Plan Review Notes For Permit 14060206 |
Permit Number |
14060206 |
|
Review Stop |
E |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2014-06-14 15:26:30 | DATE: 6/14/2014 | | PROJECT:203 LAKELAND DR. | | PERMIT#: 14060206 | | CODE: 2008 EDITION OF THE NEC | | 2010 EDITION OF THE FBC | | 2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1, | | ADMINISTRATION, 2012 FBC SUPPLEMENTS. | | | | ELECTRICAL PLAN REVIEW | | | | 1ST REVIEW | | ACTION: DENIED | | | | 1) INSIDE PANEL IS EXISTING TO REMAIN. INDICATE ON PLAN | | THE PANEL IS ADAQUATE TO SUPPORT AN UPGRADE TO 200AMPS, | | 2) NO INDICATION IS MADE AS TO THE EXISTING FEEDERS. | | INDICATE ON PLANS THAT THE EXISTING FEEDERS PREVIOUSLY | | SERVING A 100AMP PANEL THAT IT HAS THE CAPACITY | | ADAQUATE TO SUPPORT THE UPGRADE TO 200AMP. | | 3) THE SAME HOLDS TRUE FOR THE FEEDER CONDUIT/NIPPLE. | | INDICATE ON THE PLAN THE SIZE AND TYPE AND WHETHER A | | BONDING BUSHING IS REQUIRED AND/OR INSTALLED AND IF NOT | | INDICATE THE G=REQUIRED GROUND WIRE AND IT'S SIZE | | RELATING TO THE NEW OCPD. NEC 250.122 | | 4) INDICATE ON THE PLANS IF THE RIER AND WHEATHERHEAD | | ARE EXISTING TO REMAIN OR NEW. SUPPORTS SHOULD BE | | INCLUDED. | | |
|