPLETE A/C SCHEDULE WITH ALL THE | | INFORMATION. | | 7.SELECT HVAC SYSTEMS AND EQUIPMENT IN ACCORDANCE WITH | | FEC SEC.503.2.1 AND 503.2.2. | | 8.PROVIDE FLOAT SWITCH AS REQUIRED BY FMC SEC. 307.2.3. | | 9.SHOW ON PLANS THE LOCATION OF EF-2. | | 10.SHOW ON PLANS COMPLIANCE TO INTAKE OPENINGS AS | | REQUIRED BY FMC,SEC.401.4 AND THE EXHAUST OUTLETS AS | | PER FMC,SEC.501.2.1. | | | | REVIEWED BY JOHN ARITON. PLEASE CALL HAROLD MOSER AT | | 561-805-6732 IF YOU NEED ASSISTANCE. | | | | |
|