2014-06-05 11:20:15PLUMBING PLAN REVIEW
 PERMIT: 14060141
 ADD: 1106 FLORIDA AVE.
 CONT: GANNAWAY INC
 TEL: (561)557-3596
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: THURS. JUNE 05/2014
 ACTION: DENIED
  
 1) THE SUBMITTED PLAN DOES NOT SHOW ENOUGH DETAIL TO
 DETERMINE CODE COMPLIANCE. IS THIS BATHROOM LOCATED ON
 THE 1ST FLOOR OF THE RESIDENCE OR 2 ND FLOOR. THE
 PERMIT APPLICATION INDICATES THE RENOVATION OF A
 BATHROOM WHERE AS THE SUBMITTED PLAN APPEARS TO BE A
 POWDER ROOM WITH A LAV AND WATER CLOSET. 2010 WEST PALM
 BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER
 1, ADMINISTRATION CONSTRUCTION DOCUMENTS SHALL BE OF
 SUFFICIENT CLARITY TO INDICATE THE LOCATION, NATURE AND
 EXTENT OF THE WORK PROPOSED AND SHOW IN DETAIL THAT IT
 WILL CONFORM TO THE PROVISIONS OF THIS CODE AND
 RELEVANT LAWS, ORDINANCES, RULES AND REGULATIONS, AS
 DETERMINED BY THE BUILDING OFFICIAL.
  
 PLEASE PROVIDE DOMENSIONS OF THE ROOM AS WELL AS FROM
 THE WALL TO THE CENTER OF FIXTURES. 2010 FBC-R 307.1
 AND FIGURE R307.1 MINIMUM FIXTURE CLEARANCES CAN NOT BE
 DETERMINED.
  
 2) COMPLIANCE WITH MINIMUM SHOWER COMPARTMENT SIZES CAN
 NOT BE DETERMINED 2010 FBC-P2708.1
  
 3) COMPLIANCE WITH 2010 FBC-P2709.2 LINING REQUIRED,
 PLEASE PROVIDE SHOWER PAN LINING MATERIALS.
  
 4) PROVIDE COMPLIANCE WITH 2010 FBC-P BATHTUB AND
 SHOWER SPACES. SHOWER WALLS SHALL BE FINISHED IN
 ACCORDANCE WITH SECTION R307.2. R307.2 BATHTUB AND
 SHOWER SPACES. BATHTUB AND SHOWER FLOORS AND WALLS
 ABOVE BATHTUBS WITH INSTALLED SHOWER HEADS AND IN
 SHOWER COMPARTMENTS SHALL BE FINISHED WITH A
 NONABSORBENT SURFACE. SUCH WALL SURFACES SHALL EXTEND
 TO A HEIGHT OF NOT LESS THAN 6 FEET (1829 MM) ABOVE THE
 FLOOR.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL
 LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH
 A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE
 SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE
 FOUND WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR
 YOUR ANTICIPATED COOPERATION.
  