2014-07-01 07:22:52 | BUILDING PLAN REVIEW |
| PERMIT: 14060286 |
| ADD: 1220 ORTEGA RD |
| CONT: WILBUR HOBGOOD CONST. |
| TEL: (561)691-9686 |
| 2010 FLORIDA BUILDING CODE W |
| * WEST PALM BEACH ADMINISTRATIVE AMENDMENTS |
| |
| 2010 EXISTING BUILDING CODE LEVEL II 701.3 |
| COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, |
| SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS |
| OF THE FLORIDA BUILDING CODE, BUILDING. |
| |
| 1ST REVIEW |
| DATE: JULY 01/ 2014 |
| ACTION: DENIED |
| |
| 1) INFORMATIONAL: WHEN RESUBMITTING PLANS PLEASE |
| INDICATE THE REVISION & REMOVE & REPLACE ANY PAGES AS |
| NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| COOPERATION. |
| |
| 2) SHEET A-5: |
| 2A) 2010 FBC-B 1008.1.6 OR 1009.5 STAIRWAY LANDINGS. |
| THE RIGHT SIDE OF THE SHEET DOORWAY FROM STORAGE THE |
| DOOR SWINGS OUT OVER THE STAIRS FROM SHEET A2 THE |
| LANDING APPEARS TO HAVE BEEN LENGHTENED BUT NOT TO CODE |
| COMPLIANCE. THE OTHER ISSUE WITH THIS STAIR IS THAT IT |
| MAY NOT REGUIRE A GAURDRAIL THESE STAIRS DO REQUIRE A |
| HANDRAIL PER SECTION 2010 FBC-B 1009.12. |
| |
| 2B) THE NEW ACCESS RAMP SHOWS A FOOTER DETAIL SHEET A7 |
| AS (F4) THIS DETAIL SHOWS EDGE PROTECTION BUT NOT A |
| HANDRAIL NOR GAURD RAIL AS REQUIRED BY FBC-B 1010.8 AND |
| 1010.10. NOTE FLOOR ELEVATIONS IN REGARDS TO GRADE ARE |
| NOT GIVEN. THE EXISING STAIR HAS 6 RISERS @ 7 IN= 42 |
| INCHES IN HEIGHT. NOTE SHEET A6 SHOWS THE NEW |
| ACCESSIBLE RAMP AT A LOWER LEVEL THAN THE EXISTING |
| STRUCTURE WHERE AS SHEET A7 FOOTER DETAIL F2 SHOWS THE |
| FLOORS AT THE SAME LEVEL. DISCREPANCY IN PLANS. |
| |
| 2C) THE NEW ACCESSIBLE RESTROOM DOES NOT MEET THE |
| ACCEESSIBLE RESTROOMDIMENSIONAL REQUIREMENTS. THERE IS |
| A DISCREPANCY IN THE PLANS SHEET A5 SHOWS A DIMENTION |
| OF 6'-10" SHEET DETAIL ON SHEET A9 SHOWS THIS SAME WALL |
| 5'-9". THE MINIMUM DIMENSION FOR THE FIXTURE SET WALL |
| IS 7'-01/2". 2010 FBC- ACCESSIBILITY CODE 604.2 & |
| 604.3.2 & FIGURE 604.8.1.6. |
| |
| |
| 3) SHEET A7 PLEASE REVIEW BEAM TAG C, IS THIS BEAM 84 |
| INCHES DEEP OR IS THIS A TYPO? 107.2.1.3. ADITIONAL |
| INFORMATION IS REQUIRED. |
| |
| 4) SHEET A-8 ADDITIONAL INFORMATION REQUIRED A8 VERSES |
| A6, THE PLANS DO NOT PROVIDE EITHER AN INTERMEDIATE TIE |
| BEAM OR LINTEL. |
| 5 DOORS ARE DRAWN TO A 7'-0" ELEVATION |
| 1 DOOR IS INDICATED TO BE AT ELEVATION 10'-0" TOP OF |
| BEAM |
| ROOF ELEVATION IS INDICATED AT 12'-0" TOP OF BEAM OR |
| 12'-9" APPPROX. |
| SECTION THROUGH ROOF A-8 MIN ABOVE 14'-0" ABOVE |
| LANDING, THERE IS A DISCREPANCY IN THE DETAIL AND |
| ELEVATION SHEET A6. |
| |
| 5) 2010 FBC-B 1803.5.2 QUESTIONABLE SOIL. WHERE THE |
| CLASSIFICATION, STRENGTH OR COMPRESSIBILITY OF THE SOIL |
| IS IN DOUBT OR WHERE A LOAD-BEARING VALUE SUPERIOR TO |
| THAT SPECIFIED IN THIS CODE IS CLAIMED, THE BUILDING |
| OFFICIAL SHALL BE PERMITTED TO REQUIRE THAT A |
| GEOTECHNICAL INVESTIGATION BE CONDUCTED. |
| |
| 6A) 2010 FBC 107.3.4.1 PRODUCT APPROVALS. THOSE |
| PRODUCTS WHICH ARE REGULATED BY THE DCA RULE 9N-03 |
| SHALL BE REVIEWED AND APPROVED IN WRITING BY THE |
| DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR |
| JURISDICTIONAL APPROVAL. |
| FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR |
| SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS, |
| SHOP DRAWINGS ETC.. |
| |
| 6B) 2010 FBC-B 1609.1.2 PROTECTION OF OPENINGS, |
| 1609.6.4.41 COMPONENTS & CLADDING. FLORIDA DEPARTMENT |
| OF COMMUNITY AFFAIRS RULE 9N-3 NOV. 01/ 2010 (31) |
| SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION SYSTEMS THAT |
| WILL REQUIRE PRODUCT APPROVALS: |
| MISSING REPORTS: |
| (31)(B) WINDOW REPORT ONLY COVER SHEET SUBMITTED. |
| (D) ROOFING PRODUCTS AND ASSEMBLIES |
| (G) PRE-ENGINEERED A/C STANDS |
| |
| 7) NO MEP PLANS SUBMITTED!!! OLD SHEETS SHEET SHEET M-1 |
| INDICATE THE USE OF ROOF STANDS, M2 INDICATES THE ROOF |
| STANDS BEING TIED DOWN TO A CONCRETE DECK PLEASE |
| PROVIDE LOCATION OR ARE THEY BEING PLACED ON THE NEW |
| WOOD DECKS? ADDITIONAL INFORMATION REQUIRED. 107.2.1.3. |
| |
| 8) BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT |
| FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL |
| PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND |
| A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT |
| APPLICATION. PLEASE CALL (561)233-5025 FOR MORE |
| INFORMATION. |
| |
| JAMES A. WITMER CBO |
| SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| TEL: 561-805-6715 |
| FAX: 561-805-6676 |
| E-MAIL: [email protected] |
| CONSTRUCTION SERVICES HOME PAGE |
| HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP |
| |
| PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS |
| LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS |
| REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO |
| THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE |
| THEREFORE SUBJECT TO PUBLIC DISCLOSURE. |
| |
| MEMBER OF BOAF: BUILDING OFFICIALS ASSOCIATION OF |
| FLORIDA SAVING LIVES AND PROPERTY SINCE 1953 |
| |
| |