Plan Review Notes For Permit 14060286 |
Permit Number |
14060286 |
|
Review Stop |
P |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2014-07-01 07:24:11 | PLUMBING PLAN REVIEW | | PERMIT: 14060286 | | ADD: 1220 ORTEGA RD | | CONT: WILBUR HOBGOOD CONST. | | TEL: (561)691-9686 | | 2010 FLORIDA BUILDING CODE W | | * WEST PALM BEACH ADMINISTRATIVE AMENDMENTS | | | | 2010 EXISTING BUILDING CODE LEVEL II 701.3 | | COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, | | SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS | | OF THE FLORIDA BUILDING CODE, BUILDING. | | | | 1ST REVIEW | | DATE: JULY 01/ 2014 | | ACTION: DENIED | | | | 1) THE NEW ACCESSIBLE RESTROOM DOES NOT MEET THE | | ACCEESSIBLE RESTROOMDIMENSIONAL REQUIREMENTS. THERE IS | | A DISCREPANCY IN THE PLANS SHEET A5 SHOWS A DIMENTION | | OF 6'-10" SHEET DETAIL ON SHEET A9 SHOWS THIS SAME WALL | | 5'-9". THE MINIMUM DIMENSION FOR THE FIXTURE SET WALL | | IS 7'-01/2". 2010 FBC- ACCESSIBILITY CODE 604.2 & | | 604.3.2 & FIGURE 604.8.1.6. | | | | 2) 2010 WEST PALM BEACH CHAPTER 1 ADMINISTRATION LOCAL | | AMENDMENTS TO THE FLORIDA BUILDING CODE, 107.3.5 | | MINIMUM PLAN REVIEW CRITERIA FOR BUILDINGS. | | 107.3.5.1 COMMERCIAL BUILDINGS: | | 107.3.5.1.3 PLUMBING | | 1. MINIMUM PLUMBING FACILITIES | | 2. FIXTURE REQUIREMENTS | | 3. WATER SUPPLY PIPING | | 4. SANITARY DRAINAGE | | 6. VENTS | | 13. PLUMBING RISER | | | | THANK YOU FOR YOUR ANTICIPATED COOPERATION. | | | | JAMES A. WITMER CBO | | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER | | TEL: 561-805-6715 | | FAX: 561-805-6676 | | E-MAIL: [email protected] |
|