2014-09-10 11:26:22 | DATE: 9/10/2014 |
| PROJECT: 249 ALPINE RD |
| PERMIT#: 14060052 |
| CODE: 2008 EDITION OF THE NEC |
| 2010 EDITION OF THE FBC |
| 2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1, |
| ADMINISTRATION, 2012 FBC SUPPLEMENTS. |
| |
| 2ND ELECTRICAL PLAN REVIEW |
| ACTION: DENIED |
| |
| 1) A RISER DIAGRAM IS REQUIRED TO INDICATE THE LOCATION |
| OF THE SERVICE ENTRANCE DISCONNECTING MEANS. PROVIDE A |
| MAIN SERVICE DISCONNECT AT A READILY ACCESSIBLE |
| LOCATION NEAREST THE POINT OF ENTRANCE OF THE SERVICE |
| CONDUCTORS. NEC 230.70, NEC 215.5, WPB AMENDMENTS TO |
| THE FBC 107.3.5, |
| |
| 2) A PANEL SCHEDULE IS REQUIRED TO INDICATE THE CIRCUIT |
| OCPD SIZE AND CIRCUIT NUMBER. FLOOR PLAN TO BE |
| IDENTIFIED WITH THE CIRCUIT NUMBERS CORESPONDING TO THE |
| PANEL SCHEDULE IN ORDER TO DETERMINE THE CIRCUIT AND |
| WIRE SIZES CORESPONDING TO THE OUTLET OR EQUIPMENT |
| CONNECTED. NEC 215.5, WPB AMENDMENTS TO THE FBC 107.3.5 |
| |
| 3) CARBON MONOXIDE DETECTORS REQUIRED WITHIN 10' OF |
| SLEEPING AREA. FBC 315 |
| |
| 4) ALL 125V SINGLE PHASE, 15 AND 20AMP RECEPTACLES |
| INSTALLED IN THE LOCATIONS SPECIFIED IN (1) THROUGH (8) |
| SHALL HAVE GROUND FAULT CIRCUIT INTERRUPTER PROTECTION |
| FOR PERSONNEL. ALL OUTLETS IN THE GARAGE SHALL BE GFCI |
| PROTECTED INCLUDING THE GDO OUTLET. |
| |
| 5) PLANS FAIL TO INDICATE COMPLIANCE WITH SECTION |
| 210.11 (C)(3) BATHROOM BRANCH CIRCUITS IN ADDITION TO |
| THE NUMBER OF BRANCH CIRCUITS REQUIRED BY OTHER PARTS |
| OF THIS SECTION, AT LEAST ONE 20-AMPERE BRANCH CIRCUIT |
| SHALL BE PROVIDED TO SUPPLY BATHROOM RECEPTACLE |
| OUTLET(S). SUCH CIRCUITS SHALL HAVE NO OTHER OUTLETS. |
| |
| 6) LUMINAIRES IN CLOTHES CLOSETS SHALL BE INSTALLED IN |
| ACCORDANCE WITH THE PROVISIONS OF THE NEC 410.16(A) AND |
| (B). VERIFY THIS CRITERIA IS MET IN ALL CLOTHES CLOSETS |
| WITH LUMINAIRES. |
| |
| 7) SUFFICIENT ACCESS AND WORKING SPACE SHALL BE |
| PROVIDED AND MAINTAINED ABOUT ALL ELECTRICAL EQUIPMENT |
| TO PERMIT READY AND SAFE OPERATION AND MAINTENANCE OF |
| SUCH EQUIPMENT. NEC 110.26 |
| VERIFY THIS CRITERIA IS MET AT THE ELECTRICAL PANEL IN |
| THE HALLWAY ENTRANCE AND AT ALL ELECTRICAL EQUIPMENT |
| REQUIRING ACCESS FOR SERVICE AND MAINTENANCE. |
| |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. SEE LINK: |
| HTTP://WPB.ORG/DEVELOPMENT/WP-CONTENT/UPLOADS/SITES/33/ |
| 2013/09/APPLICATION_RESUBMITTAL_FORM_04132010.PDF |
| |
| ADDITIONALLY, PLEASE INSERT CORRECTED PAGES INTO |
| SUBMITTAL PACKAGE AND LEAVE THE PREVIOUSLY REVIEWED |
| SHEETS FOR COMPARATIVE REVIEW. |
| |
| DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421, |
| 561-805-6717 OR [email protected] |
| |