2014-06-05 11:19:26 | BUILDING PLAN REVIEW |
| PERMIT: 14060141 |
| ADD: 1106 FLORIDA AVE. |
| CONT: GANNAWAY INC |
| TEL: (561)557-3596 |
| |
| 2010 FLORIDA BUILDING CODE W |
| * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION |
| 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013. |
| |
| 2010 EXISTING BUILDING CODE LEVEL II 701.3 |
| COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, |
| SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS |
| OF THE FLORIDA BUILDING CODE, BUILDING. |
| |
| 1ST REVIEW |
| DATE: THURS. JUNE 05/2014 |
| ACTION: DENIED |
| |
| 1) THE SUBMITTED PLAN DOES NOT SHOW ENOUGH DETAIL TO |
| DETERMINE CODE COMPLIANCE. IS THIS BATHROOM LOCATED ON |
| THE 1ST FLOOR OF THE RESIDENCE OR 2 ND FLOOR. THE |
| PERMIT APPLICATION INDICATES THE RENOVATION OF A |
| BATHROOM WHERE AS THE SUBMITTED PLAN APPEARS TO BE A |
| POWDER ROOM WITH A LAV AND WATER CLOSET. 2010 WEST PALM |
| BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER |
| 1, ADMINISTRATION CONSTRUCTION DOCUMENTS SHALL BE OF |
| SUFFICIENT CLARITY TO INDICATE THE LOCATION, NATURE AND |
| EXTENT OF THE WORK PROPOSED AND SHOW IN DETAIL THAT IT |
| WILL CONFORM TO THE PROVISIONS OF THIS CODE AND |
| RELEVANT LAWS, ORDINANCES, RULES AND REGULATIONS, AS |
| DETERMINED BY THE BUILDING OFFICIAL. |
| |
| PLEASE PROVIDE DOMENSIONS OF THE ROOM AS WELL AS FROM |
| THE WALL TO THE CENTER OF FIXTURES. 2010 FBC-R 307.1 |
| AND FIGURE R307.1 MINIMUM FIXTURE CLEARANCES CAN NOT BE |
| DETERMINED. |
| |
| 2) COMPLIANCE WITH MINIMUM SHOWER COMPARTMENT SIZES CAN |
| NOT BE DETERMINED 2010 FBC-P2708.1 |
| |
| 3) COMPLIANCE WITH 2010 FBC-P2709.2 LINING REQUIRED, |
| PLEASE PROVIDE SHOWER PAN LINING MATERIALS. |
| |
| 4) PROVIDE COMPLIANCE WITH 2010 FBC-P BATHTUB AND |
| SHOWER SPACES. SHOWER WALLS SHALL BE FINISHED IN |
| ACCORDANCE WITH SECTION R307.2. R307.2 BATHTUB AND |
| SHOWER SPACES. BATHTUB AND SHOWER FLOORS AND WALLS |
| ABOVE BATHTUBS WITH INSTALLED SHOWER HEADS AND IN |
| SHOWER COMPARTMENTS SHALL BE FINISHED WITH A |
| NONABSORBENT SURFACE. SUCH WALL SURFACES SHALL EXTEND |
| TO A HEIGHT OF NOT LESS THAN 6 FEET (1829 MM) ABOVE THE |
| FLOOR. |
| |
| WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION & |
| REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL |
| LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH |
| A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE |
| SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE |
| FOUND WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR |
| YOUR ANTICIPATED COOPERATION. |
| |
| JAMES A. WITMER CBO |
| SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |