Date |
Text |
2014-07-29 09:51:35 | DATE: 6/21/2014 |
| PROJECT: L.A VINAS M.D |
| PERMIT#: 14060133 |
| CODE: 2008 EDITION OF THE NEC |
| 2010 EDITION OF THE FBC |
| 2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1, |
| ADMINISTRATION, 2012 FBC SUPPLEMENTS. |
| |
| 2ND ELECTRICAL PLAN REVIEW |
| ACTION: DENIED |
| |
| NOTE: THE RE-SUBMITTAL IS NOT OF SUFFICIENT SIZE AND |
| CLARITY TO SHOW APPROPRIATE DETAIL. CONSTRUCTION |
| DOCUMENTS SHALL BE OF SUFFICIENT CLARITY TO INDICATE |
| THE LOCATION, NATURE AND EXTENT OF THE WORK PROPOSED |
| AND SHOW IN DETAIL THAT IT WILL CONFORM TO THE |
| PROVISIONS OF THIS CODE AND RELEVANT LAWS, ORDINANCES, |
| RULES AND REGULATIONS, AS DETERMINED BY THE BUILDING |
| OFFICIAL. FBC 107.2.1 |
| |
| ADDITIONALLY, REQUEST THE DENIED PACKAGE WHEN YOU |
| ARRIVE TO RE-SUBMIT. REPLACE THE CORRECTED PAGES INTO |
| THE SUBMITTAL PACKAGE AND LEAVE THE PREVIOUSLY REVIEWED |
| SHEETS FOR COMPARETIVE REVIEW. . |
| |
| PLEASE INCLUDE ALL THE FOLLOWING DUPLICATE COMMENTS IN |
| THE RESUBMITTAL: |
| |
| 1) INDICATE ALL PATIENT CARE AREAS SHALL BE IN |
| COMPLIANCE WITH ARTICALE 517 OF THE NEC. SEE BELOW: |
| WIRING IN PATIENT CARE AREAS SHALL COMPLY WITH |
| 517.13(A) AND (B). NEC 517.13 |
| (A) ALL BRANCH CIRCUITS SERVING PATIENT CARE AREAS |
| SHALL BE PROVIDED WITH AN EFFECTIVE GROUND FAULT |
| CURRENT PATH BY INSTALLATION IN A METAL RACEWAY SYSTEM |
| OR A CABLE HAVING A METALLIC ARMOR SHEATH ASSEMBLY. THE |
| METAL RACEWAY SYSTEM OR METALLIC CABLE ARMOR OR SHEATH |
| ASSEMBLY SHALL ITSELF QUALIFY AS AN EQUIPMENT GROUNDING |
| CONDUCTOR IN ACCORDANCE WITH 250.118. |
| (B) THE GROUNDING TERMINALS OF ALL RECEPTACLES AND |
| NON-CURRENT-CARRYING CONDUCTIVE SURFACES FIXED |
| ELECTRICAL EQUIPMENT LIKELY TO BECOME ENERGIZED THAT |
| ARE SUBJECT TO PERSONAL CONTACT OPERATING AT OVER 100 |
| VOLTS SHALL BE CONNECTED TO AN INSULATED COPPER |
| EQUIPMENT GROUNDING CONDUCTOR. THE EQUIPMENT GROUNDING |
| CONDUCTOR SHALL BE SIZED IN ACCORDANCE WITH TABLE |
| 250.122 AND INSTALLED IN METAL RACEWAYS OR AS A PART OF |
| LISTED CABLES HAVING A METALLIC ARMOR OR SHEATH |
| ASSEMBLY WITH THE BRANCH CIRCUIT CONDUCTORS SUPPLYING |
| THESE RECEPTACLES OR FIXED EQUIPMENT. |
| |
| 2) RISER DIAGRAM ON SHEET E-1.0 INDICATES A 200AMP MAIN |
| DISCONNECT FEEDING A 200AMP MCB PANEL WITH 3, #1CU IN |
| 1,1/2" CONDUIT PRESUMED TO BE EXISTING AND UNDERGROUND. |
| #1CU THHN IS NOT ADEQUATE TO CONNECT TO A 200AMP OCPD. |
| **# 6 CU IS NOT THE ADAQUATE SIZE TO USE FOR A GEC WHEN |
| USING 3/0 CU SERVICE ENTRANCE CONDUCTORS.** PLEASE |
| REVISE THE RISER TO THE APPROPRIATE SIZE CONDUCTOR AND |
| RACEWAY TO SUPPORT THE LOAD. **RESIZE ALL THE CONDUITS |
| AND CONDUCTORS ON THE LINE SIDE AND ON THE LOAD SIDE |
| FEEDING THE PANEL.INCLUDING THE GROUNDING ELECTRODE |
| CONDUCTOR AND THE EQUIPMENT GROUND CONDUCTORS.* |
| |
| 3) PROVIDE A SAFETY LABELING SCHEDULE FOR ARC FLASH |
| PROTECTION AND FOR THE PANEL BOARDS AND MAIN |
| DISCONNECTING MEANS. NEC 110.22, 110.16, 110.22 |
| |
| 4) PLEASE INDICATE COMPLIANCE WITH FBC-ENERGY. |
| ELECTRICAL POWER AND LIGHTING SYSTEMS. (MANDATORY) |
| SECTION 505 |
| A) INTERIOR LIGHTING CONTROLS. EACH AREA ENCLOSED BY |
| WALLS OR FLOOR-TO-CEILING PARTITIONS SHALL HAVE AT |
| LEAST ONE CONTROL DEVICE TO INDEPENDENTLY CONTROL THE |
| GENERAL LIGHTING WITHIN THE SPACE. EACH MANUAL DEVICE |
| SHALL BE READILY ACCESSIBLE AND LOCATED SO THE |
| OCCUPANTS CAN SEE THE CONTROLLED LIGHTING. 505.2.1 |
| B) BUILDINGS LARGER THAN 5000SQ.FT. SHALL BE EQUIPPED |
| WITH AN AUTOMATIC CONTROL DEVICE TO SHUT OFF LIGHTING |
| IN THOSE AREAS. THIS AUTOMATIC CONTROL DEVICE SHALL |
| FUNCTION ON EITHER; |
| 1) A SCHEDULED BASIS, USING TIME OF DAY, WITH AN |
| INDEPENDENT PROGRAM SCHEDULE THAT CONTROLS THE INTERIOR |
| LIGHTING IN THE AREAS THAT DO NOT EXCEED 25000SQFT AND |
| ARE NOT MORE THAN ONE FLOOR; OR |
| 2) AN OCCUPANT SENSOR THAT SHALL TURN LIGHTING OFF |
| WITHIN 30 MINUTES OF AN OCCUPANT LEAVING A SPACE; OR |
| 3) A SIGNAL FROM ANOTHER CONTROL OR ALARM SYSTEM THAT |
| INDICATES THE AREA IS UNOCCUPIED. 505.2.2, |
| C) PROVIDE A LIGHTING DENSITY SUMMARY ON THE PLAN |
| SHOWING COMPLIANCE WITH THE FBC ENERGY 505.5.3 |
| |
| SEPARATE PERMITS WITH SHOP DRAWINGS REQUIRED FOR FIRE |
| ALARM, SECURITY, CCTV, AUDIO/VIDEO, NETWORK, AND SIGNS. |
| |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. SEE LINK: |
| |
| HTTP://WPB.ORG/DEVELOPMENT/WP-CONTENT/UPLOADS/SITES/33/ |
| 2013/09/APPLICATION_RESUBMITTAL_FORM_04132010.PDF |
| |
| DAVID HAYES, ELECTRICAL PLANS EXAMINER. 561-805-6717, |
| [email protected]. |