Plan Review Notes
Plan Review Notes For Permit 14060133
Permit Number 14060133
Review Stop E
Sequence Number 1
Notes
Date Text
2014-06-23 07:25:18DATE: 6/21/2014
 PROJECT:
 PERMIT#:
 CODE: 2008 EDITION OF THE NEC
 2010 EDITION OF THE FBC
 2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1,
 ADMINISTRATION, 2012 FBC SUPPLEMENTS.
  
 1ST ELECTRICAL PLAN REVIEW
 ACTION: DENIED
  
 1) INDICATE ALL PATIENT CARE AREAS SHALL BE IN
 COMPLIANCE WITH ARTICALE 517 OF THE NEC. SEE BELOW:
 WIRING IN PATIENT CARE AREAS SHALL COMPLY WITH
 517.13(A) AND (B). NEC 517.13
 (A) ALL BRANCH CIRCUITS SERVING PATIENT CARE AREAS
 SHALL BE PROVIDED WITH AN EFFECTIVE GROUND FAULT
 CURRENT PATH BY INSTALLATION IN A METAL RACEWAY SYSTEM
 OR A CABLE HAVING A METALLIC ARMOR SHEATH ASSEMBLY. THE
 METAL RACEWAY SYSTEM OR METALLIC CABLE ARMOR OR SHEATH
 ASSEMBLY SHALL ITSELF QUALIFY AS AN EQUIPMENT GROUNDING
 CONDUCTOR IN ACCORDANCE WITH 250.118.
 (B) THE GROUNDING TERMINALS OF ALL RECEPTACLES AND
 NON-CURRENT-CARRYING CONDUCTIVE SURFACES FIXED
 ELECTRICAL EQUIPMENT LIKELY TO BECOME ENERGIZED THAT
 ARE SUBJECT TO PERSONAL CONTACT OPERATING AT OVER 100
 VOLTS SHALL BE CONNECTED TO AN INSULATED COPPER
 EQUIPMENT GROUNDING CONDUCTOR. THE EQUIPMENT GROUNDING
 CONDUCTOR SHALL BE SIZED IN ACCORDANCE WITH TABLE
 250.122 AND INSTALLED IN METAL RACEWAYS OR AS A PART OF
 LISTED CABLES HAVING A METALLIC ARMOR OR SHEATH
 ASSEMBLY WITH THE BRANCH CIRCUIT CONDUCTORS SUPPLYING
 THESE RECEPTACLES OR FIXED EQUIPMENT.
  
 2) RISER DIAGRAM ON SHEET E-1.0 INDICATES A 200AMP MAIN
 DISCONNECT FEEDING A 200AMP MCB PANEL WITH 3, #1CU IN
 1,1/2" CONDUIT PRESUMED TO BE EXISTING AND UNDERGROUND.
 #1CU THHN IS NOT ADEQUATE TO CONNECT TO A 200AMP OCPD.
 PLEASE REVISE THE RISER TO THE APPROPRIATE SIZE
 CONDUCTOR AND RACEWAY TO SUPPORT THE LOAD.
  
 3) PROVIDE A SAFETY LABELING SCHEDULE FOR ARC FLASH
 PROTECTION AND FOR THE PANEL BOARDS AND MAIN
 DISCONNECTING MEANS. NEC 110.22, 110.16, 110.22
  
 4) PLEASE INDICATE COMPLIANCE WITH FBC-ENERGY.
 ELECTRICAL POWER AND LIGHTING SYSTEMS. (MANDATORY)
 SECTION 505
 A) INTERIOR LIGHTING CONTROLS. EACH AREA ENCLOSED BY
 WALLS OR FLOOR-TO-CEILING PARTITIONS SHALL HAVE AT
 LEAST ONE CONTROL DEVICE TO INDEPENDENTLY CONTROL THE
 GENERAL LIGHTING WITHIN THE SPACE. EACH MANUAL DEVICE
 SHALL BE READILY ACCESSIBLE AND LOCATED SO THE
 OCCUPANTS CAN SEE THE CONTROLLED LIGHTING. 505.2.1
 B) BUILDINGS LARGER THAN 5000SQ.FT. SHALL BE EQUIPPED
 WITH AN AUTOMATIC CONTROL DEVICE TO SHUT OFF LIGHTING
 IN THOSE AREAS. THIS AUTOMATIC CONTROL DEVICE SHALL
 FUNCTION ON EITHER;
 1) A SCHEDULED BASIS, USING TIME OF DAY, WITH AN
 INDEPENDENT PROGRAM SCHEDULE THAT CONTROLS THE INTERIOR
 LIGHTING IN THE AREAS THAT DO NOT EXCEED 25000SQFT AND
 ARE NOT MORE THAN ONE FLOOR; OR
 2) AN OCCUPANT SENSOR THAT SHALL TURN LIGHTING OFF
 WITHIN 30 MINUTES OF AN OCCUPANT LEAVING A SPACE; OR
 3) A SIGNAL FROM ANOTHER CONTROL OR ALARM SYSTEM THAT
 INDICATES THE AREA IS UNOCCUPIED. 505.2.2,
 C) PROVIDE A LIGHTING DENSITY SUMMARY ON THE PLAN
 SHOWING COMPLIANCE WITH THE FBC ENERGY 505.5.3
  
 SEPARATE PERMITS WITH SHOP DRAWINGS REQUIRED FOR FIRE
 ALARM, SECURITY, CCTV, AUDIO/VIDEO, NETWORK, AND SIGNS.
  
 DAVID HAYES, ELECTRICAL PLANS EXAMINER. 561-805-6717,
 [email protected].