Plan Review Notes
Plan Review Notes For Permit 14060154
Permit Number 14060154
Review Stop E
Sequence Number 1
Notes
Date Text
2014-06-05 11:33:38ADDRESS: 2400 N. FLAGLER DR WPB
 PERMIT#:14060154
 1ST ELECTRICAL REVIEW
 ACTION: DENIED.
 CODE: 2008 NEC AND 2010 FBC
  
 DEFICIENCIES:
  
 1) PROVIDE VOLTAGE DROP CALCULATION ON PLANS PER FBC
 107.2.1.
 2) PROVIDE ENGINEERING TO INDICATE COMPLIANCE WITH FBC
 WIND LOAD REQUIREMENTS AND INSTALLATION DETAILS. PER
 FBC AND NOTE ON SHEET E-2.
 3) ALTER DETAIL ON SHEET E-2 TO INDICATE ABOVE GRADE
 CONDUIT TO BE SCHEDULE 80 PER THE SPECIFICATION NOTE 20
 ON THE SAME SHEET.
 4) INDICATE BURIAL DEPTH ON PLANS PER, NEC 300.5
  
 DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421.
 561-805-6717 OR [email protected]
  