2014-06-30 17:03:28 | DATE: 6/30/2014 |
| PROJECT: ERNESTON |
| PERMIT#: 14060236 |
| CODE: 2008 EDITION OF THE NEC |
| 2010 EDITION OF THE FBC |
| 2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1, |
| ADMINISTRATION, 2012 FBC SUPPLEMENTS. |
| |
| 1ST ELECTRICAL PLAN REVIEW |
| ACTION: DENIED |
| |
| THE ADDITION INDICATES NO ELECTRICAL WORK AT ALL. BUT |
| THE FLOOR PLAN INDICATES THE INSTALLATION OF NEW OFFICE |
| AND BATHROOM AREAS. |
| |
| 1) CONSTRUCTION DOCUMENTS SHALL BE OF SUFFICIENT |
| CLARITY TO INDICATE THE LOCATION, NATURE AND EXTENT OF |
| THE WORK PROPOSED AND SHOW IN DETAIL THAT IT WILL |
| CONFORM TO THE PROVISIONS OF THIS CODE AND RELEVANT |
| LAWS, ORDINANCES, RULES AND REGULATIONS, AS DETERMINED |
| BY THE BUILDING OFFICIAL. SUCH DRAWINGS AND |
| SPECIFICATIONS SHALL CONTAIN INFORMATION, IN THE FORM |
| OF NOTES OR OTHERWISE, AS TO THE QUALITY OF MATERIALS, |
| WHERE QUALITY IS ESSENTIAL TO CONFORMITY WITH THE |
| TECHNICAL CODES. FBC 107.2.1 |
| |
| 2) INDICATE ALL LIGHTS AND RECEPTACLE OUTLETS PROPOSED |
| FOR THE NEW CONSTRUCTION AREA. FBC 107.2.1 |
| |
| 3) A SWITCHED LIGHT OUTLET IS REQUIRED AT THE ATTIC |
| ENTRANCE. FBC 306.3.1 |
| |
| 4) AN ILLUMINATED MEANS OF EGRESS SHALL BE PROVIDED FOR |
| ALL BUILDINGS OR STRUCTURES REQUIRED IN CHAPTERS 11 |
| THROUGH 43. NFPA 101 SECTION 7.9 |
| |
| 5) MEANS OF EGRESS SHALL BE MARKED WHERE REQUIRED IN |
| CHAPTERS 11 THROUGH 43. NFPA 101 SECTION 7.10 |
| |
| DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421, |
| 561-805-6717 OR [email protected] |