2014-09-10 11:26:22DATE: 9/10/2014
 PROJECT: 249 ALPINE RD
 PERMIT#: 14060052
 CODE: 2008 EDITION OF THE NEC
 2010 EDITION OF THE FBC
 2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1,
 ADMINISTRATION, 2012 FBC SUPPLEMENTS.
  
 2ND ELECTRICAL PLAN REVIEW
 ACTION: DENIED
  
 1) A RISER DIAGRAM IS REQUIRED TO INDICATE THE LOCATION
 OF THE SERVICE ENTRANCE DISCONNECTING MEANS. PROVIDE A
 MAIN SERVICE DISCONNECT AT A READILY ACCESSIBLE
 LOCATION NEAREST THE POINT OF ENTRANCE OF THE SERVICE
 CONDUCTORS. NEC 230.70, NEC 215.5, WPB AMENDMENTS TO
 THE FBC 107.3.5,
  
 2) A PANEL SCHEDULE IS REQUIRED TO INDICATE THE CIRCUIT
 OCPD SIZE AND CIRCUIT NUMBER. FLOOR PLAN TO BE
 IDENTIFIED WITH THE CIRCUIT NUMBERS CORESPONDING TO THE
 PANEL SCHEDULE IN ORDER TO DETERMINE THE CIRCUIT AND
 WIRE SIZES CORESPONDING TO THE OUTLET OR EQUIPMENT
 CONNECTED. NEC 215.5, WPB AMENDMENTS TO THE FBC 107.3.5
  
 3) CARBON MONOXIDE DETECTORS REQUIRED WITHIN 10' OF
 SLEEPING AREA. FBC 315
  
 4) ALL 125V SINGLE PHASE, 15 AND 20AMP RECEPTACLES
 INSTALLED IN THE LOCATIONS SPECIFIED IN (1) THROUGH (8)
 SHALL HAVE GROUND FAULT CIRCUIT INTERRUPTER PROTECTION
 FOR PERSONNEL. ALL OUTLETS IN THE GARAGE SHALL BE GFCI
 PROTECTED INCLUDING THE GDO OUTLET.
  
 5) PLANS FAIL TO INDICATE COMPLIANCE WITH SECTION
 210.11 (C)(3) BATHROOM BRANCH CIRCUITS IN ADDITION TO
 THE NUMBER OF BRANCH CIRCUITS REQUIRED BY OTHER PARTS
 OF THIS SECTION, AT LEAST ONE 20-AMPERE BRANCH CIRCUIT
 SHALL BE PROVIDED TO SUPPLY BATHROOM RECEPTACLE
 OUTLET(S). SUCH CIRCUITS SHALL HAVE NO OTHER OUTLETS.
  
 6) LUMINAIRES IN CLOTHES CLOSETS SHALL BE INSTALLED IN
 ACCORDANCE WITH THE PROVISIONS OF THE NEC 410.16(A) AND
 (B). VERIFY THIS CRITERIA IS MET IN ALL CLOTHES CLOSETS
 WITH LUMINAIRES.
  
 7) SUFFICIENT ACCESS AND WORKING SPACE SHALL BE
 PROVIDED AND MAINTAINED ABOUT ALL ELECTRICAL EQUIPMENT
 TO PERMIT READY AND SAFE OPERATION AND MAINTENANCE OF
 SUCH EQUIPMENT. NEC 110.26
 VERIFY THIS CRITERIA IS MET AT THE ELECTRICAL PANEL IN
 THE HALLWAY ENTRANCE AND AT ALL ELECTRICAL EQUIPMENT
 REQUIRING ACCESS FOR SERVICE AND MAINTENANCE.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. SEE LINK:
 HTTP://WPB.ORG/DEVELOPMENT/WP-CONTENT/UPLOADS/SITES/33/
 2013/09/APPLICATION_RESUBMITTAL_FORM_04132010.PDF
  
 ADDITIONALLY, PLEASE INSERT CORRECTED PAGES INTO
 SUBMITTAL PACKAGE AND LEAVE THE PREVIOUSLY REVIEWED
 SHEETS FOR COMPARATIVE REVIEW.
  
 DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421,