2014-07-01 07:24:11PLUMBING PLAN REVIEW
 PERMIT: 14060286
 ADD: 1220 ORTEGA RD
 CONT: WILBUR HOBGOOD CONST.
 TEL: (561)691-9686
 2010 FLORIDA BUILDING CODE W
 * WEST PALM BEACH ADMINISTRATIVE AMENDMENTS
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: JULY 01/ 2014
 ACTION: DENIED
  
 1) THE NEW ACCESSIBLE RESTROOM DOES NOT MEET THE
 ACCEESSIBLE RESTROOMDIMENSIONAL REQUIREMENTS. THERE IS
 A DISCREPANCY IN THE PLANS SHEET A5 SHOWS A DIMENTION
 OF 6'-10" SHEET DETAIL ON SHEET A9 SHOWS THIS SAME WALL
 5'-9". THE MINIMUM DIMENSION FOR THE FIXTURE SET WALL
 IS 7'-01/2". 2010 FBC- ACCESSIBILITY CODE 604.2 &
 604.3.2 & FIGURE 604.8.1.6.
  
 2) 2010 WEST PALM BEACH CHAPTER 1 ADMINISTRATION LOCAL
 AMENDMENTS TO THE FLORIDA BUILDING CODE, 107.3.5
 MINIMUM PLAN REVIEW CRITERIA FOR BUILDINGS.
 107.3.5.1 COMMERCIAL BUILDINGS:
 107.3.5.1.3 PLUMBING
 1. MINIMUM PLUMBING FACILITIES
 2. FIXTURE REQUIREMENTS
 3. WATER SUPPLY PIPING
 4. SANITARY DRAINAGE
 6. VENTS
 13. PLUMBING RISER
  
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676